Plan Review Details - Permit 17050731
Plan Review Stops For Permit 17050731
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-06-13 Cont ID  
Sent By tklarge Date 2017-06-13 Time 09:58 Rev Time 0.00
Received By tklarge Date 2017-06-13 Time 09:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-05-18 Cont ID  
Sent By tklarge Date 2017-05-18 Time 06:57 Rev Time 0.00
Received By tklarge Date 2017-05-18 Time 06:06 Sent To  
Notes
2017-05-18 06:57:301) SUBMIT 2 CCOPIES OF THE SIZING TABLE USED FOR THE
 SIZING OF THE LOW PRESSURE SIDE OF THED GAS SYSTEM OR
 PLACE A NOTE ON BOTH SETS OF PLANS REFERENCING THE
 TABLE USED. 2014 FBC- FUEL GAS SEC. 402.3.
 2) INDICATE THE LENGTH, SIZE & TYPE OF PIPE MATERIAL
 FOR THE LOW PRESSURE SIDE CONNECTION TO THE GENERATORS.
 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE GENERATORS. GENERATORS SHALL BE
 INSTALLED IN ACCORDANCE WITH NFPA 37 AND SHALL MEET THE
 REQUIREMENTS OF UL 2200.
 4) THE LP TANK APPEARS AS THOUGH IT MAY BE INSTALLED
 NEAR A DRIVEWAY PER PLANS ON RECORD. IDENTIFY ON THE
 PLAN THE TYPE OF AREA WHERE THE TANK IS BEING INSTALLED
 ( PLANTING/LANDSCAPED AREA). IF THE TANK WILL BE
 INSTALLED WHERE VEHICLES ARE EXPECTED, THE TANK,
 FITTING HOUSING, HOUSING COVER, CONTAINER CONNECTIONS
 AND PIPING PERR NFPA 58 SEC. 6.6.6.1 (B) (C).
 5) A CORROSION PROTECTION SYSTEM SHALL BE INSTALLED
 PERR NFPA 58 SEC. 6.6.6.1 (I). SUBMIT DETAILS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6) THE SUBMITTED DOCUMENT FROM TRINITY CONTAINERS IS
 ILLEGIBLE. SUBMIT A CLEAR AND LEGIBLE DDOCUMENT. WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-13 Cont ID  
Sent By tklarge Date 2017-06-13 Time 09:58 Rev Time 0.00
Received By tklarge Date 2017-06-09 Time 12:43 Sent To  
Notes
2017-06-12 12:44:02RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-18 Cont ID  
Sent By tklarge Date 2017-05-18 Time 06:57 Rev Time 0.00
Received By tklarge Date 2017-05-16 Time 12:53 Sent To  
Notes
2017-05-17 12:53:59PLUMBING INBOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved