Plan Review Details - Permit 17050847
Plan Review Stops For Permit 17050847
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-16 Cont ID  
Sent By tklarge Date 2017-06-16 Time 11:16 Rev Time 0.00
Received By tklarge Date 2017-06-09 Time 11:09 Sent To  
Notes
2017-06-12 11:09:26RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-06 Cont ID  
Sent By tklarge Date 2017-06-06 Time 06:18 Rev Time 0.00
Received By tklarge Date 2017-06-05 Time 14:30 Sent To  
Notes
2017-06-05 14:30:42TKLARGE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-19 Cont ID  
Sent By tklarge Date 2017-05-19 Time 09:03 Rev Time 0.00
Received By tklarge Date 2017-06-14 Time 06:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-06-16 Cont ID  
Sent By tklarge Date 2017-06-16 Time 11:16 Rev Time 0.00
Received By tklarge Date 2017-06-14 Time 06:22 Sent To  
Notes
2017-06-14 06:27:32APPROVED BY PLUMBING. SENT TO UTILITIES FOR REVIEW.
 TKL.

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-06-06 Cont ID  
Sent By tklarge Date 2017-06-06 Time 06:18 Rev Time 0.00
Received By tklarge Date 2017-06-06 Time 06:10 Sent To  
Notes
2017-06-06 06:18:281) INDICATE THE SIZE OF THE DEVICE BEING INSTALLED ON
 THE SPECIFICATIONS AND ON THE PERMIT APPLICATION. WPB
 AMEND. TO FBC SEC.107.2.1. 2ND REQUEST.
 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE PER NSF 61
 AND THE CITY OF WPB CROSS-CONNECTION CONTROL MANUAL.
 THE SUBMITTED SPECIFICATIONS DO NOT SHOW THE DEVICE IS
 LEAD FREE. 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-19 Cont ID  
Sent By tklarge Date 2017-05-19 Time 09:02 Rev Time 0.00
Received By tklarge Date 2017-05-19 Time 08:57 Sent To  
Notes
2017-05-19 09:02:541) INDICATE THE SIZE OF THE DEVICE BEING INSTALLED ON
 THE SPECIFICATIONS AND ON THE PERMIT APPLICATION. WPB
 AMEND. TO FBC SEC.107.2.1.
 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE PER NSF 61
 AND THE CITY OF WPB CROSS-CONNECTION CONTROL MANUAL.
 THE SUBMITTED SPECIFICATIONS DO NOT SHOW THE DEVICE IS
 LEAD FREE AND IT IS NOT LISTED AS LEAD FREE ON THE USC
 WEBSITE. ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY
 OF SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED
 DEVICES.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  