Plan Review Details - Permit 17060169
Plan Review Stops For Permit 17060169
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-07-06 Cont ID  
Sent By wjolin Date 2017-07-06 Time 09:41 Rev Time 0.00
Received By wjolin Date 2017-07-06 Time 09:41 Sent To M
Notes
2017-07-06 09:41:03720 8TH STREET
 TRACKING #17060169
 PERMIT #16060377
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **COMMENTS NOT ADDRESSED FROM PREVIOUS REVIEW.**
  
 SPRINKLER LOCATED 12 FEET FROM WALL OR MISSING
 SPRINKLER PROTECTION IN CLOSET #208, #221, AND #227.
  
 SPRINKLER COVERAGE IN STORAGE ROOM #218 EXCEEDS 130
 SQ.FT.
  
 FLOOR AREA BELOW 8'-0" AFF CEILING IS NOT PROTECTED BY
 THE EXTENDED COVERAGE SPRINKLER LOCATED IN THE 8'-6"
 CEILING FOR WORKROOM #232.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-06 Cont ID  
Sent By wjolin Date 2017-06-06 Time 13:52 Rev Time 0.00
Received By wjolin Date 2017-06-06 Time 13:49 Sent To M
Notes
2017-06-06 14:34:31720 8TH STREET
 TRACKING #17060169
 PERMIT #16060377
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 MISSING SPRINKLER PROTECTION IN CLOSET #208, #221, AND
 #227.
  
 SPRINKLER COVERAGE IN STORAGE ROOM #218 EXCEEDS 130
 SQ.FT.
  
 FLOOR AREA BELOW 8'-0" AFF CEILING IS NOT PROTECTED BY
 THE EXTENDED COVERAGE SPRINKLER LOCATED IN THE 8'-6"
 CEILING FOR WORKROOM #232.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-07-06 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-28 Time 13:16 Sent To  
Notes
2017-06-29 13:17:03RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-06-15 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-05 Time 09:59 Sent To  
Notes
2017-06-06 09:59:57REVISION ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-07-06 Cont ID  
Sent By ccole Date 2017-07-06 Time 12:57 Rev Time 0.00
Received By ccole Date 2017-07-06 Time 12:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-15 Cont ID  
Sent By wjolin Date 2017-06-06 Time 14:56 Rev Time 0.00
Received By ccole Date 2017-06-15 Time 11:56 Sent To  
Notes
2017-06-15 12:12:271ST REVIEW FBC-2014 MECHANICAL
 REVISION PERMIT #17060169
 MASTER #16060377
 6/15/17
  
 1) THE REVISED PLANS MUST BEAR THE SIGNATURE, SEAL, AND
 TITLE BLOCK OF THE ENGINEER OF RECORD- BRIAN J. MASKOL
 PE.- SEE FL. STATUTES SECTION 633.021, AND FAC SECTION
 61G15 23.002
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  