Plan Review Details - Permit 17050723
Plan Review Stops For Permit 17050723
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-02-26 Cont ID  
Sent By cthroop Date 2018-02-26 Time 16:42 Rev Time 0.00
Received By cthroop Date 2018-02-26 Time 16:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-25 Cont ID  
Sent By cthroop Date 2017-08-25 Time 07:01 Rev Time 0.00
Received By cthroop Date 2017-08-25 Time 06:59 Sent To  
Notes
2017-08-25 07:02:16NO WORK SHOWN ON PLAN REQUIRING A BUILDING REVIEW. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-05-30 Cont ID  
Sent By skennedy Date 2017-05-30 Time 12:18 Rev Time 0.00
Received By skennedy Date 2017-05-30 Time 12:18 Sent To  
Notes
2017-05-30 12:24:441ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 1ST REVIEW FBC 2014 EXISTING BUILDING
  
 THERE IS NO WORK SHOW HOWEVER THE PERMIT DESCRIPTION
 INDICATES REPLACEMENT OF CABINETS AND INSTALLATION OF
 FLOORING. NO PLANS REQUIRED SUBJECT TO THE INSPECTOR.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-02-22 Cont ID  
Sent By jpearson Date 2018-02-22 Time 10:21 Rev Time 0.00
Received By jpearson Date 2018-02-22 Time 10:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-17 Cont ID  
Sent By jpearson Date 2017-08-17 Time 16:16 Rev Time 0.00
Received By jpearson Date 2017-08-17 Time 16:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-02 Cont ID  
Sent By jpearson Date 2017-06-02 Time 14:27 Rev Time 0.00
Received By jpearson Date 2017-06-02 Time 14:27 Sent To  
Notes
2017-06-02 15:02:04CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL 1ST REVIEW COMMENTS:
  
 1. PROVIDE 2 COPIES OF PLAN FOR REVIEW. FBC 107.1
 2. SHOW AFCI PROTECTION PER CODE. ALL 120-VOLT, SINGLE
 PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING
 OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, OR
 SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC
 210.12, FBC RE3902.12
 3. PROVIDE PANEL SCHEDULE, INDICATE WIRE AND BREAKER
 SIZE FOR EACH CIRCUIT TO BE INSTALLED. NEC 215.5, 408.4
 4. PROVIDE SMOKE ALARM FOR BASEMENT LEVEL. FBC
 R314.3(3).
 5. PROVIDE CO ALARM WITHIN 10 FEET OF SLEEPING ROOMS.
 FBC R315.1
 6. PROVIDE LIGHT AT EXTERIOR DOOR TO BASEMENT. FOR
 DWELLING UNITS, ATTACHED GARAGES, AND DETACHED GARAGES
 WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH
 GRADE LEVEL ACCESS. NEC 210.70(A)(2)(B), FBC RE3903.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2018-02-26 Cont ID  
Sent By gjohnson Date 2018-02-26 Time 14:11 Rev Time 0.00
Received By gjohnson Date 2018-02-26 Time 14:11 Sent To  
Notes
2018-02-26 14:12:03NO GAS ON PLANS

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-08-23 Cont ID  
Sent By gjohnson Date 2017-08-23 Time 16:19 Rev Time 0.00
Received By gjohnson Date 2017-08-23 Time 16:19 Sent To  
Notes
2017-08-23 16:23:281ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. TYPE OF GAS, (LP OR NATURAL).
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 3. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 4. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 5. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 6. PLEASE SHOW REGULATOR, VALVE AND DRIP LEG. PER
 WPBAMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-02-13 Cont ID  
Sent By fmittner Date 2018-02-13 Time 15:34 Rev Time 0.00
Received By fmittner Date 2018-02-13 Time 15:34 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2017-08-18 Cont ID  
Sent By fmittner Date 2017-08-18 Time 10:04 Rev Time 0.00
Received By fmittner Date 2017-08-18 Time 10:04 Sent To  
Notes
2017-08-18 10:05:24INTERIOR ELECTRICAL WORK ONLY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-02-26 Cont ID  
Sent By cthroop Date 2018-02-26 Time 16:42 Rev Time 0.00
Received By cthroop Date 2018-02-06 Time 13:24 Sent To I
Notes
2018-02-07 13:24:39R01

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-25 Cont ID  
Sent By cthroop Date 2017-08-25 Time 07:01 Rev Time 0.00
Received By cthroop Date 2017-08-03 Time 14:13 Sent To  
Notes
2017-08-04 14:13:51R32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-09 Cont ID  
Sent By gjohnson Date 2017-06-09 Time 10:43 Rev Time 0.00
Received By gjohnson Date 2017-05-16 Time 09:05 Sent To  
Notes
2017-05-18 09:05:54R08

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-05-30 Cont ID  
Sent By skennedy Date 2017-05-30 Time 12:18 Rev Time 0.00
Received By skennedy Date 2017-05-30 Time 12:18 Sent To  
Notes
2017-05-30 12:18:32SEE 17050727 MECH OUT

Review Stop P PLUMBING
Rev No 3 Status N Date 2018-02-26 Cont ID  
Sent By gjohnson Date 2018-02-26 Time 14:12 Rev Time 0.00
Received By gjohnson Date 2018-02-26 Time 14:12 Sent To  
Notes
2018-02-26 14:13:03NO PLUMBING SHOWN ON PLANS
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-08-23 Cont ID  
Sent By gjohnson Date 2017-08-23 Time 16:02 Rev Time 0.00
Received By gjohnson Date 2017-08-23 Time 10:46 Sent To  
Notes
2017-08-23 16:10:372ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 2ND REQUEST1. TWO SETS OF PLANS REQUIRED. PER WPB AMEND
 TO FBC 107.1
  
 2. PLAN IS UNCLEAR IT APPEARS LIKE THERE MAY BE TWO
 FLOOR LEVELS BUT NO DETAILS SOME OF THE NOTES ARE
 UNCLEAR EXISTING LAUNDRY NEW MOP SINK LOCATION. I
 SUGGEST THAT SOMEONE COMES IN AND MEETS WITH ME TO
 CLARIFY THIS PLAN BEFORE RESUBMITTING OTHERWISE I WILL
 NOT BE ABLE TO APPROVE PLANS. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-06-09 Cont ID  
Sent By gjohnson Date 2017-06-09 Time 10:33 Rev Time 0.00
Received By gjohnson Date 2017-06-09 Time 10:24 Sent To  
Notes
2017-06-09 10:42:271ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. TWO SETS OF PLANS REQUIRED. PER WPB AMEND TO FBC
 107.1
  
 2. NOTES ON PLUMBING PAGE ARE NOT LEGIBLE PLEASE
 PROVIDE A SET OF PLANS THAT ARE LEGIBLE. PER WPB AMEND
 TO FBC 107.2.1.4
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  