Plan Review Details - Permit 17050856
Plan Review Stops For Permit 17050856
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-28 Cont ID  
Sent By jwitmer Date 2017-06-28 Time 06:57 Rev Time 0.00
Received By jwitmer Date 2017-06-28 Time 06:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-26 Cont ID  
Sent By jwitmer Date 2017-05-26 Time 13:34 Rev Time 0.00
Received By jwitmer Date 2017-05-26 Time 11:41 Sent To  
Notes
2017-05-26 13:34:452014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050856
 ADD: 1645 PALM BEACH LAKES SUITE: 500
 CONT: CHANDLER CONSTRUCTION
 TEL: 561-791-6934
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 26/ 2016
 ACTION: DENIED
 HIGHRISE BUILDING
 1) SHEET A-2 DETAIL # 2 THE PROPOSED FLOOR PLAN DOES
 NOT SHOW COMPLIANCE WITH 2014 FBC-B 713.14.1. EVERY
 ELEVATOR LOBBY SHALL HAVE AT ONE MEANS OF EGRESS,
 ENSURING THAT NO OCCUPANT FROM THE FLOOR HAS TO TRAVEL
 THROUGH THE ELEVATOR LOBBY TO AN EXIT. THERE APPEARS TO
 BE (2) POSSIBLE SOLUTIONS. THE FIRST WOULD BE TO CREATE
 A SECOND EXIT THROUGH ROOM # 114 INTO THE CORRIDOR YOU
 WOULD NOT HAVE TO TRAVEL THROUGH THE ELEVATOR LOBBY.
 THE 2ND SOLUTION WOULD BE TO INSTALL THE 1 HOUR RATED
 MAGNETIC DROPS FIRE AND SMOKE CURTAINS OVER EACH OF THE
 ELEVATOR OPENINGS. THE ELEVATOR FIRE AND SMOKE MAGNETIC
 CURTAIN WOULD HAVE TO BE TIED TO THE FIRE ALARM AS WELL
 TO ACTIVATE THE SYSTEM.
  
 2) SHEET A-2 COMMON PATH OF TRAVEL HAS ALSO BEEN
 EXCEEDED. FROM THE OFFICE 112 MEASURING ONE FOOT FROM
 THE WALL FROM THE FURTHEST POINT IN THAT OFFICE TO
 WHERE YOU HAVE A CHOICE OF 2 EXITS THE TRAVEL DISTANCE
 IS APPROXIMATELY 113 FEET. TABLE 1014.3 OF THE 2014
 FBC-B ONLY ALLOWS 100 FEET FOR FIRE SPRINKLERED
 BUILDINGS. PLEASE ALSO CHECK THE COMMON PATH OF TRAVEL
 FROM THE OTHER 3 CORNER OFFICES.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-05-31 Cont ID  
Sent By jpearson Date 2017-05-31 Time 14:24 Rev Time 0.00
Received By jpearson Date 2017-05-31 Time 14:24 Sent To  
Notes
2017-05-31 14:25:46APPROVED WITH EXCEPTION. PROVIDE ELECTRICAL PERMIT
 APPLICATION FOR PERMIT TO BE ISSUED. FBC 105.1

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-05-22 Cont ID  
Sent By scaldero Date 2017-05-22 Time 15:16 Rev Time 0.00
Received By scaldero Date 2017-05-22 Time 15:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-06-28 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-22 Time 13:50 Sent To  
Notes
2017-06-26 13:50:59RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-31 Cont ID  
Sent By jpearson Date 2017-05-31 Time 14:27 Rev Time 0.00
Received By jpearson Date 2017-05-18 Time 14:57 Sent To  
Notes
2017-05-19 14:57:52B04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-05-26 Cont ID  
Sent By jwitmer Date 2017-05-26 Time 13:35 Rev Time 0.00
Received By jwitmer Date 2017-05-26 Time 13:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-05-25 Cont ID  
Sent By ccole Date 2017-05-25 Time 15:24 Rev Time 0.00
Received By ccole Date 2017-05-25 Time 15:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-05-24 Cont ID  
Sent By gjohnson Date 2017-05-24 Time 17:28 Rev Time 0.00
Received By gjohnson Date 2017-05-24 Time 17:28 Sent To  
Notes
***NONE***