|
 |
 |
 |
 |
 |
Plan Review Details - Permit 17051195
Plan Review Stops For Permit 17051195 |
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2017-06-05 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2017-06-05 |
Time |
05:47 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2017-06-05 |
Time |
05:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2017-05-30 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2017-05-30 |
Time |
06:18 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2017-05-30 |
Time |
06:03 |
Sent To |
|
|
Notes |
2017-05-30 06:09:29 | 1.) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE | | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL | | GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. | | G2413. | | 2) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. | | SEC. G2413.2. | | 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | 4) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE | | DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS | | OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR | | NFPA STANDARD THAT WERE USED IN THE DESIGN OF THIS | | SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3. | | 5) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS SEC.409.4, | | FBC-RESIDENTIAL SEC. G 2420.4. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2017-06-05 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2017-06-05 |
Time |
05:47 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2017-06-01 |
Time |
14:22 |
Sent To |
|
|
Notes |
2017-06-01 14:23:06 | TLARGE'S DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-05-30 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2017-05-30 |
Time |
06:18 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2017-05-26 |
Time |
16:20 |
Sent To |
|
|
Notes |
2017-05-26 16:20:54 | PLUMB <5K |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |