Plan Review Details - Permit 17050212
Plan Review Stops For Permit 17050212
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-11 Cont ID  
Sent By ccole Date 2017-05-11 Time 12:46 Rev Time 0.00
Received By ccole Date 2017-05-04 Time 11:38 Sent To  
Notes
2017-05-04 11:39:03ROUTED TO ZONING

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-11 Cont ID  
Sent By ccole Date 2017-05-11 Time 12:47 Rev Time 0.00
Received By ccole Date 2017-05-11 Time 12:47 Sent To  
Notes
2017-05-11 12:50:231ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050212
 5/11/17
  
 1) PROVIDE A PLAN THAT SHOWS THE LOCATION OF THE
 CONDENSER ON THE ROOF, INDICATE THE FUNCTION OF THE
 CONDENSER, AND PROVIDE AN EQUIPMENT SCHEDULE.
  
 2) PROVIDE WIND LOAD ENGINEERING FOR ANCHORING THE
 CONDENSER TO THE ROOF STRUCTURE- SECTION 301.15.
  
 3) BECAUSE THIS IS A SEPARATE PERMIT FROM THE PRIMARY,
 THE MECHANICAL CONTRACTOR MUST SUBMIT A COMPLETE PERMIT
 APPLICATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-05-09 Cont ID  
Sent By njwira Date 2017-05-09 Time 17:00 Rev Time 0.00
Received By njwira Date 2017-05-04 Time 15:38 Sent To M
Notes
***NONE***