Plan Review Details - Permit 17041259
Plan Review Stops For Permit 17041259
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-07-12 Cont ID  
Sent By cthroop Date 2017-07-12 Time 11:21 Rev Time 0.00
Received By cthroop Date 2017-07-12 Time 11:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-06 Cont ID  
Sent By cthroop Date 2017-06-06 Time 08:01 Rev Time 0.00
Received By cthroop Date 2017-06-06 Time 07:28 Sent To E
Notes
2017-06-06 08:05:20BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED.
  
 ADVISORY
  
 F.S. 553.80 (2) (B)
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-10 Cont ID  
Sent By cthroop Date 2017-05-10 Time 11:14 Rev Time 0.00
Received By cthroop Date 2017-05-10 Time 11:14 Sent To E
Notes
2017-05-10 11:18:23BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE DESIGN WIND LOADS FOR PROPOSED SIGN.
 2. PROVIDE SECTION VIEW OF EXISTING EXTERIOR WALL.
 3. PROVIDE ATTACHMENT DETAIL FOR PROPOSED SIGN TO
 EXISTING WALL.
  
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-07-12 Cont ID  
Sent By jleahy Date 2017-07-12 Time 07:38 Rev Time 0.00
Received By jleahy Date 2017-07-12 Time 07:38 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-06-06 Cont ID  
Sent By jleahy Date 2017-06-06 Time 08:59 Rev Time 0.00
Received By jleahy Date 2017-06-06 Time 08:59 Sent To  
Notes
2017-06-06 08:59:39SEE COMMENTS FROM 5/10/17 REVIEW JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-10 Cont ID  
Sent By jleahy Date 2017-05-10 Time 11:29 Rev Time 0.00
Received By jleahy Date 2017-05-10 Time 11:29 Sent To  
Notes
2017-05-10 11:46:39NO ELECTRIC SHOWN FOR SIGN. NEED DETAIL OF SIGN
 ELECTRIC AND BRANCH CKT
  
 JAKE LEAHY
 561-805-6713

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-05-25 Cont ID  
Sent By destabro Date 2017-05-25 Time 14:14 Rev Time 0.00
Received By destabro Date 2017-05-25 Time 14:14 Sent To B
Notes
2017-05-25 14:15:275/25/2017 - WITH ONLY TWO ANCHOR SITES, INSTALLATION
 WILL HAVE MINIMAL IMPACT ON THE HISTORIC FABRIC OF THIS
 BUILDING. SIGN MEETS DESIGN GUIDELINES FOR HISTORIC
 BUIDLINGS. DLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-12 Cont ID  
Sent By cthroop Date 2017-07-12 Time 11:21 Rev Time 0.00
Received By cthroop Date 2017-07-10 Time 14:50 Sent To  
Notes
2017-07-11 14:50:52RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-06 Cont ID  
Sent By jleahy Date 2017-06-06 Time 08:59 Rev Time 0.00
Received By jleahy Date 2017-05-22 Time 09:52 Sent To  
Notes
2017-05-23 09:52:40RESUB ROUTED TO KMARTIN VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-23 Cont ID  
Sent By lmarchan Date 2017-05-23 Time 09:51 Rev Time 0.00
Received By lmarchan Date 2017-04-27 Time 14:45 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-05-26 Time   Rev Time 0.00
Received By kmartin Date 2017-05-26 Time 11:06 Sent To B
Notes
2017-05-26 11:08:03PROVISO
 1. SIGN BAND WILL NOT BE PERMITTED WITH A VERTICAL
 SIGN. EXISTING SIGN SHALL BE REMOVED BEFORE THIS SIGN
 IS INSTALLED.
  
 FOR MORE INFO, PLEASE CONTACT KEVIN MARTIN, URBAN
 DESIGN PLANNER AT [email protected].
2017-05-23 14:06:07ROUTED TO KEVIN MARTIN

Review Stop Z ZONING
Rev No 1 Status F Date 2017-05-04 Cont ID  
Sent By lmarchan Date 2017-05-23 Time 09:51 Rev Time 0.00
Received By kmartin Date 2017-05-04 Time 10:03 Sent To B
Notes
2017-05-04 10:09:091. VERTICAL SIGNS SHALL NOT EXCEED 10 FEET IN VERTICAL
 DIMENSION.
 2. WIDTH DIMENSION MUST BE SHOWN ON DRAWINGS, SHALL NOT
 EXCEED TWO FEET.
 3. THE DISTANCE BETWEEN THE SIGN AND THE FA?ADE EDGE
 SHALL BE SHOWN, SHALL BE AT LEAST TWO FEET.
 4. SIGN BAND WILL NOT BE PERMITTED WITH A VERTICAL
 SIGN. FOR MORE INFO, PLEASE CONTACT KEVIN MARTIN, URBAN
 DESIGN PLANNER AT [email protected].