Plan Review Details - Permit 17050689
Plan Review Stops For Permit 17050689
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-06-19 Cont ID  
Sent By jwitmer Date 2017-06-19 Time 17:31 Rev Time 0.00
Received By jwitmer Date 2017-06-19 Time 16:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-05-31 Cont ID  
Sent By jwitmer Date 2017-05-31 Time 16:10 Rev Time 0.00
Received By jwitmer Date 2017-05-31 Time 11:55 Sent To  
Notes
2017-05-31 16:09:57BUILDING PLAN REVIEW
 W. P. B. REVISION: 17050689
 W. P. B. PERMIT: 15031312
 ADD: 333 FERN ST.
 CONT: KAST CONSTRUCTION
 CONTACT :ROB HALL
 TEL: (561)689-2910
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: WED. MAY 31/ 2017
 ACTION: DENIED
  
  
  
 1A)SEMI COMPLIED. THE COVERSHEET BREAK METAL AT ENTRY
 CLADDING CALCULATIONS SUBMITTAL, DOES HAVE A TABLE OF
 CONTENTS THE SEAL IS PRINTED BUT THE SIGNATURE IS
 DIGITAL, THE EDGES OF THE SIGNATURE IS PIXALATED.
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET.
  
 1B) PAST THE FIRST 10 PAGES THAT IS COVERED UNDER THE
 INDEX SHEET THERE ARE 5 ADDITIONAL SHEETS LISTED 1-5
 WITH A MINITURIZED SEAL 1 1/4 INCHES IN DIAMETER. AGAIN
 THE SIGNATURE IS COPIED.
 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD.
 SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN
 DIAMETER, TO SAY LICENSE NOT CERTIFICATE. ALL ENGINEERS
 MUST BE UTILIZING SAID SEAL NO LATER THAN JANUARY 1,
 2006.
  
 FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE
 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS
 WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER
 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
  
 1) 1ST ROUND COMMENT. THE BREAK METAL AT ENTRY CLADDING
 CALCULATIONS SUBMITTAL, THE COVER PAGE SIGNED AND
 SEALED BY EVAN KENNEDY DOES NOT INCLUDE HOW MANY PAGES
 ARE COVERED UNDER THIS SEAL. WITHIN THE REPORT ARE
 MARKED PAGES 1-5 WITH A COPIED AND MINIATURIZED
 SIGNATURE AND SEAL.
  
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET. .
 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD.
 SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN
 DIAMETER, TO SAY LICENSE NOT CERTIFICATE. ALL ENGINEERS
 MUST BE UTILIZING SAID SEAL NO LATER THAN JANUARY 1,
 2006.
  
 2) COMPLIED.
  
 3) COMPLIED. NOA 14-0811.20 REYNOBOND COMPOSITE WALL
 PANEL SYSTEM.ACM PANELS ARE AVAILABLE IN 3MM, 4MM AND
 6MM THICKNESSES IN EITHER A STANDARD POLYETHYLENE (PE)
 OR FIRE RESISTANT (FR) CORE.
  
 4) COMPLIED. 2010 FBC-B 1407.11.1- 1407.11. SEE NOA
 14-0811.20
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-18 Cont ID  
Sent By jwitmer Date 2017-05-18 Time 08:50 Rev Time 0.00
Received By jwitmer Date 2017-05-18 Time 08:21 Sent To  
Notes
2017-05-18 08:50:55BUILDING PLAN REVIEW
 W. P. B. REVISION: 17041119
 W. P. B. PERMIT: 15031312
 ADD: 333 FERN ST.
 CONT: KAST CONSTRUCTION
 CONTACT :ROB HILL
 TEL: (561)689-2910
 E-MAIL: [email protected]
  
 1) THE BREAK METAL AT ENTRY CLADDING CALCULATIONS
 SUBMITTAL, THE COVER PAGE SIGNED AND SEALED BY EVAN
 KENNEDY DOES NOT INCLUDE HOW MANY PAGES ARE COVERED
 UNDER THIS SEAL. WITHIN THE REPORT ARE MARKED PAGES 1-5
 WITH A COPIED AND MINIATURIZED SIGNATURE AND SEAL.
  
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET. .
 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD.
 SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN
 DIAMETER, TO SAY LICENSE NOT CERTIFICATE. ALL ENGINEERS
 MUST BE UTILIZING SAID SEAL NO LATER THAN JANUARY 1,
 2006.
  
 2) WIND CALCULATIONS ARE BASED ON ASCE 7-10 LOW RISE
 BUILDINGS (H<60 FT.) PLEASE NOTE NEGATIVE PRESSURES ARE
 TAKEN FROM THE ROOF LEVEL. NEGATIVE PRESSURES(Z),
 POSITIVE PRESSURES( H). ASCE 7-10.
 THIS IS A 16 STORY HIGH-RISE. ELEVATION TAKEN @ 15
 FEET. CALCULATIONS NOT SHOWN ONLY THE END VALUES.
  
 3) ACM PANELS ARE AVAILABLE IN 3MM, 4MM AND 6MM
 THICKNESSES IN EITHER A STANDARD POLYETHYLENE (PE) OR
 FIRE RESISTANT (FR) CORE. NO PRODUCT INFORMATION HAS
 BEEN SUBMITTED. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(C) PANEL WALLS: ACM PANELS AND OTHER PRODUCTS
 INTRODUCED BY NEW TECHNOLOGIES
  
 4) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1407.11.1-
 1407.11.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-19 Cont ID  
Sent By jwitmer Date 2017-06-19 Time 17:31 Rev Time 0.00
Received By jwitmer Date 2017-06-07 Time 13:30 Sent To  
Notes
2017-06-08 13:31:01JWITMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-05-31 Time   Rev Time 0.00
Received By lmarchan Date 2017-05-24 Time 13:31 Sent To  
Notes
2017-05-25 13:31:52RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-05-18 Time   Rev Time 0.00
Received By lmarchan Date 2017-05-15 Time 09:29 Sent To  
Notes
2017-05-16 09:29:58SUBMITTAL ROUTED TO JWITMER