2017-06-01 08:04:22 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| REVISION TO MASTER 16120343; REVIEW #1 |
| |
| 1. THIS PROJECT IS LOCATED IN THE SPECIAL FLOOD HAZARD |
| AREA. |
| |
| A9.4 NOTE 1 STATES THAT ALL SPOT ELEVATIONS ARE TO THE |
| TOP OF THE CIP CONCRETE. REVISE PLAN TO INCORPORATE |
| MINIMUM REQUIREMENT UTILIZING NGVD29 DATUM TO CORRELATE |
| WITH THE CIVIL SHEETS OR PROPOSED STRUCTURES' ABILITY |
| TO RESIST FLOOD LOADS. |
| |
| SEE FBC B 1612.4. ALTHOUGH THERE IS NO FINISHED FLOOR |
| REQUIREMENT FOR THE ENTRY FEATURES (NOT A BUILDING), |
| THE PROPOSED NEW STRUCTURES ARE TO EITHER BE ELEVATED |
| TO >=13' NGVD29 OR BE DESIGNED TO RESIST FLOOD LOADS. |
| REVISE PLAN ACCORDINGLY. IF EOR/AOR ELECT TO REQUIRE A |
| MINIMUM ELEVATION, IT IS RECOMMENDED THAT THE |
| REQUIREMENT BE INCORPORATED INTO BOTH A AND S SHEETS. |
| |
| 2. I AM UNABLE TO LOCATE WIND DESIGN CRITERIA ON THE |
| PLAN, FBC 1609. REVISE PLAN TO INCLUDE THE WIND DESIGN |
| CRITERIA FOR THE NEW ENTRY FEATURES PROPOSED OR ADVISE |
| WHERE THIS CAN BE LOCATED. |
| |
| 3. PROVISO, THIS PERMIT WILL BE ISSUED AT APPLICANT'S |
| RISK; ENGINEERING OR PRODUCT APPROVAL REQUIRED FOR THE |
| PRECAST; PROVIDE AT INSPECTION OR (SUBJECT TO |
| INSPECTOR'S DISCRETION) SUBMIT PRIOR TO INSTALLATION. |
| |
| 4. FBC A 903.3, PLAN SHOWS 20" DEEP; NOTE THAT THIS IS |
| A MINIMUM REQUIREMENT AN CANNOT BE REDUCED IN THE |
| FIELD; TO AVOID FIELD ISSUES, IT IS RECOMMENDED TO |
| REVISE PLAN TO NOTE REQUIREMENT. |
| |
| 5. FBC A 903.2, REVISE PLAN TO SHOW CLEAR GROUND SPACE |
| REQUIREMENT. |
| |
| 6. FBC A 903.4, PLAN SHOWS 18" HIGH FOR WALL (BACK) |
| BEHIND BENCH; NOTE THAT THIS IS A MINIMUM REQUIREMENT |
| AND CANNOT BE REDUCED IN THE FIELD. IT IS NOT CLEAR HOW |
| THE DECORATIVE WALL WILL AFFECT USE OF THAT PORTION OF |
| THE WALL AS A BACK. IT IS RECOMMENDED THAT THE 18" |
| MINIMUM REQUIREMENT BE INCORPORATED INTO THE PLAN TO |
| AVOID FIELD ISSUES. |
| |
| 7. 4-A9.1, A PORTION OF THE TEXT IS NOT LEGIBLE; PLEASE |
| ADJUST, FBC 107. |
| |
| 8. N/A |
| |