2017-06-08 15:40:05 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17020219 |
| ADD: 400 N. FLAGLER DR. SUITE: 2302 |
| CONT: PALM BEACH HURRICANE WINDOWS |
| TEL: 561-678-8332 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. JUNE 08/2017 |
| ACTION: DENIED |
| |
| 1) PLEASE PROVIDE ON THE FLOOR PLAN IF THIS IS AN END |
| UNIT OR AN INTERIOR UNIT AWAY FROM THE CORNERS OF THE |
| BUILDING. ADDITIONAL INFORMATION REQUIRED TO BE ABLE TO |
| DETERMINE IF THE SLIDING GLASS DOORS ARE IN WALL END |
| ZONE 5 OR WALL INTERIOR ZONE 4. PRESSURE WILL VARY |
| DRASTICALLY! 107. 2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 2) PLEASE ALSO INDICATE THE SIZE OF THE OPENINGS 1 & 2. |
| PROVIDE HOW MANY PANELS ARE GOING TO MAKE UP EACH |
| OPENING. 107. 2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3A) PLEASE ALSO INDICATE ON THE FLOOR PLAN IF THESE |
| SLIDING GLASS DOORS ARE TO BE INSTALLED AT THE EDGE OF |
| THE CONCRETE SLAB, OR SET BACK AWAY FROM THE EDGE |
| MAKING A PORCH WITH OVERHANG. IF PORCH PLEASE PROVIDE |
| HOW FAR BACK FROM THE EDGE OF THE SLAB WILL THE DOORS |
| ARE INSTALLED? SEE FBC-B 1710.5.1.1 OVERHANG RATIOS FOR |
| HABITABLE SPACES. DOOR ASSEMBLIES INSTALLED WHERE THE |
| OVERHANG (OH) RATIO IS EQUAL TO OR MORE THAN 1 NEED NOT |
| BE TESTED FOR WATER INTRUSION. |
| |
| 3B) SUBMITTED MIAMI-DADE NOA 15-1210.01. IN THE |
| TECHNICAL SHEETS 7 OF 21 PROVIDES THE TABLE B1 SILL |
| HEIGHTS PLEASE CIRCLE THE SILL TO BE INSTALLED FOR THIS |
| INSTALLATION. |
| |
| 4) SUBMITTED MIAMI-DADE NOA 15-1210.01. IN THE |
| TECHNICAL SHEETS 7 OF 21 PROVIDES THE TABLE 1, IDENTIFY |
| PANEL WIDTH, DOOR UNIT HEIGHT, TYPE OF GLAZING, |
| ASSOCIATED PRESSURES & ANCHORS. |
| 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND DOORS |
| SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING |
| SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| THE TESTS. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |