Plan Review Details - Permit 17060200
Plan Review Stops For Permit 17060200
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-08-16 Cont ID  
Sent By jgomez Date 2017-08-16 Time 10:26 Rev Time 0.00
Received By jgomez Date 2017-08-15 Time 14:01 Sent To  
Notes
2017-08-15 14:02:2308/15/17 MET WITH JUNIOR. HE WANTS BUILDING PROVISO TO
 GET PERMIT. REVISION FEES WILL APPLY.
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE ENERGY CALCULATIONS: A)BUILDER'S NAME. B)AREA
 ON ITEM #6 FOR MASTER SUITE & LEISURE ROOM. C)ITEM #9
 IS MISSING LEISURE ROOM. ALSO, ADD FRAMED WALL AREA AT
 MASTER SUITE. D)CEILING AREA ON ITEM #10. E)ROOF TYPE
 IS MISSING THE GABLE. F)REVISE WINDOW ORIENTATION &
 SQUARE FOOTAGE TO MATCH PLANS.
 2- REVISE MASTER BEDROOM EGRESS WINDOW SIZE.
 3- PROVIDE PRODUCT APPROVAL FOR: A) SWING DOOR. NEED
 FL. PRODUCT APPROVAL COVER PAGE. B) LEISURE RM WINDOWS
 NEED TO HAVE HURRICANE IMPACT PROTECTION. NEED SHUTTERS
 PRODUCT APPROVALS AND INSTALLATION SCHEDULE.
 4- ARCHITECT TO APPROVE ALL PRODUCT APPROVALS.
 5- NEED LEISURE RM EXT. DOOR FRAMING DETAIL. SPECIFY
 ALL FRAMING MEMBERS & CONNECTORS.
 6- NEED COPIES OF ANSI Z97.1 TEST DONE FOR THE 3M
 SAFETY FILM SPECIFIED IN THE LEISURE ROOM WINDOWS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-08 Cont ID  
Sent By jgomez Date 2017-08-08 Time 10:20 Rev Time 0.00
Received By jgomez Date 2017-08-07 Time 11:45 Sent To  
Notes
2017-08-07 11:46:10RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AND
 DATE AT THE BOTTOM OF THE FORM AS REQUIRED SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 C) CONDITIONED FLOOR AREA SPECIFIED ON ITEM #6 IS
 INCORRECT. THE NEW A/C AREA IS THE MASTER SUITE AND
 LEISURE ROOM. SEE A/C PLAN. REVISE AS REQUIRED TO MATCH
 PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) WALL TYPES INFORMATION ON ITEM #9 IS MISSING THE
 INFORMATION FOR THE LEISURE ROOM. THIS IS NOT CONCRETE
 BLOCK. ALSO, NEED TO ADD THE FRAMED WALL AREA AT
 EXISTING GARAGE DOOR OPENING TO BE CLOSED. SEE PLANS
 FOR SPECIFIED INSULATION R-VALUE. REVISE AS REQUIRED.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) CEILING AREA ON ITEM #10 NEEDS TO BE COORDINATED
 WITH CORRECT A/C AREA ON ITEM # 1(C) ABOVE. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F) ROOF TYPE SPECIFIED ON PAGE 2 OF 4 IS INCORRECT.
 MISSING THE GABLE END AREA. SEE PLANS AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) CEILING R-VALUE SPECIFIED ON PAGE 2 OF 4 DOESN'T
 MATCH INFORMATION SPECIFIED ON ITEM #10 ON PAGE 1 OF 4
 AND PLANS. REVISE AS REQUIRED TO MATCH. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H) REVISE WINDOWS INFORMATION ON PAGE 3 OF 4 TO MATCH
 PLANS. REVISE WINDOW ORIENTATION AND SQUARE FOOTAGE TO
 MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 NOTE: LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS IS
 REQUIRED WHEN THE CALCULATIONS ARE NOT DONE USING THE
 DEFAULT FACTOR FOR GLAZING.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.
  
 3- NEW MASTER BEDROOM: CLEARLY SPECIFY TYPE AND SIZE OF
 EGRESS WINDOW. AND, PROVIDE MANUFACTURER'S CUT SHEETS
 FOR THE SPECIFIED SIZE (24EH) TO VERIFY COMPLIANCE WITH
 THE EGRESS REQUIREMENTS OF SEC. R310 FBC-RESIDENTIAL.
 ALSO, REVISE THE WINDOW EGRESS NOTE SHOWN ON SHEET A-2
 BELOW THE PROPOSED FLOOR PLAN. THE CODE TO BE
 REFERENCED FOR SINGLE FAMILY RESIDENCES IS THE
 RESIDENTIAL CODE NOT THE BUILDING CODE. THE CORRECT
 SEC. IS R310. ALSO, IS MISSING THE MINIMUM HEIGHT
 DIMENSION. REVISE AS REQUIRED.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL. NO
 INFORMATION WAS SUBMITTED TO VERIFY EGRESS WINDOW
 COMPLIANCE.
  
 4- NEW MASTER BEDROOM: PROVIDE SPECIFICATIONS FOR THE
 INSULATION IN WALLS. NOTE: COORDINATE WITH THE ENERGY
 CALCULATIONS TO AVOID CONFLICTS/DELAYS. SEC. R103.2
 FBC-ENERGY CONSERVATION.
 RESPONSE: CONCRETE BLOCK WALL INSULATION R-VALUE IS NOT
 SPECIFIED. COORDINATE WITH THE ENERGY CALCULATIONS.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) NEW SWING DOOR AS SPECIFIED ON PLANS FOR THE NEW
 LEISURE ROOM.
 RESPONSE: PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE
 THAT CORRESPONDS TO DRAWINGS SUBMITTED. IF THERE IS NOT
 FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA, THEN
 MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL.
 COMPLETE ORIGINAL ENGINEERED PACKAGE WILL BE REQUIRED.
  
 B) THE WINDOWS IN THE NEW LEISURE ROOM NEED TO HAVE
 HURRICANE IMPACT PROTECTION AS REQUIRED BY SEC.
 R301.2.1.2 FBC-RESIDENTIAL. SHOW COMPLIANCE. IF THE
 WINDOWS ARE NON-IMPACT, THEN SHUTTERS ARE REQUIRED. IF
 SHUTTERS ARE REQUIRED, THEN, PROVIDE SHUTTERS PRODUCT
 APPROVALS AND COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
 6- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 ( NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: PLEASE PLACE REVIEW STAMP ON THE COVER OF THE
 PRODUCT APPROVAL NOT ON THE BACK OF THE FRONT PAGE.
 STAMPS ON THE BACK OF THE FRONT PAGE ARE NOT PRACTICAL
 FOR THE CITY RECORDS RETENTION PROCEDURE.
  
 7- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE NEW LEISURE ROOM EXTERIOR DOOR. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS. SEC. R301.1
 FBC-RESIDENTIAL.
 RESPONSE: PROVIDE COMPLETE FRAMING DETAIL. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS.
  
 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL THE LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. REVISE VALUATION AS REQUIRED AND INCLUDE
 THE DESIGN PROFESSIONAL FEES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 9- PROVIDE COPIES OF TESTING DONE FOR 3M SAFETY FILM.
 WINDOWS IN THE LEISURE ROOM BY THE NEW WASHER/DRYER
 NEED TO HAVE SAFETY GLASS AS REQUIRED BY SEC. R308.4.2
 FBC-RESIDENTIAL. SHOW COMPLIANCE WITH THIS REQUIREMENT.
 NOTE: PROVIDE COPIES OF TESTING DONE FOR THE 3M SAFETY
 FILM AS REQUIRED BY SEC. R308.3.1 FBC-RESIDENTIAL.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS TO PLANS. SUBMIT OLD
 DRAWINGS FOR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-30 Cont ID  
Sent By jgomez Date 2017-06-30 Time 10:53 Rev Time 0.00
Received By jgomez Date 2017-06-30 Time 10:52 Sent To  
Notes
2017-06-30 11:11:37RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE ENERGY CALCULATIONS ( 2 COPIES) AS REQUIRED
 BY SEC. R101.4.3 AND R101.4.4 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
 NOTE: ENERGY CALCULATIONS TO INCLUDE THE GARAGE
 CONVERSION AND THE ENCLOSED PORCH CONVERSION. SEE ITEM
 #3 BELOW.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.
 NOTE: THIS IS FOR THE CONVERSION OF GARAGE TO MASTER
 BEDROOM AND ENCLOSED PORCH TO LEISURE ROOM.
  
 3- REVISE THE LEVEL OF ALTERATION AND SCOPE OF WORK
 SPECIFIED ON SHEET A-1 TO INCLUDE CHANGE OF OCCUPANCY.
 THE EXISTING GARAGE CONVERSION TO MASTER BEDROOM AND
 THE EXISTING ENCLOSED PORCH CONVERSION TO LEISURE ROOM.
 SEC. 506 FBC-EXISTING BUILDING, 5TH EDITION (2014).
  
 4- NEW MASTER BEDROOM: CLEARLY SPECIFY TYPE OF EGRESS
 WINDOW. AND, PROVIDE MANUFACTURER'S CUT SHEETS FOR THE
 SPECIFIED SIZE (24EH) TO VERIFY COMPLIANCE WITH THE
 EGRESS REQUIREMENTS OF SEC. R310 FBC-RESIDENTIAL. ALSO,
 REVISE THE WINDOW EGRESS NOTE SHOWN ON SHEET A-2 BELOW
 THE PROPOSED FLOOR PLAN. THE CODE TO BE REFERENCED FOR
 SINGLE FAMILY RESIDENCES IS THE RESIDENTIAL CODE NOT
 THE BUILDING CODE. THE CORRECT SEC. IS R310. ALSO, IS
 MISSING THE MINIMUM HEIGHT DIMENSION. REVISE AS
 REQUIRED.
  
 5- SPECIFY CARBON MONOXIDE ALARMS BY ALL THE BEDROOMS
 AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 6- WINDOWS IN THE LEISURE ROOM BY THE NEW WASHER/DRYER
 NEED TO HAVE SAFETY GLASS AS REQUIRED BY SEC. R308.4.2
 FBC-RESIDENTIAL. SHOW COMPLIANCE WITH THIS REQUIREMENT.
  
 7- NEW LEISURE ROOM: PROVIDE SPECIFICATIONS FOR THE
 INSULATION IN WALLS AND CEILING. NOTE: COORDINATE WITH
 THE ENERGY CALCULATIONS TO AVOID CONFLICTS/DELAYS. SEC.
 R103.2 FBC-ENERGY CONSERVATION.
  
 8- NEW MASTER BEDROOM: PROVIDE SPECIFICATIONS FOR THE
 INSULATION IN WALLS. NOTE: COORDINATE WITH THE ENERGY
 CALCULATIONS TO AVOID CONFLICTS/DELAYS. SEC. R103.2
 FBC-ENERGY CONSERVATION.
  
 9- INSULATION VALUE SPECIFIED IN THE FLOOR PLAN IN
 SHEET A-2 DOESN'T MATCH INSULATION VALUE SPECIFIED IN
 THE SECTION SHOWN IN SHEET A-3. REVISE AS REQUIRED TO
 MATCH. COORDINATE WITH THE ENERGY CALCULATIONS. SEC.
 107.2.1 CITY AMENDMENTS.
  
 10- SECTION DETAILS IN SHEET A-3: R-30 BATT INSULATION
 IS 9-1/2" THICK +/-. SPECIFY SIZE OF FRAMING MEMBERS TO
 VERIFY THAT R-30 BATT INSULATION WILL FIT AND WILL ALSO
 ALLOW THE 1" CLEARANCE FOR ATTIC VENTILATION AS
 REQUIRED BY SEC. R806.3 FBC-RESIDENTIAL. NOTE:
 COORDINATE INSULATION VALUE WITH THE ENERGY
 CALCULATIONS.
  
 11- DEMOLITION PLAN IN SHEET A-3: THE LEISURE ROOM IS
 THE PROPOSED USE OF THIS ROOM. CURRENTLY THIS IS AN
 ENCLOSED PORCH NOT LEISURE ROOM. REVISE NAME OF ROOM AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) NEW WINDOW AS SPECIFIED ON PLANS FOR THE NEW MASTER
 BEDROOM.
  
 B) NEW SWING DOOR AS SPECIFIED ON PLANS FOR THE NEW
 LEISURE ROOM.
  
 C) SHUTTERS IF WINDOW AND DOOR DON'T HAVE IMPACT
 GLAZING. AND, PROVIDE COMPLETE INSTALLATION SCHEDULE.
 SEE CITY SAMPLE.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS FOR THE FRAMING OF EXTERIOR WALLS. PROVIDE
 ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE
 SHOWING THE SPECIFIED CONNECTOR OR ARCHITECT TO LIST
 THE FLORIDA PRODUCT APPROVAL NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 13- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN
 WRITING ( NOT SIGNING AND SEALING) ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 14- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE NEW LEISURE ROOM EXTERIOR DOOR. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 15- PROVIDE COMPLIANCE WITH THE HEATING REQUIREMENTS OF
 SEC. R303.9 FBC-RESIDENTIAL FOR THE NEW MASTER BEDROOM.
  
 16- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL THE LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. REVISE VALUATION AS REQUIRED AND INCLUDE
 THE DESIGN PROFESSIONAL FEES.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS TO PLANS. SUBMIT OLD
 DRAWINGS FOR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-16 Cont ID  
Sent By jleahy Date 2017-08-16 Time 09:11 Rev Time 0.00
Received By jleahy Date 2017-08-16 Time 09:11 Sent To  
Notes
2017-08-07 11:44:18REVISED DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-06-20 Cont ID  
Sent By jleahy Date 2017-06-20 Time 11:04 Rev Time 0.00
Received By jleahy Date 2017-06-20 Time 11:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-16 Cont ID  
Sent By jgomez Date 2017-08-16 Time 12:06 Rev Time 0.00
Received By jgomez Date 2017-08-01 Time 14:35 Sent To  
Notes
2017-08-09 14:09:2908/09/17 CONTRACTOR SIGNED OUT ONE SET OF PLANS FOR
 IMPACT FEES. APPLICATION AND SECOND SET ON JULIO'S
 DESK. JG.
2017-08-02 14:35:38R05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-30 Cont ID  
Sent By jgomez Date 2017-06-30 Time 17:51 Rev Time 0.00
Received By jgomez Date 2017-06-06 Time 10:17 Sent To  
Notes
2017-06-07 10:17:31R20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2017-08-15 Cont ID  
Sent By jgomez Date 2017-08-15 Time 14:54 Rev Time 0.00
Received By jgomez Date 2017-08-15 Time 14:54 Sent To  
Notes
2017-08-15 14:56:48NO FEES DUE. MU-2017-22630 PLANS STAMPED BY DB.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-08-08 Cont ID  
Sent By jgomez Date 2017-08-08 Time 12:24 Rev Time 0.00
Received By jgomez Date 2017-08-08 Time 12:24 Sent To  
Notes
2017-08-08 12:24:271- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.
 NOTE: THIS IS FOR THE CONVERSION OF GARAGE TO MASTER
 BEDROOM AND ENCLOSED PORCH TO LEISURE ROOM.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-06-30 Cont ID  
Sent By jgomez Date 2017-06-30 Time 13:36 Rev Time 0.00
Received By jgomez Date 2017-06-30 Time 13:36 Sent To  
Notes
2017-06-30 13:37:061- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.
 NOTE: THIS IS FOR THE CONVERSION OF GARAGE TO MASTER
 BEDROOM AND ENCLOSED PORCH TO LEISURE ROOM.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2017-08-15 Cont ID  
Sent By jgomez Date 2017-08-15 Time 14:25 Rev Time 0.00
Received By jgomez Date 2017-08-15 Time 14:25 Sent To  
Notes
2017-08-15 14:26:5008/15/17 MET WITH JUNIOR. HE SAID MECHANICAL CONTRACTOR
 TO SUBMIT ALL THE INFORMATION UNDER A SEPARATE PERMIT.
 JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-08 Cont ID  
Sent By jgomez Date 2017-08-08 Time 10:56 Rev Time 0.00
Received By jgomez Date 2017-08-08 Time 10:56 Sent To  
Notes
2017-08-08 10:58:32RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 NO MECHANICAL INFORMATION WAS SUBMITTED FOR THE FIRST
 REVIEW. THIS IS THE FIRST TIME MECHANICAL INFORMATION
 IS SUBMITTED.
  
 1- A/C DRAWING SUBMITTED HAS A COPY OF THE ARCHITECT'S
 SEAL AND SIGNATURE. A/C PLANS NEEDS TO HAVE THE
 ORIGINAL SEAL AND SIGNATURE OF THE ARCHITECT SHOWN ON
 THE TITLE BLOCK AS REQUIRED BY CHAPTER 481 F.S. WHEN
 SUBMITTING DRAWINGS FOR PUBLIC RECORDS.
  
 2- THE LEISURE ROOM NEEDS TO COMPLY WITH THE BALANCED
 RETURN AIR SECTION M1602.4 FBC-RESIDENTIAL. 5TH EDITION
 (2014). REVISE A/C PLAN AS REQUIRED.
  
 3- IT LOOKS LIKE THE RETURN AIR GRILL SHOWN ON THE
 LIVING ROOM IS TOO CLOSE TO THE EXISTING FIREPLACE. IT
 LOOKS LIKE IT'S LESS THAN 10 FEET. THIS IS A PROHIBITED
 LOCATION. REVISE AS REQUIRED. SEC. M1602.2
 FBC-RESIDENTIAL.
  
 4- EQUIPMENT SIZING CALCULATIONS SUBMITTED:
 A) PLAN FOR A/C SUBMITTED SHOWS THAT AIR IS DISTRIBUTED
 TO ALL ROOMS, INCLUDING THE LEISURE ROOM. CALCULATIONS
 SUBMITTED DON'T INCLUDE THIS ROOM. REVISE AS REQUIRED
 TO MATCH PLAN. SEC. R403.6.1 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 B) CFM'S SHOWN ON THE CALCULATIONS DON'T MATCH CFM
 SHOWN ON A/C PLAN. REVISE AS REQUIRED TO MATCH. SEC.
 R403.6.1 FBC-ENERGY CONSERVATION.
  
 C) SIZE OF ROOMS AND AREA OF ROOMS DON'T MATCH PLANS.
 REVISE AS REQUIRE TO MATCH. SEC. R403.6.1 FBC-ENERGY
 CONSERVATION.
  
 D) COORDINATE ALL THE COMPONENTS OF THE HOUSE WITH
 PLANS. NOT ALL THE WALLS ARE CONCRETE BLOCK WALL. THERE
 ARE SOME WOOD FRAMED WALLS. ALSO, USE THE SOFTWARE
 DEFAULT FACTOR FOR GLAZING U-FACTOR AND SHGC FACTOR OR
 PROVIDE INFORMATION SHOWING THAT THE EXISTING WINDOWS
 HAVE THE SPECIFIED FACTORS. REVISE AS REQUIRED TO MATCH
 PLANS. SEC. R403.6.1 FBC-ENERGY CONSERVATION.
  
 E) PAGE OF 12 OF CALCULATIONS SUBMITTED SPECIFY NATURAL
 GAS FURNACE AS THE HEATING SYSTEM. PLANS DON'T SHOW ANY
 NATURAL GAS FURNACE. REVISE AS REQUIRED TO MATCH PLANS.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS TO PLANS. SUBMIT OLD
 DRAWINGS FOR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-06-30 Cont ID  
Sent By jgomez Date 2017-06-30 Time 17:24 Rev Time 0.00
Received By jgomez Date 2017-06-30 Time 17:24 Sent To  
Notes
2017-06-30 17:24:49NO MECHANICAL WORK SHOWN.

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-16 Cont ID  
Sent By jgomez Date 2017-08-16 Time 12:06 Rev Time 0.00
Received By jgomez Date 2017-08-16 Time 12:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-23 Cont ID  
Sent By gjohnson Date 2017-06-23 Time 10:01 Rev Time 0.00
Received By gjohnson Date 2017-06-21 Time 08:14 Sent To  
Notes
2017-06-23 10:02:081ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE PLUMBING RISER DIAGRAM. PER WPB AMEND
 TO FBC 107.3.5.3(11)
  
 2. THE SHUT OFF VALVES FOR WASHING MACHINE SHALL BE
 ACCESSIBLE WITHOUT MOVING MACHINE. PER FBC RES
 P2903.9.3
  
 3. PAN DRAIN REQUIRED FOR WATER HEATER DRAIN PAN. PER
 FBC RES P2801.5.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-08-15 Cont ID  
Sent By njwira Date 2017-08-15 Time 15:22 Rev Time 0.00
Received By njwira Date 2017-08-15 Time 15:22 Sent To  
Notes
2017-08-07 11:44:06REVISED DRAWINGS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2017-07-05 Cont ID  
Sent By njwira Date 2017-07-05 Time 09:13 Rev Time 0.00
Received By njwira Date 2017-06-12 Time 16:41 Sent To I
Notes
***NONE***