Plan Review Details - Permit 17050520
Plan Review Stops For Permit 17050520
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-07-24 Cont ID  
Sent By jwitmer Date 2017-07-24 Time 17:26 Rev Time 0.00
Received By jwitmer Date 2017-07-24 Time 14:59 Sent To  
Notes
2017-07-24 17:15:592014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050520
 ADD: 250 S. AUSTRALIAN AVE. SUITE: 1300
 CONT: CHANDLER CONSTRUCTION
 TEL: 561-791-6934
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. JULY 24/ 2017
 ACTION: BUILDING PROVISO
 APPROVED WITH EXCEPTION
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTIONS AND THE
 ASSESSMENT OF RE-INSPECTION FEES.
  
 1) SEMI-COMPLIED THE SHEETS ALS1,1 AND A1.1.3 STILL
 SHOW THE ACCESSIBILITY ISSUE,THE MAIL ROOM DOOR 1318
 MISSING THE REQUIRED 18 INCHES ON THE LATCH SIDE.
 ACCESS CODE 404.2.4.1 SWINGING DOORS AND GATES.
 SWINGING DOORS AND GATES SHALL HAVE MANEUVERING
 CLEARANCES COMPLYING WITH TABLE 404.2.4.1.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-26 Cont ID  
Sent By jwitmer Date 2017-05-26 Time 16:56 Rev Time 0.00
Received By jwitmer Date 2017-05-25 Time 16:27 Sent To  
Notes
2017-05-26 16:56:542014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050520
 ADD: 250 S. AUSTRALIAN AVE. SUITE: 1300
 CONT: CHANDLER CONSTRUCTION
 TEL: 561-791-6934
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 26, 2017
 ACTION: DENIED
  
 1) SHEET ALS1.1 THE RIGHT SIDE OF THE SHEET SHOWS A
 COMMON PATH OF TRAVEL OF 70.5 FEET. THE COMMON PATH OF
 TRAVEL STOPS SHORT, PLEASE CONTINUE THE COMMON PATH OF
 TRAVEL PAST THE ELEVATOR BANK TO WHERE YOU HAVE A
 CHOICE BETWEEN WHICH EXIT YOU WOULD WANT TO TRAVEL TOO.
 ELEVATORS WILL BE CALLED BACK TO THE 1ST FLOOR FOR THE
 FIREMANS USE. COMMON PATH OF TRAVEL IS LIMITED TO 100
 FT. PLEASE PROVIDE THE OVERALL DISTANCE. 2014 FBC-B
 TABLE 1014.3.
  
 2) SHEET A1.1.1 SHOWS THE MAIL ROOM DOOR 1318 MISSING
 THE REQUIRED 18 INCHES ON THE LATCH SIDE.
 ACCESS CODE 404.2.4.1 SWINGING DOORS AND GATES.
 SWINGING DOORS AND GATES SHALL HAVE MANEUVERING
 CLEARANCES COMPLYING WITH TABLE 404.2.4.1.
  
 3) SHEET A2.0:
 3A) THE WINDOW SCHEDULE DOES NOT SHOW COMPLIANCE WITH
 SAFETY GLAZING REQUIREMENTS PER TABLE 2406.2(2) OF THE
 2014 FBC-B.
  
 3B) THE DOOR TYPES SHOW A DOOR TYPE A WITH A SINGLE
 LIGHT WITHIN THE FRAME OF THE DOOR. THE PLANS DO NOT
 ADDRESS THE NEED FOR SAFETY GLAZING FOR THE GLAZING IN
 THE DOOR ITSELF. SHOW COMPLIANCE WITH TABLE 2406.2(2)
 OF THE 2014 FBC-B.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-07-17 Cont ID  
Sent By jpearson Date 2017-07-17 Time 10:07 Rev Time 0.00
Received By jpearson Date 2017-07-17 Time 10:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-06-05 Cont ID  
Sent By jpearson Date 2017-06-05 Time 14:11 Rev Time 0.00
Received By jpearson Date 2017-06-05 Time 14:11 Sent To  
Notes
2017-06-05 14:13:22CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. SHEET E0.1, ELECTRICAL SPECIFICATIONS, # C.11
 REFERENCES THE CITY OF BOYNTON BEACH CODES. PLEASE
 REMOVE NOTE FOR THIS PLAN. FBC 107.2.1
 2. SHEET E0.1, SHEET INDEX STATES THERE IS AN
 ELECTRICAL RISER DIAGRAM SHEET # E5.1. THIS SHEET IS
 MISSING. CLARIFY AND/OR CORRECT. FBC 107.2.1
 3. SPECIFY METHOD OF ATTACHING AND/OR SUPPORTING THE
 LAY IN LIGHT FIXTURES. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-30 Cont ID  
Sent By pleduc Date 2017-06-30 Time   Rev Time 0.00
Received By pleduc Date 2017-06-30 Time 12:13 Sent To  
Notes
2017-06-30 12:58:292ND REVIEW COMMENTS
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-05-16 Cont ID  
Sent By pleduc Date 2017-05-16 Time   Rev Time 0.00
Received By pleduc Date 2017-05-15 Time 17:05 Sent To  
Notes
2017-05-16 14:14:02THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-07-24 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-27 Time 14:45 Sent To  
Notes
2017-06-28 14:45:55C23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-09 Cont ID  
Sent By gjohnson Date 2017-06-09 Time 12:15 Rev Time 0.00
Received By gjohnson Date 2017-05-10 Time 14:17 Sent To  
Notes
2017-05-12 14:17:18C22

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-05-26 Cont ID  
Sent By jwitmer Date 2017-05-26 Time 15:39 Rev Time 0.00
Received By jwitmer Date 2017-05-25 Time 16:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-07-24 Cont ID  
Sent By ccole Date 2017-07-24 Time 11:16 Rev Time 0.00
Received By ccole Date 2017-07-24 Time 10:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-19 Cont ID  
Sent By ccole Date 2017-05-19 Time 13:59 Rev Time 0.00
Received By ccole Date 2017-05-19 Time 13:58 Sent To  
Notes
2017-05-19 14:11:371ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050520
 5/19/17
  
 RESULTS: DENIED
  
 1) THE PLAN SHOWS NEW TRANSFER OPENINGS FROM THE TENANT
 SPACES INTO THE CORRIDOR. CLARIFY IF AIR IS TO BE
 TRANSFERRED INTO THE CORRIDOR, OR ABOVE THE CORRIDOR
 CEILING IN A PLENUM SPACE. SEE SECTIONS 601.2 AND
 601.2.1 FOR EXCEPTIONS AND ALLOWANCES.
  
 2) PROVIDE THE FLEX DUCT SIZES ON THE DUCT LAYOUT PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-06-09 Cont ID  
Sent By gjohnson Date 2017-06-09 Time 12:15 Rev Time 0.00
Received By gjohnson Date 2017-06-09 Time 10:22 Sent To  
Notes
***NONE***