Plan Review Details - Permit 17041312
Plan Review Stops For Permit 17041312
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-15 Cont ID  
Sent By hmoser Date 2017-05-15 Time 11:07 Rev Time 0.00
Received By hmoser Date 2017-05-10 Time 12:26 Sent To  
Notes
2017-05-11 12:27:17HMOSER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-02 Cont ID  
Sent By hmoser Date 2017-05-02 Time 14:48 Rev Time 0.00
Received By hmoser Date 2017-04-28 Time 12:48 Sent To  
Notes
2017-05-01 12:48:43REVISION ROUTED TO HMOSER

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-05-15 Cont ID  
Sent By hmoser Date 2017-05-15 Time 11:07 Rev Time 0.00
Received By hmoser Date 2017-05-15 Time 11:03 Sent To  
Notes
2017-05-15 11:06:56PASS PROVISO
 REFER TO SECTION M1602.4 BALANCED RETURN AIR
 2014 RESIDENTIAL CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-02 Cont ID  
Sent By hmoser Date 2017-05-02 Time 14:48 Rev Time 0.00
Received By hmoser Date 2017-05-02 Time 14:36 Sent To  
Notes
2017-05-02 14:48:37REVISION DENIED
 1) PROVIDE CFM ON ALL SUPPLY GRILLS.
 2) MISSING DUCT SIZE ON LAUNDRY ROOM SUPPLY
 DUCT AND ALL RETURN AIR DUCT.
 3) APPLICATION IS FOR A/C CHANGE OUT PLAN
 CALLS FOR EXISTING CONDENSER. REFER TO SECTION 107
 FBC 2014
 4) REFER TO SECTION M1602.4 BALANCED RETURN AIR
 #3 (LAUNDRY ROOM) 2014 FBR CODE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676