Plan Review Details - Permit 17050223
Plan Review Stops For Permit 17050223
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-07-13 Cont ID  
Sent By jgomez Date 2017-07-13 Time 17:56 Rev Time 0.00
Received By jgomez Date 2017-07-13 Time 15:32 Sent To  
Notes
2017-07-13 16:41:09BUILDING REVIEW APPROVED WITH PROVISO:
 1- INSPECTION REQUIRED FOR PROPOSED DRAINAGE PLAN.
 2- PROVIDE CORRECT AREA CALCULATION ON SHEET A-1.
 3- PROVIDE SURVEY W/ ORIGINAL SEAL/SIGNATURE.
 4- REVISE CARBON MONOXIDE ALARMS LOCATION.
 5- REVISE WINDOW/DOOR BUCK DETAILS. BEVELED BUCKS ARE
 NOT ALLOWED AND THE BUCK NEEDS TO PROVIDE FULL SUPPORT
 TO THE WINDOW/DOOR FRAME.
 6- REVISE ENERGY CALCULATIONS: (A) COMPLETE
 INFORMATION: OWNER NAME, PERMIT OFFICE, JURISDICTION
 NUMBER (604700). (B) NEED CALCULATIONS FOR THE ACTUAL
 ORIENTATION OF THE BUILDING, NOT WORST CASE. C) MISSING
 INFORMATION ABOUT ADJACENT WALL. D) REVISE TYPE AND
 MATERIALS OF THE ROOF INFORMATION. E) REVISE DOORS
 INFORMATION. NO INSULATED DOORS. REVISE SIZE ALSO. F)
 DOORS WITH GLASS NEED TO BE CONSIDERED IN THE WINDOW
 AREA. G) REVISE THE WINDOWS INFORMATION. THE OVERHANG
 SEPARATION DOESN'T MATCH PLANS. H) PROVIDE
 MANUFACTURER'S SPECIFICATIONS SHOWING THE SPECIFIED
 U-FACTOR AND SHGC FACTOR FOR DOORS AND WINDOWS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-07-07 Cont ID  
Sent By jgomez Date 2017-07-07 Time 16:44 Rev Time 0.00
Received By jgomez Date 2017-07-06 Time 17:16 Sent To  
Notes
2017-07-06 17:38:03NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR AGREES TO SUBMIT THE REQUIRED
 INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE
 INSPECTIONS TO AVOID CONFLICTS/DELAYS. REVISION FEES
 WILL APPLY. CONTRACTOR TO ADVICE IN WRITING IF PROVISO
 OPTION IS PREFERRED AT THIS TIME. PERMIT WILL BE
 PROCESSED ONCE THE ENERGY CALCULATIONS ARE SIGNED BY
 THE OWNER AND THE IMPACT FEE COUNTY STAMP ON PLANS AND
 COPY OF PAID FEES ARE SUBMITTED.
  
  
 1- AREA CALCULATION ON SHEET A-1 IS INCORRECT. REVISE
 AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
 RESPONSE: GARAGE AREA IS INCORRECT AND THE TOTAL AREA
 IS INCORRECT ALSO. REVISE AS REQUIRED.
  
 2-ENLARGED SURVEY SUBMITTED NEEDS THE ORIGINAL SEAL AND
 SIGNATURE OF THE SURVEYOR AS REQUIRED BY CHAPTER 472
 FLORIDA STATUTE. NOTE: ENGINEER OF RECORD SIGNED AND
 SEALED THE SURVEY. HE CAN NOT SIGN AND SEAL THE SURVEY
 IF IT WAS NOT DONE BY HIM. FAC 61G15-23.002.
 RESPONSE: NO SURVEY OR SITE PLAN WAS SUBMITTED AT THIS
 TIME. NEED SURVEY OR SITE PLANS AS REQUIRED BY SEC.
 107.3.5.3 CITY AMENDMENTS.
  
 3- ENGINEER OF RECORD TO SPECIFY CARBON MONOXIDE ALARMS
 ON PLANS AS REQUIRED BY SEC. R315 FBC-RESIDENTIAL.
 RESPONSE: ENGINEER TO CHECK SEC. R315 FBC-RESIDENTIAL
 AND REVISE ALARM LOCATION ON PLANS AS REQUIRED.
  
 4- WINDOW AND DOOR BUCK DETAILS AND SPECIFICATIONS
 SHOWN ON SHEET A-1: BEVELED BUCKS ARE NOT ALLOWED AND
 THE BUCK NEEDS TO PROVIDE FULL SUPPORT TO THE WINDOW
 AND DOOR FRAME. REVISE DETAILS AND SPECIFICATIONS AS
 REQUIRED TO SHOW COMPLIANCE. SEC. R612.7.2.1
 FBC-RESIDENTIAL.
 RESPONSE: DETAILS ON SHEET A-1 SPECIFY BEVELED BUCK AND
 NEED TO PROVIDE FULL SUPPORT TO THE DOOR FRAME. SEE
 DOORS PRODUCT APPROVAL FOR SIZE OF DOOR FRAME AND
 REVISE BUCK SIZE AS REQUIRED.
  
 5- REVISE ENERGY CALCULATIONS SUBMITTED:
 ENGINEER OF RECORD RESPONSE LETTER STATED THE
 FOLLOWING; " FORMS AND CALCULATIONS ARE IN PROCESS OF
 SUBSTANTIAL REVISIONS BY OTHERS. THEREFORE, AT THIS
 TIME IT IS REQUESTED THAT THE SUBJECT IS DEFERRED FOR A
 REASONABLE TIME".
 RESPONSE: NEED REVISED ENERGY CALCULATIONS SIGNED BY
 THE OWNER OR LEGALLY DESIGNATED AGENT ARE REQUIRED
 PRIOR TO RECEIVING THE PERMIT AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 A) AFTER THE ENERGY CALCULATIONS ARE REVISED, THE OWNER
 NEEDS TO CERTIFY AT THE BOTTOM OF THE FORM AS REQUIRED
 BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE: NOT ADDRESSED.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE OWNER NAME, PERMIT OFFICE AND
 JURISDICTION NUMBER (604700) . SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
 RESPONSE: NOT ADDRESSED.
  
 C) ENERGY CALCULATIONS SUBMITTED ARE DONE FOR THE WORST
 CASE SCENARIO. ENERGY CALCULATIONS NEED TO BE DONE FOR
 THE ACTUAL ORIENTATION OF THE BUILDING. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 RESPONSE: NOT ADDRESSED.
  
 D) ITEM #9 IS MISSING THE INFORMATION ABOUT THE
 ADJACENT WALL SEPARATING THE GARAGE FROM THE MAIN
 HOUSE. PROVIDE COMPLETE INFORMATION. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
 RESPONSE: NOT ADDRESSED.
 RESPONSE: NOT ADDRESSED.
  
 E) THE TYPE AND MATERIALS OF THE ROOF INFORMATION ON
 PAGE 2 OF 4 IS INCORRECT. SEE PLANS AND PRODUCT
 APPROVALS AND REVISE AS REQUIRED TO MATCH. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 RESPONSE: NOT ADDRESSED.
  
 F) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION. WHERE ARE THE
 INSULATED DOORS. ALSO, SIZE OF DOORS DON'T MATCH PLANS.
 SEE PLANS AND PRODUCT APPROVALS SUBMITTED AND REVISE AS
 REQUIRED TO MATCH.
 RESPONSE: NOT ADDRESSED.
  
 G) DOORS WITH GLASS NEED TO BE CONSIDERED IN THE WINDOW
 AREA AS REQUIRED BY SEC. R405.5.3.3 FBC-ENERGY
 CONSERVATION. SEE PLANS AND PRODUCT APPROVALS SUBMITTED
 AND REVISE AS REQUIRED TO MATCH.
 RESPONSE: NOT ADDRESSED.
  
 H) REVISE THE WINDOWS INFORMATION ON PAGE 3 OF 4. THE
 OVERHANG SEPARATION DOESN'T MATCH PLANS. SEE PLANS AND
 REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
 RESPONSE: NOT ADDRESSED.
  
 I) SINCE THE ENERGY CALCULATIONS (ITEM #7) ARE USING
 WINDOWS WITH A U-FACTOR AND SHGC FACTOR OTHER THAN THE
 DEFAULT FACTOR, THEN PROVIDE MANUFACTURER'S
 SPECIFICATIONS SHOWING THE CALCULATED FACTORS FOR ALL
 DOORS AND WINDOWS. NOTE: LABEL ON THE WINDOWS AND DOORS
 WILL BE REQUIRED AT TIME OF INSPECTION.
 SEC. R405.3 FBC-ENERGY CONSERVATION.
 RESPONSE: NOT ADDRESSED.
  
 ****ADD NOTE ON PROVISO FOR INSPECTOR TO CHECK THE
 ENGINEER'S DRAINAGE PROPOSAL.
  
 NOTES:
 *****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-06-02 Cont ID  
Sent By jgomez Date 2017-06-01 Time 18:58 Rev Time 0.00
Received By jgomez Date 2017-06-01 Time 07:09 Sent To  
Notes
2017-06-01 08:31:42NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT. COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED
 LAND DEVELOPMENT CODE.
  
 2- EGRESS WINDOWS:
 A) EGRESS WINDOWS 34SH SPECIFIED ON FLOOR PLAN ON SHEET
 A-1: TYPICALLY WINDOWS WITH THE SPECIFIED HEIGHT DON'T
 MEET THE EGRESS REQUIREMENT. SPECIFY THE MASONRY
 OPENING DIMENSIONS ON PLANS AND PROVIDE MANUFACTURER'S
 SPECIFICATIONS FOR THESE SINGLE HUNG PVC WINDOWS
 SHOWING THAT THEY MEET THE MINIMUM HEIGHT EGRESS
 REQUIREMENTS OF SEC. R310.1.2 FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 B) IT'S NOT CLEAR WHAT KIND OF WINDOWS ARE GOING TO BE
 INSTALLED. HORIZONTAL ROLLING WINDOWS NOA 16-0714.17
 WAS SUBMITTED. PLANS SPECIFY SINGLE HUNG WINDOWS. PLANS
 DON'T SPECIFY ANY HORIZONTAL ROLLING WINDOWS. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- DESIGN CRITERIA ON SHEET A-3:
 A) SPECIFY ROOF LOADS (LIVE AND DEAD), INCLUDING THE
 ATTIC LIVE LOAD AS REQUIRED BY NOTES "B" AND "G" OF
 TABLE R301.5 FBC-RESIDENTIAL.
  
 B) SPECIFY THE SOIL BEARING CAPACITY REQUIRED FOR THE
 STRUCTURE. SEC. R301.1 AND SEC. R401.2 FBC-RESIDENTIAL.
  
 4- THERE ARE SOME DIFFERENCES IN THE FOOTING DESIGN
 RECOMMENDATIONS SPECIFIED ON THE SOIL INVESTIGATION
 REPORT AND THE FOOTING DESIGN SHOWN ON PLANS. ENGINEER
 OF RECORD TO REVIEW THE SOIL INVESTIGATION REPORT AND
 RESPOND IN WRITING IF PROPOSED FOOTING SIZE IS ADEQUATE
 AND EXPLAIN HOW THE SOIL INVESTIGATION REPORT FOOTING
 RECOMMENDATIONS ARE ADDRESSED. NOTE: THIS ALSO INCLUDES
 THE SLAB ISOLATION RECOMMENDATION SPECIFIED ON PAGE 3
 OF THE SOIL INVESTIGATION REPORT.
 SEC. R403.1 FBC-RESIDENTIAL.
  
