Plan Review Details - Permit 17060032
Plan Review Stops For Permit 17060032
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-11-14 Cont ID  
Sent By jwitmer Date 2017-11-14 Time 09:30 Rev Time 0.00
Received By jwitmer Date 2017-11-14 Time 08:06 Sent To  
Notes
2017-11-14 09:30:122014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060032
 ADD: 444 25TH STREET / UNIT: 3
 CONT: H. LAYTON MAINGUY
 TEL: 954-249-8500
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. NOV. 14/2017
 ACTION: DENIED
  
 1) THE COVERSHEET A-1.0:
 1A-D) COMPLIED.
  
 1E) 2ND REQUEST. THE PLANS HAVE NO SATISFIED THE
 MECHANICAL COMMENTS MAY REQUIRE ADDITIONAL MECHANICAL
 EQUIPMENT EITHER ON THE ROOF OR THROUGH THE WALL. SCOPE
 OF WORK INCLUDES WORK IN A HAIR SALON THAT CONSISTS OF
 THE FOLLOWING AREAS: SHAMPOOS, PEDICURES, NAIL
 POLISHING, WAXING, AND HAIR STYLING. YOU WILL RECEIVE
 COMMENTS FROM THE MECHANICAL PLANS REVIEWER ON THE
 FRESH AIR AND EXHAUST AIR THAT WILL BE REQUIRED FOR
 PEDICURES AND NAIL POLISHING. PLEASE BE AWARE THAT
 EITHER THE FRESH AIR OR EXHAUST AIR WILL BE THROUGH THE
 ROOF AND MAY REQUIRE ADDITIONAL ROOF FRAMING, ANCHORING
 OF ROOF TOP CURBS AND INTAKE AND EXHAUST FANS. NONE OF
 THIS INFORMATION HAS BEEN PROVIDED FOR THIS REVIEW.
 FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF
 TOP FANS
 (G) PRE-ENGINEERED A/C STANDS (POSSIBLY)
  
 2) SEMI COMPLIED. THE PLANS PROVIDE THE WIND SPEED OF
 170 VULT, IMPORTANCE FACTOR OF 1.0, BUILDING RISK
 CATEGORY LL AND EXPOSURE C. THE NOMENCLATURE 160 VUIC
 AND 124 VAST ARE UNKNOWN TERMS.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
 IF THE DESIGNER IS TRYING TO INTERPOLATE BETWEEN
 CONTOUR LINES FOR FIGURE 1609A THE 160 VULT CONTOUR
 LINE IS FURTHER WEST THAN THE CITY LIMITS FOR WEST PALM
 BEACH. INTERPOLATION FOR THIS LOCATION WOULD BE 168
 VULT AND 130 VASD.
  
 3) SHEET A-1.1 SECTION 1 INDICATES A RAISED PLATFORM 11
 INCHES FROM THE FLOOR.
 3A-B) COMPLIED.
  
 3C) 2ND REQUEST. THE RESPONSE LETTER INDICATES THE USE
 OF A PORTABLE PEDICURE SPA IT SHOWS COMPLIANCE WITH THE
 2014 ACCESSIBILITY CODE SECTION 103 EQUIVALENT
 FACILITATION.
 PLEASE PROVIDE HOW A PERSON IN A WHEEL CHAIR IS GOING
 TO ACHIEVE ACCESS TO THE CHAIR ON THE PLATFORM.
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2014 FBC-ACCESS. CODE 202.3 ALTERATIONS. WHERE EXISTING
 ELEMENTS OR SPACES OR COMMON AREAS ARE ALTERED, EACH
 ALTERED ELEMENT, SPACE OR AREA SHALL COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF CHAPTER 2 AND SECTION
 201.1.1.
 2014 ACCESS. CODE. 201.1.1 VERTICAL ACCESSIBILITY.
 SECTIONS 553.501-553.513, F.S., AND THE ADA STANDARDS
 FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY.
  
 4) THE VALUE OF THE PROJECT MAY BE INCREASED BECAUSE OF
 THE REQUIRED, INTAKE AND EXHAUST AIR, FRAMING AND ROOF
 TOP MECHANICAL EQUIPMENT. WITH THE INCREASED VALUE THE
 VALUE OF THE PROJECT WILL BE OVER $2,500.00 IN VALUE
 REQUIRING NOTARIZED SIGNATURE THE CONTRACTOR.
  
 5) 2ND REQUEST. THE PLANS DO NOT INDICATE TRYING TO
 MAKE ANY ACCESSIBLE UPGRADES PLEASE REVIEW THE
 FOLLOWING:
 2014 FBC-ACCESS. CODE:
 202.4.3 SERIES OF SMALLER ALTERATIONS. THE OBLIGATION
 TO PROVIDE AN ACCESSIBLE PATH OF TRAVEL MAY NOT BE
 EVADED BY PERFORMING A SERIES OF SMALL ALTERATIONS TO
 THE AREA SERVED BY A SINGLE PATH OF TRAVEL IF THOSE
 ALTERATIONS COULD HAVE BEEN PERFORMED AS A SINGLE
 UNDERTAKING.
  
 NEW COMMENT IN REGARDS TO DISPROPORTIONALITY. PLEASE
 NOTE SHEET A1.0 DOOR #4 IN THE OFFICE IS BEING REMOVE
 DOOR.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION SECTION 104.9.1 USED MATERIALS AND
 EQUIPMENT. THE USE OF USED, RECYCLED, OR RECLAIMED
 MATERIALS WHICH MEET THE REQUIREMENTS OF THIS CODE FOR
 NEW MATERIALS IS PERMITTED. USED
 EQUIPMENT AND DEVICES SHALL NOT BE REUSED UNLESS
 APPROVED BY THE BUILDING OFFICIAL.
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. DOOR # 4 NEEDS TO BE A
 36 INCH WIDE DOOR THAT WILL PROVIDE THE REQUIRED 32
 INCHES CLEAR. THIS DOOR WOULD ALSO QUALIFY FOR THE 20 %
 DISPROPORTIONATE COST, THE GRAB BARS DOESN?T SINCE
 THERE IS AN EXISTING 2 FOOT WIDE DOOR, AND NOT BEING
 REPLACED. A WHEELCHAIR BOUND PERSON CODE NOT GET IN THE
 RESTROOM.
  
 202.4.3.1 IF AN AREA CONTAINING A PRIMARY FUNCTION HAS
 BEEN ALTERED WITHOUT PROVIDING AN ACCESSIBLE PATH OF
 TRAVEL TO THAT AREA, AND SUBSEQUENT ALTERATIONS OF THAT
 AREA, OR A DIFFERENT AREA ON THE SAME PATH OF TRAVEL,
 ARE UNDERTAKEN WITHIN THREE YEARS OF THE ORIGINAL
 ALTERATION, THE TOTAL COST OF ALTERATIONS TO THE
 PRIMARY FUNCTION AREAS ON THAT PATH OF TRAVEL DURING
 THE PRECEDING THREE YEAR PERIOD SHALL BE CONSIDERED IN
 DETERMINING WHETHER THE COST OF MAKING THAT PATH OF
 TRAVEL ACCESSIBLE IS DISPROPORTIONATE.
  
 202.4.1 DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COSTS THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COSTS
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (II) COSTS
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COSTS ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COSTS ASSOCIATED WITH RELOCATING AN INACCESSIBLE
 DRINKING FOUNTAIN.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-05 Cont ID  
Sent By jwitmer Date 2017-06-05 Time 17:28 Rev Time 0.00
Received By jwitmer Date 2017-06-05 Time 14:21 Sent To  
Notes
2017-06-05 17:28:022014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060032
 ADD: 444 25TH STREET / UNIT: 3
 CONT: H. LAYTON MAINGUY
 TEL: 954-249-8500
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 05/2017
 ACTION: DENIED
  
 1) THE COVERSHEET A-1.0:
 1A) THE DESIGNER OF RECORD HAS NOT INDICATED TO WHICH
 COMPLIANCE METHOD THE PLANS WERE DESIGNED TOO?
 2014 FBC-EXISTING BUILDING CODE :
 301.1.1 PRESCRIPTIVE COMPLIANCE METHOD.
 301.1.2 WORK AREA COMPLIANCE METHOD.
 301.1.3 PERFORMANCE COMPLIANCE METHOD.
  
 1B) SHEET A-1.0 INDICATES THE CONSTRUCTION TYPE AS TYPE
 III? IS THIS A OR B? FBC-B TABLE 503.
 1C) THE PLANS INDICATE THE USE AS A BEAUTY PARLOR/
 BUSINESS OCCUPANCY. PLEASE NOTE THE TOTAL SQUARE
 FOOTAGE IS 1740 SQ. FT. THIS TENANT SPACE. THE STORE
 AREA IS 199.3 SQ. FT. OR OVER THE 10 % FLOOR AREA OF
 THE TENANT SPACE. TO LOOK AT ACCESSORY OCCUPANCIES
 VERSES MIXED USE OCCUPANCIES YOU TAKE THE TOTAL FLOOR
 AREA OF THE BUILDING, NOT THE TENANT SPACE. SEE FBC-B
 508.2.1 AREA LIMITATIONS.
 B 508.2.1 AREA LIMITATIONS. AGGREGATE ACCESSORY
 OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10 PERCENT OF
 THE BUILDING AREA OF THE STORY IN WHICH THEY ARE
 LOCATED AND SHALL NOT EXCEED THE TABULAR VALUES IN
 TABLE 503, WITHOUT BUILDING AREA INCREASES IN
 ACCORDANCE WITH SECTION 506 FOR SUCH ACCESSORY
 OCCUPANCIES.
 1D) OCCUPANT LOADS. PLEASE NOTE IN THE OCCUPANT LOAD
 CALCULATIONS THERE ARE 15.4 AND 0.7 OCCUPANTS. PLEASE
 NOTE YOU ONLY COUNT WHOLE OCCUPANTS, YOU ALWAYS ROUND
 UP. THERE ARE NO PARTIAL OCCUPANTS. FLORIDA BUILDING
 CODE INFORMAL INTERPRETATION REPORT # 5479 SECTION
 1004.1.2.
 1E) SCOPE OF WORK INCLUDES WORK IN A HAIR SALON THAT
 CONSIST OF THE FOLLOWING AREAS: SHAMPOOS, PEDICURES,
 NAIL POLISHING, WAXING, AND HAIR STYLING. YOU WILL
 RECEIVE COMMENTS FROM THE MECHANICAL PLANS REVIEWER ON
 THE FRESH AIR AND EXHAUST AIR THAT WILL BE REQUIRED FOR
 PEDICURES AND NAIL POLISHING. PLEASE BE AWARE THAT
 EITHER THE FRESH AIR AND EXHAUST AIR WILL BE THROUGH
 THE ROOF AND MAY REQUIRE ADDITIONAL ROOF FRAMING,
 ANCHORING OF ROOF TOP CURBS AND INTAKE AND EXHAUST
 FANS. NONE OF THIS INFORMATION HAS BEEN PROVIDED FOR
 THIS REVIEW.
 FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF
 TOP FANS
 (G) PRE-ENGINEERED A/C STANDS (POSSIBLY)
  
 2) FOR THE ROOF TOP MECHANICAL EQUIPMENT PLEASE PROVIDE
 THE WIND DESIGN CRITERIA, 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2.2. RISK CATEGORY.
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3) SHEET A-1.1 SECTION 1 INDICATES A RAISED PLATFORM 11
 INCHES FROM THE FLOOR.
 3A) PLEASE NOTE THE 2 STAIRS ARE NOT THE SAME IN
 HEIGHT. 2014 FBC-B 1009.7.4 DIMENSIONAL UNIFORMITY.
  
 3B) THE PLATFORM SECTION SHOWS THE USE OF 2 X2 WOOD
 JOIST AT 16 INCHES ON CENTER. PLEASE REVIEW THE
 VERTICAL DIMENSION I BELIEVE IT IS MISLABELED, A TYPO,
 PLEASE CORRECT. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3C) PLEASE PROVIDE HOW A PERSON IN A WHEEL CHAIR IS
 GOING TO ACHIEVE ACCESS TO THE CHAIR ON THE PLATFORM.
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2014 FBC-ACCESS. CODE 202.3 ALTERATIONS. WHERE EXISTING
 ELEMENTS OR SPACES OR COMMON AREAS ARE ALTERED, EACH
 ALTERED ELEMENT, SPACE OR AREA SHALL COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF CHAPTER 2 AND SECTION
 201.1.1.
 2014 ACCESS. CODE. 201.1.1 VERTICAL ACCESSIBILITY.
 SECTIONS 553.501-553.513, F.S., AND THE ADA STANDARDS
 FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY.
  
 4) THE VALUE OF THE PROJECT MAY BE INCREASED BECAUSE OF
 THE REQUIRED, INTAKE AND EXHAUST AIR, FRAMING AND ROOF
 TOP MECHANICAL EQUIPMENT. WITH THE INCREASED VALUE THE
 VALUE OF THE PROJECT WILL BE OVER $2,500.00 IN VALUE
 REQUIRING NOTARIZED SIGNATURE THE CONTRACTOR.
  
 5) THE PLANS DO NOT INDICATE TRYING TO MAKE ANY
 ACCESSIBLE UPGRADES PLEASE REVIEW THE FOLLOWING:
 2014 FBC-ACCESS. CODE:
 202.4.3 SERIES OF SMALLER ALTERATIONS. THE OBLIGATION
 TO PROVIDE AN ACCESSIBLE PATH OF TRAVEL MAY NOT BE
 EVADED BY PERFORMING A SERIES OF SMALL ALTERATIONS TO
 THE AREA SERVED BY A SINGLE PATH OF TRAVEL IF THOSE
 ALTERATIONS COULD HAVE BEEN PERFORMED AS A SINGLE
 UNDERTAKING.
  
 202.4.3.1 IF AN AREA CONTAINING A PRIMARY FUNCTION HAS
 BEEN ALTERED WITHOUT PROVIDING AN ACCESSIBLE PATH OF
 TRAVEL TO THAT AREA, AND SUBSEQUENT ALTERATIONS OF THAT
 AREA, OR A DIFFERENT AREA ON THE SAME PATH OF TRAVEL,
 ARE UNDERTAKEN WITHIN THREE YEARS OF THE ORIGINAL
 ALTERATION, THE TOTAL COST OF ALTERATIONS TO THE
 PRIMARY FUNCTION AREAS ON THAT PATH OF TRAVEL DURING
 THE PRECEDING THREE YEAR PERIOD SHALL BE CONSIDERED IN
 DETERMINING WHETHER THE COST OF MAKING THAT PATH OF
 TRAVEL ACCESSIBLE IS DISPROPORTIONATE.
  
 202.4.1 DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COSTS THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COSTS
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (II) COSTS
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COSTS ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COSTS ASSOCIATED WITH RELOCATING AN INACCESSIBLE
 DRINKING FOUNTAIN.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-11-15 Cont ID  
Sent By jpearson Date 2017-11-15 Time 14:19 Rev Time 0.00
Received By jpearson Date 2017-11-15 Time 14:19 Sent To  
Notes
2017-11-15 14:19:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS A 100 AMP PANEL (PANEL A) BEING
 FED FROM PANEL B, HOWEVER, THE LOAD FOR PANEL A IS NOT
 INCLUDED WITH LOAD CALCULATION. PROVIDE ACCURATE LOAD
 CALCULATION WITH ALL LOADS ACCOUNTED FOR TO DETERMINE
 IF SERVICE SIZE IS ADEQUATE. BE ADVISED THAT ONLY ONE
 SERVICE IS PERMITTED PER LOCATION. NEC 220, 230.2
 2. PROVIDE PANEL SCHEDULES FOR ALL PANELS INDICATING
 ANY NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE
 FOR THESE CIRCUITS, AND GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 215.5, 408.4
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94
 4. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63
 5. ELECTRICAL PLAN PROVIDED IS INCOMPLETE. SHOW ALL
 EXISTING ELECTRICAL AND ANY NEW INSTALLATIONS RELATING
 TO CHANGE OF USE AS A HAIR SALON. FBC 107.2.1, 107.3.5
 6. PROVIDE SHOW WINDOW OUTLETS REQUIRED PER CODE. NEC
 210.62
 7. PROVIDE DEDICATED SIGN CIRCUIT WITH AUTOMATIC
 CONTROL PER CODE. NEC 600.5; FBC CE 405.2.4
  
 A COMPLETE REVIEW IS NOT POSSIBLE AT THIS TIME AS THERE
 IS INFORMATION MISSING FROM THE PLANS SUBMITTED.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-09 Cont ID  
Sent By jpearson Date 2017-06-09 Time 07:37 Rev Time 0.00
Received By jpearson Date 2017-06-09 Time 07:36 Sent To  
Notes
2017-06-09 07:40:20CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW. INDICATE ANY
 EXISTING SERVICE AND ANY UPGRADES AS NECESSARY. PROVIDE
 FLOOR PLAN SHOWING LOCATIONS OF ALL OUTLETS AND
 LIGHTING, NEW AND EXISTING. PROVIDE RISER DIAGRAM AND
 PANEL SCHEDULE WITH WIRE AND CONDUIT SIZING. PROVIDE
 SPEC SHEETS FOR EQUIPMENT. FBC 107.2.1, 107.3.5, NEC
 110.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-11-06 Cont ID  
Sent By pleduc Date 2017-11-06 Time   Rev Time 0.00
Received By pleduc Date 2017-11-06 Time 14:42 Sent To  
Notes
2017-11-06 16:50:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) IF YOU ARE PROPOSING A SINGLE EXIT FROM THE BUSINESS
 AREA THEN REMOVE EXIT SIGN FROM REAR HALLWAY. USE IT AS
 AN EMERGENCY LIGHT IF YOU CHOOSE, IT'S NOT REQUIRED.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-07 Cont ID  
Sent By pleduc Date 2017-06-07 Time   Rev Time 0.00
Received By pleduc Date 2017-06-06 Time 13:09 Sent To  
Notes
2017-06-07 14:23:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 1.1 - THE DOOR SWING FROM THE OFFICE/STAFF
 ROOM INTO THE HALLWAY CHANGES FROM SHEET A 1.0 & A 1.1.
 WHICH ONE IS CORRECT AND CORRECT THE OTHERS. IT IS
 IMPORTANT TO NOTE THAT SHEET A 1.1 SHOWS IT AS NOT
 BLOCKING THE HALLWAY.
  
 PLEASE CLARIFY.
  
  
  
  
 2) SHEET A 1.0 - THE OCCUPANCY IS INDICATED AS
 BUSINESS; HOWEVER, A STORAGE AREA IS INDICATED.
  
 PER NFPA 101, CHAPTER 6 CLASSIFICATION OF OCCUPANCY AND
 HAZARD OF CONTENTS
  
 6.1 CLASSIFICATION OF OCCUPANCY.
 6.1.1 GENERAL.
 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A
 BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR
 STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2
 THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE
 SUBJECT TO THE RULING OF THE AUTHORITY HAVING
 JURISDICTION WHERE THERE IS A QUESTION OF PROPER
 CLASSIFICATION IN ANY INDIVIDUAL CASE.
  
 6.1.14 MULTIPLE OCCUPANCIES.
 6.1.14.1 GENERAL.
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ? 6.1.14.4
 6.1.14.1.2 WHERE EXIT ACCESS FROM AN OCCUPANCY
 TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE OCCUPANCY
 SHALL BE TREATED AS A MIXED OCCUPANCY.
  
 6.1.14.2 DEFINITIONS.
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE
 RESISTANCE?RATED ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION 6.1
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED,
 UNLESS SEPARATE SAFEGUARDS ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES.
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE BUILDING COMPRISING A DISTINCT
 OCCUPANCY, AS DESCRIBED IN THIS CHAPTER, SHALL BE
 COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2,
 6.1.14.4.3, TABLE 6.1.14.4.1(A), AND TABLE
 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED BY
 APPROVED EXISTING SEPARATIONS.
  
 PLEASE CLARIFY YOUR OCCUPANCY.
  
  
  
  
 3) SHEET A 1.1 - A BARN DOOR IS INDICATED AT THE
 HALLWAY IN THE CENTER OF THE OCCUPANCY AND IN THE EXIT
 PATH OF TRAVEL.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS,
  
 7.2.1.14 HORIZONTAL-SLIDING DOOR ASSEMBLIES.
 HORIZONTAL-SLIDING DOOR ASSEMBLIES SHALL BE PERMITTED
 IN MEANS OF EGRESS, PROVIDED THAT ALL OF THE FOLLOWING
 CRITERIA ARE MET:
 (1) THE DOOR LEAF IS READILY OPERABLE FROM EITHER SIDE
 WITHOUT SPECIAL KNOWLEDGE OR EFFORT.
 (2) THE FORCE THAT, WHEN APPLIED TO THE OPERATING
 DEVICE IN THE DIRECTION OF EGRESS, IS REQUIRED TO
 OPERATE THE DOOR LEAF IS NOT MORE THAN 15 LBF (67 N).
 (3) THE FORCE REQUIRED TO OPERATE THE DOOR LEAF IN THE
 DIRECTION OF TRAVEL IS NOT MORE THAN 30 LBF (133 N) TO
 SET THE LEAF IN MOTION AND IS NOT MORE THAN 15 LBF (67
 N) TO CLOSE THE LEAF OR OPEN IT TO THE MINIMUM REQUIRED
 WIDTH.
 (4) THE DOOR LEAF IS OPERABLE USING A FORCE OF NOT MORE
 THAN 50 LBF (222 N) WHEN A FORCE OF 250 LBF (1100 N) IS
 APPLIED PERPENDICULARLY TO THE LEAF ADJACENT TO THE
 OPERATING DEVICE, UNLESS THE DOOR OPENING IS AN
 EXISTING HORIZONTAL-SLIDING EXIT ACCESS DOOR ASSEMBLY
 SERVING AN AREA WITH AN OCCUPANT LOAD OF FEWER THAN 50.
 (5) THE DOOR ASSEMBLY COMPLIES WITH THE FIRE PROTECTION
 RATING, IF REQUIRED, AND, WHERE RATED, IS SELF-CLOSING
 OR AUTOMATICCLOSING BY MEANS OF SMOKE DETECTION IN
 ACCORDANCE WITH 7.2.1.8 AND IS INSTALLED IN ACCORDANCE
 WITH NFPA 80, STANDARD FOR FIRE DOORS AND OTHER OPENING
 PROTECTIVES.
 (6) THE DOOR SHALL BE POWER OPERATED AND SHALL BE
 CAPABLE OF BEING OPERATED MANUALLY IN THE EVENT OF
 POWER FAILURE.
  
 PLEASE REVIEW FOR COMPLIANCE AND PROVIDE DETAILS.
  
  
  
 4) SHEET A 1.2 - THERE IS NO EXIT SIGN IN THE HALLWAY
 LEADING TO THE FRONT EXIT. IN THE EVENT THAT THE DOES
 COMPLY WITH ABOVE AND THEY ARE CLOSED THERE IS NO EXIT
 INDICATORS.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 5) SHEET A 1.2 - THERE IS EXITING INDICATED FROM A
 BUSINESS AREA THROUGH A STORAGE OCCUPANCY. EXITING
 CANNOT PASS THROUGH AN AREA FORM A LOWER HAZARD
 (BUSINESS) THROUGH A HIGHER HAZARD (STORAGE.
  
 PER NFPA CHAPTER 7, 7.5.1.6 EXIT ACCESS FROM ROOMS OR
 SPACES SHALL BE PERMITTED TO BE THROUGH ADJOINING OR
 INTERVENING ROOMS OR AREAS, PROVIDED THAT SUCH ROOMS OR
 AREAS ARE ACCESSORY TO THE AREA SERVED. FOYERS,
 LOBBIES, AND RECEPTION ROOMS CONSTRUCTED AS REQUIRED
 FOR CORRIDORS SHALL NOT BE CONSTRUED AS INTERVENING
 ROOMS. EXIT ACCESS SHALL BE ARRANGED SOTHAT IT IS NOT
 NECESSARY TO PASS THROUGH ANY AREA IDENTIFIED UNDER
 PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 6) ALL SHEETS - THERE IS A PLATFORM WITH TWO STEPS
 INDICATED. THERE IS LITTLE TO NO DETAIL ON THESE STEPS.
  
 PEOPLE MUST EGRESS DOWN THESE STEPS TO EXIT THE
 OCCUPANCY. PER NFPA 101, CHAPTER 7, 7.2.2.4 GUARDS AND
 HANDRAILS.
 7.2.2.4.1 HANDRAILS.
 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON
 BOTH SIDES, UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5
 OR 7.2.2.4.1.6.
 7.2.2.4.1.2 IN ADDITION TO THE HANDRAILS REQUIRED AT
 THE SIDES OF STAIRS BY 7.2.2.4.1.1, BOTH OF THE
 FOLLOWING PROVISIONS SHALL APPLY:
 (1) FOR NEW STAIRS, HANDRAILS SHALL BE PROVIDED WITHIN
 30 IN. (760 MM) OF ALL PORTIONS OF THE REQUIRED EGRESS
 WIDTH.
 (2) FOR EXISTING STAIRS, HANDRAILS SHALL MEET THE
 FOLLOWING CRITERIA:
 (A) THEY SHALL BE PROVIDED WITHIN 44 IN. (1120 MM) OF
 ALL PORTIONS OF THE REQUIRED EGRESS WIDTH.
 (B) SUCH STAIRS SHALL NOT HAVE THEIR EGRESS CAPACITY
 ADJUSTED TO A HIGHER OCCUPANT LOAD THAN PERMITTED BY
 THE CAPACITY FACTOR IN TABLE 7.3.3.1 IF THE STAIR?S
 CLEAR WIDTH BETWEEN HANDRAILS EXCEEDS 60 IN. (1525 MM).
 7.2.2.4.1.3 WHERE NEW INTERMEDIATE HANDRAILS ARE
 PROVIDED IN ACCORDANCE WITH 7.2.2.4.1.2, THE MINIMUM
 CLEAR WIDTH BETWEEN HANDRAILS SHALL BE 20 IN. (510 MM).
 7.2.2.4.1.4* THE REQUIRED EGRESS WIDTH SHALL BE
 PROVIDED ALONG THE NATURAL PATH OF TRAVEL.
 7.2.2.4.1.5 IF A SINGLE STEP OR A RAMP IS PART OF A
 CURB THAT SEPARATES A SIDEWALK FROM A VEHICULAR WAY, IT
 SHALL NOT BE REQUIRED TO HAVE A HANDRAIL.
  
 PLEASE REVIEW, CLARIFY OR CORRECT.
  
  
  
 7) SHEET A 1.2 - THERE IS NO DOOR SCHEDULE INDICATING
 SIZE, LOCKS OR LATCHES, OR HARDWARE.
  
 PLEASE PROVIDE.
  
  
 8) SHEET A 1.2 - THERE IS AN EXIT DOOR INDICATED AT THE
 REAR OF THE OCCUPANCY; HOWEVER, IT IS NO CLEAR IF THIS
 EXIT LEADS TO A PUBLIC WAY.
  
 PLEAASE PROVIDE A PROPERTY SITE PLAN INCLUDING ANY
 FENCING OR WALL DETAILS THAT MAY RESTRICT ACCESS TO A
 PUBLIC WAY.
  
  
  
 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-16 Cont ID  
Sent By gjohnson Date 2017-11-16 Time 16:55 Rev Time 0.00
Received By gjohnson Date 2017-11-02 Time 10:08 Sent To  
Notes
2017-11-03 10:09:02B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-07-03 Cont ID  
Sent By cpuell Date 2017-07-03 Time 11:15 Rev Time 0.00
Received By cpuell Date 2017-06-01 Time 14:42 Sent To  
Notes
2017-06-01 14:42:29B09

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-11-13 Cont ID  
Sent By ccole Date 2017-11-13 Time 08:45 Rev Time 0.00
Received By ccole Date 2017-11-09 Time 17:21 Sent To  
Notes
2017-11-13 09:02:492ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17060032
 11/13/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE 24X24 TRANSFER GRILL IS ALLOWING RECIRCULATION
 OF AIR FROM THE SALON INTO THE OFFICE AREA WHICH IS
 PROHIBITED PER TABLE 403.3 FOOTNOTE B.
  
 2) THE PLAN DOES NOT SHOW THE REQUIRED SOURCE CAPTURE
 SYSTEMS REQUIRED AT EACH MANI AND PEDI STATION, AND HOW
 THE FUMES, VAPORS ETC. ARE BEING EXHAUSTED OUT OF THE
 BUILDING. PLEASE SEE SECTION 501.3 WHICH REQUIRES THE
 HEALTHY AIR SOURCE CAPTURE SYSTEMS TO BE DUCTED TO THE
 OUTDOORS. PLEASE PROVIDE A MEDCHANICAL FLOOR PLAN
 DRAWING THAT SHOWS THE STATIONS, THE SYSTEMS, THE
  
 DUCT RUNS, AND EXHAUST OUTLET LOCATIONS. INDICATE THE
 TYPES AND SIZES OF EXHAUST DUCTS TO BE INSTALLED, AND
 PROVIDE SUPPORT AND CONNECTION DETAILS.
  
 3) THE SUBMITTED PRODUCT INFORMATION SHEETS FOR THE
 HEALTHY AIR SYSTEMS DO NOT PROVIDE ANY LISTING OR
 LABELING INFORMATION, OR INDICATE THAT THE PRODUCT HAS
 BEEN TESTED AND APPROVED BY ANY AGENCIES SUCH AS ETL OR
 UL. PLEASE SUBMIT PRODUCT DATA SHEETS WITH SHOP DRAWING
 APPROVAL SIGNATURES BY THE ENGINEER OF RECORD.
  
 4) PROVIDE EXHAUST VENTILATION CALCULATIONS, AND AIR
 BALANCE CALCULATIONS.
  
 5) PROVIDE A SEQUENCE OF OPERATION FOR EF-1- SEE
 SECTION 501.4
  
 6) IT APPEARS THAT THE NEW CONDENSER IS BEING LOCATED
 WITHIN 10' OF THE ROOF EDGE WHICH WOULD REQUIRE A GUARD
 OR PARAPET AT A MINIMUM HEIGHT OF 42"- PLEASE COMPLY.
 PLEASE NOTE THAT PERMANENT LADDERS ARE REQUIRED FOR
 ROOF TOP MECHANICAL EQUIPMENT LOCATED OVWER 16' FROM
 GRADE.
  
