2017-05-25 07:25:27 | JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION |
| |
| |
| 110.24 AVAILABLE FAULT CURRENT. |
| (A) FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN |
| DWELLING UNITS SHALL BE LEGIBLY MARKED IN THE FIELD |
| WITH THE |
| MAXIMUM AVAILABLE FAULT CURRENT. THE FIELD MARKLNG(S) |
| SHALL |
| INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS |
| PERFORMED |
| AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE |
| ENVIRONMENT |
| INVOLVED. |
| |
| (B) MODIFICATIONS. WHEN MODIFICATIONS TO THE ELECTRICAL |
| INSTALLATION OCCUR THAT AFFECT THE MAXIMUM AVAILABLE |
| FAULT |
| CURRENT AT THE SERVICE, THE MAXIMUM AVAILABLE FAULT |
| CURRENT |
| SHALL BE VERIFIED OR RECALCULATED AS NECESSARY TO |
| ENSURE THE |
| SERVICE EQUIPMENT RATINGS ARE SUFTICIENT FOR THE |
| MAXIMUM |
| AVAILABLE FAULT CULTENT AT THE LINE TERMINALS OF THE |
| EQUIPMENT. |
| THE REQUIRED FIELD MARKING(S) IN LLO.24(A) SHALL BE |
| ADJUSTED TO |
| REFLECT THE NEW LEVEL OF MAXIMUM AVAILABLE FAULT |
| CURRENT |
| |
| 408.4 FIELD IDENTIFICATION REQUIRED. |
| (B) SOURCE OF SUPPLY. ALL SWITCHBOARDS,SWITEHGEAR, AND |
| PANELBOARDS SUPPLIED BY A FEEDER(S) IN OTHER THAN ONE- |
| OR |
| TWO-FAMILY DWELLINGS SHALL BE MARKED TO INDICATE EACH |
| DEVICE |
| OR EQUIPMENT WHERE THE POWER ORIGINATES. |
| |
| C405.5 INTERIOR LIGHTING POWER REQUIREMENTS |
| (PRESCRIPTIVE). |
| A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL |
| CONNECTED LIGHTING |
| POWER CALCULATED UNDER SECTION C405.5.1 IS NO GREATER |
| THAN THE |
| INTERIOR LIGHTING POWER CALCULATED UNDER SECTION |
| C405.5.2. |
| |
| C405.5.1 TOTAL CONNECTED INTERIOR LIGHTING POWER. |
| THE TOTAL CONNECTED INTERIOR LIGHTING POWER (WATTS) |
| SHALL BE THE |
| SUM OF THE WATTS OF ALL INTERIOR LIGHTING EQUIPMENT AS |
| DETERMINED |
| IN ACCORDANCE WITH SECTIONS C405.5.1.1 THROUGH |
| C405.5.1.4. |
| |
| C405.2 LIGHTING CONTROLS (MANDATORY). |
| LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS |
| SPECIFIED |
| IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND C405.2.4. |
| |
| C405.2.1 MANUAL LIGHTING CONTROLS. |
| ALL BUILDINGS SHALL INCLUDE MANUAL LIGHTING CONTROLS |
| THAT MEET |
| THE REQUIREMENTS OF SECTIONS C405.2.1.1 AND C405.2.1.2. |
| |
| |
| |
| |