Plan Review Details - Permit 17050622
Plan Review Stops For Permit 17050622
Review Stop AD ADDRESSING
Rev No 2 Status N Date 2017-08-02 Cont ID  
Sent By shill Date 2017-08-02 Time 12:57 Rev Time 0.00
Received By shill Date 2017-08-02 Time 12:57 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2017-05-25 Cont ID  
Sent By shill Date 2017-05-25 Time 08:30 Rev Time 0.00
Received By shill Date 2017-05-25 Time 08:30 Sent To  
Notes
2017-05-25 08:31:19CONTACT:
  
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET ? WEST PALM BEACH ? FLORIDA 33401
 P: 561.494.1080
  
 PROVIDE THE FOLLOWING INFORMATION:
  
 ADVISE AS TO NEW UNIT NUMBER(S) SO THEY CAN BE SET IN
 THE CITY'S ADDRESS DATABASES.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-02 Cont ID  
Sent By shill Date 2017-08-02 Time 12:57 Rev Time 0.00
Received By shill Date 2017-08-02 Time 12:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-05-19 Cont ID  
Sent By shill Date 2017-05-19 Time 17:15 Rev Time 0.00
Received By shill Date 2017-05-19 Time 15:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-04 Cont ID  
Sent By jpearson Date 2017-08-04 Time 08:54 Rev Time 0.00
Received By jpearson Date 2017-08-04 Time 08:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-25 Cont ID  
Sent By jleahy Date 2017-05-25 Time 07:19 Rev Time 0.00
Received By jleahy Date 2017-05-25 Time 07:19 Sent To  
Notes
2017-05-25 07:25:27JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
  
 110.24 AVAILABLE FAULT CURRENT.
 (A) FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN
 DWELLING UNITS SHALL BE LEGIBLY MARKED IN THE FIELD
 WITH THE
 MAXIMUM AVAILABLE FAULT CURRENT. THE FIELD MARKLNG(S)
 SHALL
 INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS
 PERFORMED
 AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE
 ENVIRONMENT
 INVOLVED.
  
 (B) MODIFICATIONS. WHEN MODIFICATIONS TO THE ELECTRICAL
 INSTALLATION OCCUR THAT AFFECT THE MAXIMUM AVAILABLE
 FAULT
 CURRENT AT THE SERVICE, THE MAXIMUM AVAILABLE FAULT
 CURRENT
 SHALL BE VERIFIED OR RECALCULATED AS NECESSARY TO
 ENSURE THE
 SERVICE EQUIPMENT RATINGS ARE SUFTICIENT FOR THE
 MAXIMUM
 AVAILABLE FAULT CULTENT AT THE LINE TERMINALS OF THE
 EQUIPMENT.
 THE REQUIRED FIELD MARKING(S) IN LLO.24(A) SHALL BE
 ADJUSTED TO
 REFLECT THE NEW LEVEL OF MAXIMUM AVAILABLE FAULT
 CURRENT
  
 408.4 FIELD IDENTIFICATION REQUIRED.
 (B) SOURCE OF SUPPLY. ALL SWITCHBOARDS,SWITEHGEAR, AND
 PANELBOARDS SUPPLIED BY A FEEDER(S) IN OTHER THAN ONE-
 OR
 TWO-FAMILY DWELLINGS SHALL BE MARKED TO INDICATE EACH
 DEVICE
 OR EQUIPMENT WHERE THE POWER ORIGINATES.
  
 C405.5 INTERIOR LIGHTING POWER REQUIREMENTS
 (PRESCRIPTIVE).
 A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING
 POWER CALCULATED UNDER SECTION C405.5.1 IS NO GREATER
 THAN THE
 INTERIOR LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.2.
  
 C405.5.1 TOTAL CONNECTED INTERIOR LIGHTING POWER.
 THE TOTAL CONNECTED INTERIOR LIGHTING POWER (WATTS)
 SHALL BE THE
 SUM OF THE WATTS OF ALL INTERIOR LIGHTING EQUIPMENT AS
 DETERMINED
 IN ACCORDANCE WITH SECTIONS C405.5.1.1 THROUGH
 C405.5.1.4.
  
 C405.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 SPECIFIED
 IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND C405.2.4.
  
 C405.2.1 MANUAL LIGHTING CONTROLS.
 ALL BUILDINGS SHALL INCLUDE MANUAL LIGHTING CONTROLS
 THAT MEET
 THE REQUIREMENTS OF SECTIONS C405.2.1.1 AND C405.2.1.2.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-05-17 Cont ID  
Sent By pleduc Date 2017-05-17 Time   Rev Time 0.00
Received By pleduc Date 2017-05-16 Time 16:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-08-10 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-31 Time 10:59 Sent To  
Notes
2017-08-02 11:00:05B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-25 Cont ID  
Sent By jleahy Date 2017-05-25 Time 07:26 Rev Time 0.00
Received By jleahy Date 2017-05-12 Time 13:36 Sent To  
Notes
2017-05-15 13:36:35B06

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-08-10 Cont ID  
Sent By ccole Date 2017-08-10 Time 11:09 Rev Time 0.00
Received By ccole Date 2017-08-10 Time 10:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-18 Cont ID  
Sent By ccole Date 2017-05-18 Time 16:04 Rev Time 0.00
Received By ccole Date 2017-05-18 Time 16:04 Sent To  
Notes
2017-05-18 16:14:441ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17050622
 5/18/17
  
 1) SHEET M6.1 LISTED IN THE INDEX WAS NOT INCLUDED IN
 THE PLAN SETS- PLEASE PROVIDE THE PLAN.
  
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 3) PROVIDE THE FLEX DUCT SIZES AND AN AIR DEVICE
 SCHEDULE
  
 4) M2.1: RELOCATE THE FIRE DAMPER SHOWN IN THE O/A DUCT
 RUN IN THE MIDDLE OF THE ROOM TO THE DUCT PENETRATION
 AT THE NEW FIRE-RATED WALL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  