 7) THE ARCHITECTURAL PLANS ARE INDICATING THE AHU-1
 CLOSET DOOR IS WOOD, HOWEVER AC CLOSET DOORS SHALL BE
 NON-COMBUSTIBLE IN COMPLIANCE WITH SECTION C403.2.7.2
 FBC-14 ENERGY CONSERVATION AND SECTION 602 FBC-14
 MECHANICAL. PLEASE NOTE THAT THE NO CLOSET WALLS OR
 DOOR ARE SHOWN FOR AHU-2 ALTHOUGH THERE IS A NOTE ON
 THE PLAN INDICATING A LOUVERED DOOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-08 Cont ID  
Sent By ccole Date 2017-06-08 Time 12:33 Rev Time 0.00
Received By ccole Date 2017-06-08 Time 12:33 Sent To  
Notes
2017-06-08 13:11:441ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060032
 6/8/17
  
 RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS HAVE BEEN SUBMITTED FOR THE
 PROPOSED BEAUTY/NAIL SALON. PLEASE PROVIDE PLANS,
 DETAILS, AND SPECIFICATIONS FOR ALL HVAC ALTERATIONS
 AND INSTALLATIONS REQUIRED TO ACCOMODATE THE NEW
 OCCUPANCY AS OUTLINED IN SECTION 403 AND TABLE 403.3
 FBC-14 MECHANICAL. PLEASE NOTE THAT MECHANICAL EXHAUST
 SYSTEMS ARE REQUIRED AND RECIRCULATION OF AIR
  
 FROM THE SALON OR NAIL STATIONS IS PROHIBITED- SEE
 SECTION 403.2.1 ITEM 3. SEE REQUIREMENTS LISTED BELOW.
  
 A) PROVIDE EXHAUST VENTILATION SYSTEMS FOR THE MANICURE
 TABLES AND THE PEDICURE CHAIRS AT A RATE NOT LESS THAN
 50 CFMS PER NAIL STATION. EACH STATION SHALL BE
 PROVIDED WITH A SOURCE CAPTURE SYSTEM- SEE FOOTNOTE H
 UNDER TABLE 403.3. RECIRCULATION OF THE EXHAUST AIR IS
 PROHIBITED- FOOTNOTE B
  
 B) PROVIDE EXHAUST VENTILATION SYSTEM FOR THE BEAUTY
 SALON AT AN EXHAUST RATE OF 0.6 CFMS PER SF- TABLE
 403.3.
  
 C) PROVIDE A MEANS OF MAKEUP AIR FOR THE EXHAUST
 SYSTEMS- 501.4.
  
 D) CALCULATIONS REQUIRED: EXHAUST, OUTDOOR AIR FOR ALL
 OCCUPIED ROOMS AND SPACES, AND AIR BALANCE.
  
 E) PROVIDE AN EQUIPMENT SCHEDULE FOR THE EXISTING AC
 SYSTEM THAT LISTS THE MAKE AND MODEL AND COOLING AND
 HEATING CAPACITIES OF THE SYSTEM.
  
 2) PLEASE SEE BUILDING REVIEW COMMENTS #1E AND #2 FOR
 EXTERIOR MECHANICAL EQUIPMENT AND APPLIANCE
 INSTALLATION REQUIREMENTS.
  
 3) PLEASE NOTE FURTHER COMMENTS MAY FOLLOW THIS REVIEW
 AFTER CORRECTED AND REVISED PLANS ARE RESUBMITTED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-11-16 Cont ID  
Sent By gjohnson Date 2017-11-16 Time 16:53 Rev Time 0.00
Received By gjohnson Date 2017-11-16 Time 14:07 Sent To  
Notes
2017-11-16 16:55:402ND-REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: NOT COMPLIED
  
 SHALL COMPLY WITH BUILDINGS COMMENT #5 1. ALTHOUGH A
 PLUMBING PERMIT HAS BEEN ISSUED #17030673 ADDITIONAL
 PLUMBING MAY BE REQUIRED TO COMPLY WITH BUILDINGS
 COMMENT #5 FOR ACCESSIBILITY DISPROPORTIONATE COST.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-13 Cont ID  
Sent By gjohnson Date 2017-06-13 Time 17:34 Rev Time 0.00
Received By gjohnson Date 2017-06-13 Time 12:59 Sent To  
Notes
2017-06-13 17:39:221ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. ALTHOUGH A PLUMBING PERMIT HAS BEEN ISSUED #17030673
 ADDITIONAL PLUMBING MAY BE REQUIRED TO COMPLY WITH
 BUILDINGS COMMENT #5 FOR ACCESSIBILITY DISPROPORTIONATE
 COST.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-06-30 Cont ID  
Sent By llouie Date 2017-06-30 Time   Rev Time  
Received By llouie Date 2017-06-30 Time   Sent To  
Notes
2017-06-30 15:50:38* INTERIOR MODIFICATIONS ONLY (NO EXTERIOR CHANGES).
  
 * SALON USE PERMITTED, PER AVANN, PLANNING AND ZONING
 ADMINISTRATOR.