Plan Review Details - Permit 17050546
Plan Review Stops For Permit 17050546
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-10-29 Cont ID  
Sent By pleduc Date 2018-10-29 Time   Rev Time 0.00
Received By pleduc Date 2018-10-29 Time 10:32 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2018-09-24 Cont ID  
Sent By pleduc Date 2018-09-24 Time   Rev Time 0.00
Received By pleduc Date 2018-09-24 Time 10:32 Sent To I
Notes
2018-09-24 10:43:51THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) PLEASE ADDRESS MECHANICAL COMMENTS;
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-06-01 Cont ID  
Sent By pleduc Date 2017-06-01 Time   Rev Time 0.00
Received By pleduc Date 2017-06-01 Time 15:43 Sent To  
Notes
2017-06-01 15:52:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTAL DID NOT PROVIDE ANY PRODUCT/EQUIPMENT
 DETAILS OR SPECIFICATIONS TO REVIEW OR VERIFY AGAINST
 THE APPLICABLE FIRE CODES OR EOR DRAWINGS AND/OR
 REQUIREMENTS.
  
 PLEASE PROVIDE
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-29 Cont ID  
Sent By cpuell Date 2018-10-29 Time 11:16 Rev Time 0.00
Received By cpuell Date 2018-09-27 Time 06:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-24 Cont ID  
Sent By lmarchan Date 2018-09-24 Time 13:13 Rev Time 0.00
Received By lmarchan Date 2018-09-12 Time 13:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-06 Cont ID  
Sent By lmarchan Date 2017-06-06 Time 07:55 Rev Time 0.00
Received By lmarchan Date 2017-05-16 Time 14:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-10-12 Cont ID  
Sent By ccole Date 2018-10-12 Time 15:02 Rev Time 0.00
Received By ccole Date 2018-10-12 Time 15:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-09-21 Cont ID  
Sent By ccole Date 2018-09-21 Time 13:18 Rev Time 0.00
Received By ccole Date 2018-09-21 Time 07:35 Sent To  
Notes
2018-09-21 13:23:002ND REVIEW FBC-2014 MECHANICAL
 SUBMITTAL #17050546
 BRIGHTLINE MASTER #16070715
 9/21/18
  
 COMMENTS #4 & 5 FROM THE 1ST REVIEW STILL EXIST
  
 4) PLEASE REVISE THE FAN SCHEDULE ON THE PLAN TO MATCH
 THE SUBMITTALS. (PLEASE SEE SHEET M1301- MASTER PERMT
 #16070715).
  
 5) MOTORIZED DAMPERS: THE SUBMITTAL FOR THE DUROZONE
 MOTORIZED DAMPER DOES NOT INDICATE THE UNIT IS CLASS 1A
 RATED AND, DOES NOT EXCEED THE MAXIMUM LEAKAGE RATE
 WHEN TESTED IN ACCORDANCE WITH AMCA 500D- SEE SECTION
 C402.4.5.2 FBC-14 ENERGY CONSERVATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-24 Cont ID  
Sent By ccole Date 2017-05-24 Time 10:39 Rev Time 0.00
Received By ccole Date 2017-05-18 Time 12:53 Sent To  
Notes
2017-05-24 10:39:371ST REVIEW FBC-2014 MECHANICAL
 SUBMITTAL #17050546
 BRIGHTLINE MASTER #16070715
 5/24/17
  
 1) EF-25-1: THE SUBMITTAL FOR THE PENNBARRY D10 SMOKE
 EXHAUST FAN DOES NOT PROVIDE EVIDENCE THAT THE FAN IS
 RATED AND CERTIFIED BY THE MANUFACTURER FOR THE
 PROBABLE TEMPERATURE RISE AS REQUIRED BY SECTION
 513.10.1 FBC-14 MECHANICAL. THE SUBMITTAL DOES NOT
 INDICATE THE FAN IS UL 705 LISTED AND LABELED PER THE
 ENGINEER'S NOTES IN THE FAN SCHEDULE (SHEET M1301), AND
 DOES NOT INDICATE THE FAN WILL BE EQUIPPED WITH TWO
 BELTS. PLEASE REVIEW THE SUBMITTAL FOR COMPLIANCE.
  
 2) DUCTS: REFER TO SECTION 513.10.2 FBC-14 MECHANICAL
 AND INDICATE WHICH DUCTS IN THE SUBMITTAL PACKAGE ARE
 DESIGNATED FOR SMOKE CONTROL AND EXHAUST, AND PROVIDE
 EVIDENCE THAT THE DESIGNATED DUCTS HAVE BEEN TESTED FOR
 RESISTANCE TO TEMPERATURE RISE AND PRESSURE, AND LEAK
 TESTED TO 1.5 TIMES THE MAXIMUM DESIGN PRESSURE.
  
 3) IT DOES NOT APPEAR THAT THE PENNBARRY SMOKE CONTROL
 FAN SUBMITTALS INDICATE THAT THE SELECTED SMOKE CONTROL
 FANS ARE EQUIPPED WITH TWO BELTS AS REQUIRED BY SECTION
 513.10.5 FBC-14 MECHANICAL, AND ALSO BY THE ENGINEER OF
 RECORD'S DESIGN- SEE SUBMITTAL REVIEW COMMENTS BY C.
 BUI.
  
 4) PLEASE REVISE THE FAN SCHEDULE ON THE PLAN TO MATCH
 THE SUBMITTALS.
  
 5) MOTORIZED DAMPERS: THE SUBMITTAL FOR THE DUROZONE
 MOTORIZED DAMPER DOES NOT INDICATE THE UNIT IS CLASS 1A
 RATED AND, DOES NOT EXCEED THE MAXIMUM LEAKAGE RATE
 WHEN TESTED IN ACCORDANCE WITH AMCA 500D- SEE SECTION
 C402.4.5.2 FBC-14 ENERGY CONSERVATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2017-05-24 Cont ID  
Sent By ccole Date 2017-05-24 Time 10:40 Rev Time 0.00
Received By ccole Date 2017-05-24 Time 10:40 Sent To  
Notes
2017-05-24 10:41:57DIG/SIGS NOT REQUIRED FOR SHOP DRAWINGS AND PRODUCT
 SUBMITTALS.
 CCOLE- 5/24/17