 5- PROVIDE PROPOSED SURFACE DRAINAGE PLAN. SURFACE
 WATER SHALL BE DIVERTED TO AN APPROVED COLLECTION POINT
 AS REQUIRED BY SEC. R401.3 FBC-RESIDENTIAL.
  
 6- ENLARGED SURVEY SUBMITTED NEEDS THE ORIGINAL SEAL
 AND SIGNATURE OF THE SURVEYOR AS REQUIRED BY CHAPTER
 472 FLORIDA STATUTE. NOTE: ENGINEER OF RECORD SIGNED
 AND SEALED THE SURVEY. HE CAN NOT SIGN AND SEAL THE
 SURVEY IF IT WAS NOT DONE BY HIM. FAC 61G15-23.002.
  
 7- ENGINEER OF RECORD TO SPECIFY CARBON MONOXIDE ALARMS
 ON PLANS AS REQUIRED BY SEC. R315 FBC-RESIDENTIAL.
  
 8- ENGINEER OF RECORD TO PROVIDE SPECIFICATIONS FOR THE
 GARAGE DOOR LEADING TO THE UTILITY AREA. SPECIFY FIRE
 RATING AND SELF CLOSING DEVICE AS REQUIRED BY SEC.
 R302.5.1 FBC-RESIDENTIAL.
  
 9- ATTIC ACCESS SHOWN ON FLOOR PLAN ON SHEET A-1:
 A) SPECIFY SIZE SHOWING COMPLIANCE WITH SEC. R807
 FBC-RESIDENTIAL.
  
 B) LOCATION OF THE ATTIC ACCESS IN THE GARAGE MAY NO
 PROVIDE THE MINIMUM HEADROOM REQUIRED BY SEC. R807
 FBC-RESIDENTIAL. SHOW COMPLIANCE WITH THE MIN. REQUIRED
 HEADROOM.
  
 10- WINDOW AND DOOR BUCK DETAILS AND SPECIFICATIONS
 SHOWN ON SHEET A-1: BEVELED BUCKS ARE NOT ALLOWED AND
 THE BUCK NEEDS TO PROVIDE FULL SUPPORT TO THE WINDOW
 AND DOOR FRAME. REVISE DETAILS AND SPECIFICATIONS AS
 REQUIRED TO SHOW COMPLIANCE. SEC. R612.7.2.1
 FBC-RESIDENTIAL.
  
 11- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. THE VALUATION WAS UPDATED TO $200,579. THE
 PERMIT FEE BALANCE IS $3882.89.
  
 12- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 THE GABLE END WALLS ON THE FRONT OF THE HOUSE SHOWING
 COMPLIANCE WITH SEC. R609.4 FBC-RESIDENTIAL. . ONLY
 SPECIFICATIONS FOR THE REAR GABLE END WALL WAS PROVIDED
 ON THE ROOF FRAMING PLAN ON SHEET A-3.
  
