Plan Review Details - Permit 17041325
Plan Review Stops For Permit 17041325
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-06 Cont ID  
Sent By hmoser Date 2017-06-06 Time 09:51 Rev Time 0.00
Received By hmoser Date 2017-05-31 Time 09:41 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-03 Cont ID  
Sent By hmoser Date 2017-05-03 Time 15:27 Rev Time 0.00
Received By hmoser Date 2017-04-28 Time 13:59 Sent To  
Notes
2017-05-01 13:59:49MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-06-06 Cont ID  
Sent By hmoser Date 2017-06-06 Time 09:52 Rev Time 0.00
Received By hmoser Date 2017-06-06 Time 09:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-03 Cont ID  
Sent By hmoser Date 2017-05-03 Time 15:27 Rev Time 0.00
Received By hmoser Date 2017-05-03 Time 15:27 Sent To  
Notes
2017-05-03 15:39:39PLAN DENIED.
 1) PROVIDE CFM ON ALL SUPPLY AIR GRILLS. PER
 SECTION 107 FBC.
 2) REFER TO SECTION 107.2.1 LOCAL AMENDMENTS.
 PLAN MUST HAVE THE SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676