Plan Review Details - Permit 17060045
Plan Review Stops For Permit 17060045
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-08 Cont ID  
Sent By ppetty Date 2017-06-08 Time 08:49 Rev Time 0.00
Received By ppetty Date 2017-06-08 Time 08:49 Sent To  
Notes
2017-06-08 08:50:46NEC 110.3-B NEED LISTING FOR F/A USE
 DENIED K

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-06-05 Cont ID  
Sent By ppetty Date 2017-06-08 Time 08:51 Rev Time 0.00
Received By pleduc Date 2017-06-05 Time 13:54 Sent To E
Notes
2017-06-05 14:00:25THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE FA SHALL BE TESTED PER NFPA 72.
  
 14.4.1.2* REACCEPTANCE TESTING.
 14.4.1.2.1 REACCEPTANCE TESTING SHALL BE PERFORMED AS
 REQUIRED IN 14.4.1.2.1.1 THROUGH 14.4.1.2.1.4.
 14.4.1.2.1.1 WHEN AN INITIATING DEVICE, NOTIFICATION
 APPLIANCE, OR CONTROL RELAY IS ADDED, IT SHALL BE
 FUNCTIONALLY TESTED.
 14.4.1.2.1.2 WHEN AN INITIATING DEVICE, NOTIFICATION
 APPLIANCE, OR CONTROL RELAY IS DELETED, ANOTHER DEVICE,
 APPLIANCE, OR CONTROL RELAY ON THE CIRCUIT SHALL BE
 OPERATED.
 14.4.1.2.1.3 WHEN MODIFICATIONS OR REPAIRS TO CONTROL
 EQUIPMENT HARDWARE ARE MADE, THE CONTROL EQUIPMENT
 SHALL BE TESTED IN ACCORDANCE WITH TABLE 14.4.2.2,
 ITEMS 1(A) AND 1(D).
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-08 Cont ID  
Sent By ppetty Date 2017-06-08 Time 08:51 Rev Time 0.00
Received By ppetty Date 2017-06-01 Time 17:11 Sent To FIRE
Notes
***NONE***