Plan Review Details - Permit 17050035
Plan Review Stops For Permit 17050035
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-07 Cont ID  
Sent By ppetty Date 2017-08-07 Time 10:50 Rev Time 0.00
Received By ppetty Date 2017-08-07 Time 10:12 Sent To ENG-P
Notes
2017-08-07 10:51:12IN GEN/POOL BOX

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-05-23 Cont ID  
Sent By ppetty Date 2017-05-23 Time 11:19 Rev Time 0.00
Received By ppetty Date 2017-05-23 Time 11:15 Sent To  
Notes
2017-05-23 11:20:18TO FIRE

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-08-18 Cont ID  
Sent By pleduc Date 2017-08-18 Time   Rev Time 0.00
Received By pleduc Date 2017-08-17 Time 15:46 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-05-24 Cont ID  
Sent By pleduc Date 2017-05-24 Time   Rev Time 0.00
Received By pleduc Date 2017-05-24 Time 12:32 Sent To PC
Notes
2017-05-24 13:25:30THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE NO PLAN SHEETS SUBMITTAL THAT INDICATES
 LOCATION AND OR COMPLAINCE WITH ANY FIRE CODE.
  
 PLEASE PROVIDE DETAILED FLOOR PLAN SHEETS INDICATING
 LOCATION OF THE GENERATOR AND THE LOCATION AND
 IDENTIFICATION OF EACH PIECE OF EQUIPMENT IN THE ROOM.
  
  
  
 2) THERE IS NO SCOPE OF WORK SUBMITTED.
  
  
 PLEASE A DETAILED PROVIDE THE SCOPE OF WORK UNDER THIS
 PERMIT.
  
  
  
 3) THIS APPEARS TO BE AN EMERGENCY GENERATOR THAT
 PROVIDES EMERGENCY POWER TO THE LIFE SAFETY FEATURES OF
 THE BUILDING.
  
 IF SO, IT SHALL COMPLY WITH NFPA 110, STANDARD FOR
 EMERGENCY AND STANDBY POWER SYSTEMS.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE
 INDICATING NOTE OF THE PLAN SHEETS.
  
  
  
  
 4) THE EMERGENCY GENERATOR SHALL BE TIED INTO THE FIRE
 COMMAND ROOM. THE FIRE COMMAND CENTER SHALL COMPLY WITH
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL
 CONTAIN, BUT NOT LIMITED TO, THE FOLLOWING FEATURES:
  
 12. EMERGENCY AND STANDBY POWER STATUS INDICATORS
  
 14. GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
  
 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED
  
 PLEASE ENSURE COMPLAINCE AND PROVIDE AN APPLICABLE NOTE
 OF COMPLIANCE ON THE PLAN SHEETS.
  
  
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-18 Cont ID  
Sent By cpuell Date 2017-08-18 Time 13:32 Rev Time 0.00
Received By cpuell Date 2017-07-31 Time 15:29 Sent To  
Notes
2017-08-01 15:29:33RESUB ROUTED TO KMARTIN VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-31 Cont ID  
Sent By lmarchan Date 2017-05-31 Time 15:47 Rev Time 0.00
Received By lmarchan Date 2017-05-01 Time 09:57 Sent To  
Notes
2017-05-02 09:57:21ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2017-08-04 Cont ID  
Sent By   Date 2017-08-04 Time   Rev Time 0.00
Received By kmartin Date 2017-08-04 Time 12:18 Sent To E
Notes
2017-08-02 08:55:58ROUTED TO KEVIN MARTIN

Review Stop Z ZONING
Rev No 1 Status P Date 2017-05-10 Cont ID  
Sent By   Date 2017-05-10 Time   Rev Time 0.00
Received By kmartin Date 2017-05-10 Time 15:28 Sent To E
Notes
2017-05-02 14:53:06ROUTED TO KEVIN MARTIN