 13- SHEET A-3:
 A) ATTIC VENTILATION INFORMATION SHOWN BY THE ROOF
 FRAMING PLAN DOESN'T MATCH INFORMATION SHOWN ON THE
 TYPICAL WALL SECTION ON SAME SHEET. REVISE AS REQUIRED
 TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) CONCRETE SLAB STRENGTH SPECIFICATIONS SHOWN ON THE
 TYPICAL WALL SECTION DON'T MATCH SPECIFICATIONS SHOWN
 ON THE FOUNDATION PLAN ON SHEET A-2. REVISE AS REQUIRED
 TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 14- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) AFTER THE ENERGY CALCULATIONS ARE REVISED, THE OWNER
 NEEDS TO CERTIFY AT THE BOTTOM OF THE FORM AS REQUIRED
 BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE OWNER NAME, PERMIT OFFICE AND
 JURISDICTION NUMBER (604700) . SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 C) ENERGY CALCULATIONS SUBMITTED ARE DONE FOR THE WORST
 CASE SCENARIO. ENERGY CALCULATIONS NEED TO BE DONE FOR
 THE ACTUAL ORIENTATION OF THE BUILDING. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) ITEM #9 IS MISSING THE INFORMATION ABOUT THE
 ADJACENT WALL SEPARATING THE GARAGE FROM THE MAIN
 HOUSE. PROVIDE COMPLETE INFORMATION. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E) THE TYPE AND MATERIALS OF THE ROOF INFORMATION ON
 PAGE 2 OF 4 IS INCORRECT. SEE PLANS AND PRODUCT
 APPROVALS AND REVISE AS REQUIRED TO MATCH. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION. WHERE ARE THE
 INSULATED DOORS. ALSO, SIZE OF DOORS DON'T MATCH PLANS.
 SEE PLANS AND PRODUCT APPROVALS SUBMITTED AND REVISE AS
 REQUIRED TO MATCH.
  
 G) DOORS WITH GLASS NEED TO BE CONSIDERED IN THE WINDOW
 AREA AS REQUIRED BY SEC. R405.5.3.3 FBC-ENERGY
 CONSERVATION. SEE PLANS AND PRODUCT APPROVALS SUBMITTED
 AND REVISE AS REQUIRED TO MATCH.
  
 H) REVISE THE WINDOWS INFORMATION ON PAGE 3 OF 4. THE
 OVERHANG SEPARATION DOESN'T MATCH PLANS. SEE PLANS AND
 REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 I) SINCE THE ENERGY CALCULATIONS (ITEM #7) ARE USING
 WINDOWS WITH A U-FACTOR AND SHGC FACTOR OTHER THAN THE
 DEFAULT FACTOR, THEN PROVIDE MANUFACTURER'S
 SPECIFICATIONS SHOWING THE CALCULATED FACTORS FOR ALL
 DOORS AND WINDOWS. NOTE: LABEL ON THE WINDOWS AND DOORS
 WILL BE REQUIRED AT TIME OF INSPECTION.
 SEC. R405.3 FBC-ENERGY CONSERVATION.
  
 15- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 B) GABLE END VENTS AS SHOWN ON EXTERIOR ELEVATIONS.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 FRAMING PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR OR ENGINEER OF RECORD TO LIST THE
 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 D) HUGHES STRUCTURAL CONNECTORS SPECIFIED ON THE KNEE
 WALL DETAIL ON SHEET A-3. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR OR ENGINEER OF RECORD TO LIST THE
 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
  
 16- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 17- PROVIDE GARAGE DOOR STRUCTURAL BUCK DETAIL AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
  
 NOTES:
 *****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-07-14 Cont ID  
Sent By jleahy Date 2017-07-14 Time 13:01 Rev Time 0.00
Received By jleahy Date 2017-07-14 Time 11:26 Sent To P
Notes
2017-07-06 17:55:42NEW DRAWINGS SUBMITTED. JG.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-05-23 Cont ID  
Sent By jleahy Date 2017-05-23 Time 18:47 Rev Time 0.00
Received By jleahy Date 2017-05-23 Time 18:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2017-06-26 Time 14:17 Sent To  
Notes
2017-06-27 14:17:43R24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-02 Cont ID  
Sent By jgomez Date 2017-06-02 Time 10:57 Rev Time 0.00
Received By jgomez Date 2017-05-04 Time 14:55 Sent To  
Notes
2017-05-04 14:55:37R16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2017-07-13 Cont ID  
Sent By jgomez Date 2017-07-13 Time 18:19 Rev Time 0.00
Received By jgomez Date 2017-07-13 Time 18:19 Sent To  
Notes
2017-07-13 18:20:11NO FEES DUE. MU-2017-019361.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-07-07 Cont ID  
Sent By jgomez Date 2017-07-07 Time 17:16 Rev Time 0.00
Received By jgomez Date 2017-07-07 Time 17:16 Sent To  
Notes
2017-07-07 17:16:551- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT. COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED
 LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-06-01 Cont ID  
Sent By jgomez Date 2017-06-01 Time 10:37 Rev Time 0.00
Received By jgomez Date 2017-06-01 Time 10:37 Sent To  
Notes
2017-06-01 10:37:201- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT. COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED
 LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2017-07-13 Cont ID  
Sent By jgomez Date 2017-07-13 Time 17:56 Rev Time 0.00
Received By jgomez Date 2017-07-13 Time 17:56 Sent To  
Notes
2017-07-13 17:57:56NO INFORMATION SUBMITTED. PROVIDE COMPLETE A/C PLAN AND
 EQUIPMENT SIZING CALCULATIONS UNDER A SEPARATE PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-07-07 Cont ID  
Sent By jgomez Date 2017-07-07 Time 17:17 Rev Time 0.00
Received By jgomez Date 2017-07-07 Time 17:17 Sent To  
Notes
2017-07-07 17:19:031- PROVIDE COMPLETE INFORMATION UNDER A SEPARATE
 PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-06-02 Cont ID  
Sent By jgomez Date 2017-06-02 Time 09:15 Rev Time 0.00
Received By jgomez Date 2017-06-02 Time 09:15 Sent To  
Notes
2017-06-02 09:25:29NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- ACCORDING TO THE ENERGY CALCULATIONS SUBMITTED, IT
 LOOKS LIKE THE EQUIPMENT SIZING CALCULATIONS WERE DONE
 BASED ON THE WORST CASE SCENARIO (SEE BUILDING REVIEW
 COMMENTS). THE EQUIPMENT SIZING NEEDS TO BE CALCULATED
 BASED ON THE ACTUAL ORIENTATION OF THE BUILDING AS
 REQUIRED BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014). REVISE CALCULATIONS AND PROVIDE
 COMPLETE CALCULATIONS NOT JUST THE SUMMARY SHEET.
  
 2- PROVIDE COMPLETE A/C PLAN. NOTE: A/C PLAN TO INCLUDE
 THE EQUIPMENT MANUFACTURER AND MODEL SPECIFIED ON THE
 EQUIPMENT SIZING CALCULATIONS. SEC. 107.3.5.3(10) CITY
 AMENDMENTS.
  
 NOTE:
 *****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-07-14 Cont ID  
Sent By gjohnson Date 2017-07-14 Time 13:22 Rev Time 0.00
Received By gjohnson Date 2017-07-14 Time 13:10 Sent To  
Notes
2017-07-06 17:55:14NEW DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-05-09 Cont ID  
Sent By gjohnson Date 2017-05-09 Time 15:30 Rev Time 0.00
Received By gjohnson Date 2017-05-09 Time 12:01 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-06-02 Cont ID  
Sent By jgomez Date 2017-06-02 Time 10:55 Rev Time 0.00
Received By jgomez Date 2017-06-02 Time 10:54 Sent To  
Notes
2017-06-02 10:57:261) ROOF TILE NOA 16-0112.08.
  
 2) ROOF TILE ADHESIVE NOA 16-0222.01.

Review Stop Z ZONING
Rev No 2 Status P Date 2017-06-29 Cont ID  
Sent By njwira Date 2017-06-29 Time 11:17 Rev Time 0.00
Received By njwira Date 2017-06-28 Time 14:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-05-12 Cont ID  
Sent By njwira Date 2017-05-12 Time 16:30 Rev Time 0.00
Received By njwira Date 2017-05-12 Time 09:16 Sent To  
Notes
2017-05-12 16:31:219/12/17- PASSED
  
 LANDSCAPE PERMIT REQUIRED PRIOR TO CO
 DRIVEWAY PERMIT FAILED
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved