Plan Review Details - Permit 17050052
Plan Review Stops For Permit 17050052
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-18 Cont ID  
Sent By shill Date 2017-05-18 Time 08:51 Rev Time 0.00
Received By shill Date 2017-05-18 Time 08:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-05-11 Cont ID  
Sent By shill Date 2017-05-11 Time 07:52 Rev Time 0.00
Received By shill Date 2017-05-10 Time 16:02 Sent To  
Notes
2017-05-11 07:52:33REDLINED PLAN - WHISPERMAT CS PER EMAIL FROM ARCHITECT
 JAMES PAINE 5/11/17
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-05-17 Cont ID  
Sent By jleahy Date 2017-05-15 Time 15:09 Rev Time 0.00
Received By jleahy Date 2017-05-15 Time 15:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-05-05 Cont ID  
Sent By wjolin Date 2017-05-05 Time 11:58 Rev Time 0.00
Received By wjolin Date 2017-05-05 Time 11:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2017-05-16 Time 13:22 Sent To  
Notes
2017-05-17 13:22:13B08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-15 Cont ID  
Sent By jleahy Date 2017-05-15 Time 15:09 Rev Time 0.00
Received By jleahy Date 2017-05-01 Time 10:39 Sent To  
Notes
2017-05-02 10:41:16B08

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-05-24 Cont ID  
Sent By ccole Date 2017-05-24 Time 17:19 Rev Time 0.00
Received By ccole Date 2017-05-24 Time 16:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-08 Cont ID  
Sent By ccole Date 2017-05-08 Time 12:35 Rev Time 0.00
Received By ccole Date 2017-05-08 Time 12:32 Sent To  
Notes
2017-05-08 12:38:571ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050052
 5/8/17
  
 RESULT: DENIED
 PLEASE ADDRESS THE COMMENTS LISTED BELOW.
  
 1) SHOW THE LOCATIONS OF THE REPLACED DIFFUSERS, AND
 CLARIFY IF THE NEW DROPPED CEILING IN THE KITCHEN WILL
 REQUIRE ANY AC OR EXHAUST DUCTWORK ALTERATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-23 Cont ID  
Sent By gjohnson Date 2017-05-23 Time 17:56 Rev Time 0.00
Received By gjohnson Date 2017-05-23 Time 17:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-05-11 Cont ID  
Sent By gjohnson Date 2017-05-11 Time 14:47 Rev Time 0.00
Received By gjohnson Date 2017-05-11 Time 14:47 Sent To  
Notes
***NONE***