Plan Review Details - Permit 17050765
Plan Review Stops For Permit 17050765
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-07-19 Cont ID  
Sent By jwitmer Date 2017-07-19 Time 15:19 Rev Time 0.00
Received By jwitmer Date 2017-07-18 Time 11:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-20 Cont ID  
Sent By jwitmer Date 2017-06-20 Time 16:56 Rev Time 0.00
Received By jwitmer Date 2017-06-20 Time 16:04 Sent To  
Notes
2017-06-20 16:56:282014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050765
 ADD: 6901 OKEECHOBEE BLVD./ SUITE NUMBER: ????????
 CONT: KCA CONSTRUCTION INC.
 TEL: 561-818-7777
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUESDAY, JUNE 20, 2017J
 ACTION: DENIED
  
 1) NEITHER THE PLANS AND PERMIT APPLICATION PROVIDE THE
 SUITE NUMBER FOR ADDRESSING AND LOCATION FOR THE
 PROJECT FOR THE INSPECTORS TO LOCATE THE JOBSITE.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED.
 2014 FBC-B [F] 501.2 ADDRESS IDENTIFICATION.
 WEST PALM BEACH MUNI CODE SECTION 78-6(1-7).
  
 2) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 1. FLOOR PLAN TO INDICATE THE OCCUPANCY TYPE FOR THE
 ADJOINING TENANTS/ OCCUPANCY SEPARATION FBC-B
 TABLE 503.
 2.OCCUPANCY GROUP.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 5. IS THE BUILDING FIRE SPRINKLERED OR NOT.
  
 3) PLEASE PROVIDE AN INTERIOR DEMOLITION PLAN FOR THIS
 TENANT SPACE, INDICATE AREAS TO BE DEMOLISHED.
 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 4) THE DEMISING WALL TO THE RIGHT OF THE TENANT SPACE
 INDICATES IT IS A ONE HOUR WALL, IS THIS A NEW TENANT
 AND OR OCCUPANCY SEPARATION WALL? NO PERMITS HAVE BEEN
 PULLED FOR THIS WALL!!!! 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 5) THE DOOR TO THE REAR RIGHT OF THE PLAN, DOOR # 8, IS
 THIS TO BE A SHARED REAR REQUIRED EXIT FOR THE ADJACENT
 TENANT? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-07-24 Cont ID  
Sent By jpearson Date 2017-07-24 Time 11:32 Rev Time 0.00
Received By jpearson Date 2017-07-24 Time 11:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-16 Cont ID  
Sent By jpearson Date 2017-06-16 Time 10:27 Rev Time 0.00
Received By jpearson Date 2017-06-16 Time 10:27 Sent To  
Notes
2017-06-16 10:37:23CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE AUTOMATIC LIGHTING SHUTOFF FOR AREAS OF
 PROPESED WORK PER FBC ENERGY CONSERVATION. FBC-
 C405.2.2
 2. PROVIDE LIGHT FIXTURE SCHEDULE WITH DETAILS OF
 ENERGY USE FOR EACH TYPE. FBC 107.2.1, FBC TABLE
 C405.5.2(1) NEC 110.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-07-27 Cont ID  
Sent By scaldero Date 2017-07-27 Time 08:12 Rev Time 0.00
Received By scaldero Date 2017-07-27 Time 08:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-26 Cont ID  
Sent By scaldero Date 2017-06-26 Time 10:10 Rev Time 0.00
Received By scaldero Date 2017-06-26 Time 10:08 Sent To  
Notes
2017-06-26 10:10:20PERMIT # 17050765
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) REVIEW AND RESPOND TO BUILDING DEPT. COMMENTS.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-07-20 Cont ID  
Sent By gjohnson Date 2017-07-20 Time 16:05 Rev Time 0.00
Received By gjohnson Date 2017-07-20 Time 16:05 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-06-19 Cont ID  
Sent By gjohnson Date 2017-06-19 Time 12:11 Rev Time 0.00
Received By gjohnson Date 2017-06-19 Time 12:11 Sent To  
Notes
2017-06-19 13:19:361ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE GAS LOAD CALCULATIONS SHOW 4 STOCK POTS THE
 RISER ONLY SHOWS 3 PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 2. THE LONGEST LENGTH LISTED UNDER THE GAS LOAD
 CALCULATIONS IS 48' IT IS UNCLEAR BY LOOKING AT THE
 RISER WHAT THE LONGEST LENGTH IS NONE OF THE
 MEASUREMENTS ADD UP TO 48. PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 3. IT APPEARS THAT YOU SOME EXTRA PIPING LABELS ON THE
 RISER DIAGRAM PLEASE CLARIFY THESE 30' @ 11/2 (488K),
 8' @ 11/2 (747K) AND 6 @1/1/2 (488K)
  
 4. SHOW ALL REGULATORS TO INDICATE .5LB FROM 2LB
 SYSTEMS. PER WPB AMEND TO FBC
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 8. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-31 Cont ID  
Sent By lmarchan Date 2017-07-31 Time 14:11 Rev Time 0.00
Received By lmarchan Date 2017-07-11 Time 11:12 Sent To  
Notes
2017-07-13 11:12:31B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-28 Cont ID  
Sent By lmarchan Date 2017-06-28 Time 10:16 Rev Time 0.00
Received By lmarchan Date 2017-06-15 Time 10:16 Sent To  
Notes
2017-06-15 14:37:12B12
2017-05-18 14:28:01B11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-06-20 Cont ID  
Sent By jwitmer Date 2017-06-20 Time 16:56 Rev Time 0.00
Received By jwitmer Date 2017-06-20 Time 16:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-07-24 Cont ID  
Sent By ccole Date 2017-07-24 Time 08:46 Rev Time 0.00
Received By ccole Date 2017-07-24 Time 08:42 Sent To  
Notes
2017-07-24 08:47:22SEPARATE PERMITS REQUIRED FOR MECHANICAL WORK, KTICHEN
 HOODS AND FIRE SUPPRESSION ALTERATIONS- CCOLE- 7/24/17

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-21 Cont ID  
Sent By ccole Date 2017-06-21 Time 09:19 Rev Time 0.00
Received By ccole Date 2017-06-21 Time 09:19 Sent To  
Notes
2017-06-21 09:22:211ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050765
 6/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A BALANCED AIR PLAN FOR THE NEW OFFICE-
 SUPPLY AND RETURN AIR DETAILS- SECTION 601.5.
  
 2) PLEASE NOTE THAT ADDITIONAL MECHANICAL COMMENTS MAY
 OCCUR PENDING RESPONSES TO THE BUILDING PLAN REVIEW
 COMMENTS,
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-07-20 Cont ID  
Sent By gjohnson Date 2017-07-20 Time 16:06 Rev Time 0.00
Received By gjohnson Date 2017-07-20 Time 13:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-19 Cont ID  
Sent By gjohnson Date 2017-06-19 Time 11:48 Rev Time 0.00
Received By gjohnson Date 2017-06-19 Time 09:12 Sent To  
Notes
2017-06-19 12:10:521ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE EXISTING FLOOR PLAN. PER WPB AMEND TO
 FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy