Plan Review Stops For Permit 17041135
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-07-19 Cont ID  
Sent By rmcdouga Date 2017-07-19 Time 19:00 Rev Time 0.00
Received By rmcdouga Date 2017-07-19 Time 08:14 Sent To M
Notes
2017-07-19 18:59:23PLAN
 REVIEW COMMENTS
  
 2ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE HEATING AND COOLING EQUIPMENT LISTED ON THE
 ENERGY FORM R405-2014 DOES NOT MATCH THE EQUIPMENT
 SPECIFIED ON THE MECHANICAL PLANS OR THE EQUIPMENT
 SIZING SUMMARY FORMS. PLEASE CORRECT. FBC ENERGY
 CONSERVATION - SECT. R103.2
  
 2) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD. FBC 107.3.4 -
 PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER
 FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING OF THE CERTAINTEED
 MODIFIED BITUMEN ROOFING SYSTEM AS REQUIRED BY
 LIMITATION NUMBER 7 ON PAGE 42 OF NOA NO. 14-0529.02.
  
 4) THE CASEMENT WINDOW SPECIFIED ON SHEET A-402.00 IS
 LARGER THAN THE MAXIMUM WINDOW SIZE ALLOWED BY NOA NO.
 16-0629.21. SUBMIT ANOTHER PRODUCT APPROVAL OR REVISE
 THE WINDOW SIZE. FBC-R301.2.1
  
 5) NOA NO. 07-1105.05 FOR THE MAXIM SKYLIGHT EXPIRED ON
 JANUARY 10, 2013. SUBMIT A CURRENT PRODUCT APPROVAL FOR
 THE SKYLIGHT. FBC 107.3.4
  
 6) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-18 Cont ID  
Sent By rmcdouga Date 2017-05-18 Time 19:00 Rev Time 0.00
Received By rmcdouga Date 2017-05-18 Time 17:48 Sent To  
Notes
2017-05-18 15:37:22PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF A SITE DRAINAGE PLAN THAT
 COMPLIES WITH FBC-R R401.3. SURFACE DRAINAGE SHALL BE
 DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS
 SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 2) FBC 107.3.5.3 - INDICATE THE MEANS OF TERMITE
 PROTECTION PROPOSED PURSUANT TO FBC-R318.
  
 3) R1001.10 WHERE THE FIREPLACE OPENING IS 6 SQUARE
 FEET (0.6 M2) OR LARGER, THE HEARTH EXTENSION SHALL
 EXTEND AT LEAST 20 INCHES (508 MM) IN FRONT OF AND AT
 LEAST 12 INCHES (305 MM) BEYOND EACH SIDE OF THE
 FIREPLACE OPENING.
  
 4) SPECIFY THE HEIGHT OF THE CHIMNEY ABOVE THE ROOF ON
 THE PLANS. R1003.9 CHIMNEYS SHALL EXTEND AT LEAST 2
 FEET (610 MM) HIGHER THAN ANY PORTION OF A BUILDING
 WITHIN 10 FEET (3048 MM), BUT SHALL NOT BE LESS THAN 3
 FEET (914 MM) ABOVE THE HIGHEST POINT WHERE THE CHIMNEY
 PASSES THROUGH THE ROOF.
  
 5) SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS
 WITH INSTALLATION REQUIREMENTS FOR THE 2 HR FIRE RATED
 INSULATED ALL-FUEL STAINLESS STEEL FLUE. FBC-R 1003.11
  
 6) SPECIFY THE DOOR TYPES FOR THE DOORS TO BEDROOMS 1
 AND 2 THAT ARE LOCATED IN W1-6 AND W1-8 ON THE PLANS.
 FBC 107.2.1
  
 7) SPECIFY THE DOOR TYPES FOR D1-1 AND D1-2. THEY WERE
 NOT IDENTIFIED ON THE PLANS. FBC 107.2.1
  
 8) THE ENERGY CALCULATIONS SPECIFY A VENTED ATTIC. SHOW
 COMPLIANCE WITH FBC-R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW. VENTILATION OPENINGS SHALL
 HAVE A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM
 AND 1/4 INCH (6.4 MM) MAXIMUM. VENTILATION OPENINGS
 HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH (6.4 MM)
 SHALL BE PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH
 SCREENING, HARDWARE CLOTH, OR SIMILAR MATERIAL WITH
 OPENINGS HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM)
 MINIMUM AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF
 FRAMING MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF
 SECTION R802.1.8. REQUIRED VENTILATION OPENINGS SHALL
 OPEN DIRECTLY TO THE OUTSIDE AIR. R806.2 THE MINIMUM
 NET FREE VENTILATING AREA SHALL BE 1/150 OF THE AREA OF
 THE VENTED SPACE.
  
 9) PROVIDE SIZING CALCULATIONS, SPECIFY THE SIZE AND
 LOCATIONS OF THE OVERFLOW SCUPPERS. FBC-R903.4.1
 OVERFLOW DRAINS AND SCUPPERS. WHEN OTHER MEANS OF
 DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW
 SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS
 THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES (102 MM)
 ABOVE THE FINISHED ROOF COVERING AND SHALL BE LOCATED
 AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL LEADERS OR
 DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW
 SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, PLUMBING. OVERFLOW DRAINS SHALL
 DISCHARGE TO AN APPROVED LOCATION AND SHALL NOT BE
 CONNECTED TO ROOF DRAIN LINES.
  
 10) THE ENERGY FORM R405 CONTAINS SOME ERRORS. FBC
 ENERGY CONSERVATION R101.5.1.1.2, R103.2 AND R405.4.2
 -THE NAME OF THE INDIVIDUAL COMPLETING THE COMPLIANCE
 REPORT IS REQUIRED.
 - THE RESIDENCE DOES NOT HAVE A METAL ROOF AS LISTED ON
 THE FORM UNDER ROOF MATERIALS.
 - THERE ARE THREE SEPARATE HEATING AND COOLING SYSTEMS.
 THE KBTU/HR HAVE BEEN COMBINED INTO ONE ON THE
 COMPLIANCE FORM.
 -THE SYSTEMS HAVE DIFFERENT SEERS AND NEED TO BE LISTED
 SEPARATELY IN ORDER TO SHOW THIS.
  
 11) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, SKYLIGHTS, WINDOW/GLASS TYPES,
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES.
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-07-11 Cont ID  
Sent By jpearson Date 2017-07-11 Time 13:58 Rev Time 0.00
Received By jpearson Date 2017-07-11 Time 13:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-19 Cont ID  
Sent By jleahy Date 2017-05-19 Time 10:33 Rev Time 0.00
Received By jleahy Date 2017-05-19 Time 10:33 Sent To  
Notes
2017-05-19 12:05:06JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL, AND 2011 NEC
  
 1) GENERAL SPACING OF THE OUTLETS IN THE UNIT ARE NOT
 PER CODE, MASTR BEDROOM, KITCHEN, LIVING ROOM
  
 E3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829
  
 E3901.2.2 WALL SPACE.
 AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE
 FOLLOWING:
  
 1. ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN WIDTH,
 INCLUDING SPACE MEASURED AROUND CORNERS, AND THAT IS
 UNBROKEN ALONG THE
 FLOOR LINE BY DOORWAYS AND SIMILAR OPENINGS,
 FIREPLACES, AND FIXED CABINETS.
  
 2. THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR
 WALLS, EXCLUDING SLIDING PANELS.
  
 3. THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS
 RAILINGS AND FREESTANDING BAR-TYPE COUNTERS.
  
 E3901.2.3 FLOOR RECEPTACLES.
 RECEPTACLE OUTLETS IN FLOORS SHALL NOT BE COUNTED AS
 PART OF THE REQUIRED NUMBER OF RECEPTACLE OUTLETS
 EXCEPT WHERE LOCATED WITHIN 18 INCHES (457 MM) OF THE
 WALL.
  
 2) SERVICE CALCULATION APPEARS TO HAVE COMMERCIAL
 ALLOWANCES NOT ALLOWED BY RESIDENTIAL CODE.
 PANEL SCHEDULE AND LOAD CALCULATION IS VERY SMALL AND
 HARD TO READ PLEASE MAKE THESE ITEMS LARGER ON
 RESUBMITTAL FOR REVIEW. ALTHOUGH THEY ARE IN A GREAT
 FROMAT
 THEY ARE TO SMAL TO READ.
  
 E3602.2 SERVICE LOAD.
 THE MINIMUM LOAD FOR UNGROUNDED SERVICE CONDUCTORS AND
 SERVICE DEVICES THAT SERVE 100 PERCENT OF THE DWELLING
 UNIT LOAD SHALL BE COMPUTED IN ACCORDANCE WITH
 TABLE E3602.2. UNGROUNDED SERVICE CONDUCTORS AND
 SERVICE DEVICES THAT SERVE LESS THAN 100 PERCENT OF THE
 DWELLING UNIT LOAD SHALL BE COMPUTED AS REQUIRED FOR
 FEEDERS IN ACCORDANCE WITH CHAPTER 37.
  
 3) SMOKE ALARMS AND CARBON MONOXIDE ALARMS NOT PER
 CODE.
  
 R314.2 SMOKE DETECTION SYSTEMS.
 HOUSEHOLD FIRE ALARM SYSTEMS INSTALLED IN ACCORDANCE
 WITH NFPA 72 THAT INCLUDE SMOKE ALARMS, OR A
 COMBINATION OF SMOKE DETECTOR AND AUDIBLE NOTIFICATION
 DEVICE
 INSTALLED AS REQUIRED BY THIS SECTION FOR SMOKE ALARMS,
 SHALL BE PERMITTED. THE HOUSEHOLD FIRE ALARM SYSTEM
 SHALL PROVIDE THE SAME LEVEL OF SMOKE DETECTION AND
 ALARM
 AS REQUIRED BY THIS SECTION FOR SMOKE ALARMS. WHERE A
 HOUSEHOLD FIRE WARNING SYSTEM IS INSTALLED USING A
 COMBINATION OF SMOKE DETECTOR AND AUDIBLE NOTIFICATION
 DEVICE(S), IT SHALL BECOME A PERMANENT FIXTURE OF THE
 OCCUPANCY AND OWNED BY THE HOMEOWNER. THE SYSTEM SHALL
 BE MONITORED BY AN APPROVED SUPERVISING STATION
 AND BE MAINTAINED IN ACCORDANCE WITH NFPA 72.
  
 EXCEPTION: WHERE SMOKE ALARMS ARE PROVIDED MEETING THE
 REQUIREMENTS OF SECTION R314.4.
  
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
  
 1. IN EACH SLEEPING ROOM.
  
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL
  
 R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE,
 A FIREPLACE, AN ATTACHED GARAGE, OR OTHER FEATURE,
 FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE AS
 BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048 MM) OF
 EACH ROOM USED FOR SLEEPING PURPOSES.
  
 R315.1.1 CARBON MONOXIDE ALARM.
 THE REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED
 BY PROVIDING FOR ONE OF THE FOLLOWING ALARM
 INSTALLATIONS:
  
 (1) A HARD-WIRED CARBON MONOXIDE ALARM.
  
 (2) A BATTERY-POWERED CARBON MONOXIDE ALARM.
  
 (3) A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE
 ALARM.
  
 (4) A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND
 SMOKE ALARM.
  
 R315.1.2 COMBINATION ALARMS.
 COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-07-13 Cont ID  
Sent By gjohnson Date 2017-07-13 Time 09:49 Rev Time 0.00
Received By gjohnson Date 2017-07-13 Time 09:49 Sent To  
Notes
2017-07-13 10:43:181ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SYSTEM SHALL BE SIZED FOR MAX GAS DEMAND PER FBC
 FG 402.2 THE TANKLESS WATER MAX LOAD SHALL BE LISTED AT
 199 MBH NOT 25 MBH WHICH WILL MAKE YOUR TOTAL GAS LOAD
 ON THE SYSTEM 319 MBH PLEASE CLARIFY ON PLAN. PER WPB
 AMEND TO FBC 107.2.1
  
 2. PER THE MANUFACTURE SPECS THE TANKLESS HEATER IS
 DESIGNED TO BE A DIRECT VENT THE DETAIL DRAWING ON SHT
 P-2.0 IS SHOWING ONLY EXAUST PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 3. THIS APPEARS TO BE DESIGNED AS A 2LB SYSTEM IF SO
 PLEASE SHOW REGULATORS AT EACH APPLIANCE. PER FBC FG
 410.1
  
 4 PLEASE PROVIDE MANUFACTURE SPECIFICATION THAT SHOW
 THE STANDARDS THAT THEY COMPLY WITH THE ONES THAT ARE
 IN THE SUBMITTAL PACKAGE NOW DO NOT SHOW COMPLIANCE.
 PER FBC FG 301.3 AND 301.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-05-22 Cont ID  
Sent By gjohnson Date 2017-05-22 Time 16:25 Rev Time 0.00
Received By gjohnson Date 2017-05-22 Time 16:24 Sent To  
Notes
2017-05-22 16:43:451ST REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS: DENIED 5/22/17
  
 1. THE GAS WATER HEATER ON THE RISER AND GAS FIXTURE
 LOAD SUMMERY LIST THE MBH AT 25 ON SHT P-1.0 NOTE #7 IT
 LIST THE MBH AT 199 PLEASE CLARIFY PER WPB AMEND TO FBC
 107.2.1
  
 2. THE LONGEST RUN IS LISTED AT 20' THE MEASUREMENTS ON
 THE RISER ADD UP TO 56' PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 3. USING THE LONGEST RUN METHOD OF SIZING, YOUR FIRST
 SECTION OF PIPE IS UNDERSIZED PER FBC FG TABLE
 402.4(10(20) IT SHOULD BE 11/4" THE SECTION TO TEE FOR
 THE DRYER SHOULD BE 1" THE SECTION TO TANKLESS HEATER
 SHOULD BE 1"
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 5. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 6. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND
 INSTALLATION GUIDE FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS SEC. 402.2
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-21 Cont ID  
Sent By hmoser Date 2017-07-21 Time 12:07 Rev Time 0.00
Received By hmoser Date 2017-06-21 Time 14:35 Sent To  
Notes
2017-06-22 14:35:21R27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-22 Cont ID  
Sent By njwira Date 2017-05-22 Time 16:43 Rev Time 0.00
Received By gjohnson Date 2017-04-25 Time 13:57 Sent To  
Notes
2017-04-26 13:57:57R27

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-05-16 Cont ID  
Sent By rmcdouga Date 2017-05-16 Time 17:07 Rev Time 0.00
Received By rmcdouga Date 2017-05-16 Time 17:07 Sent To  
Notes
2017-05-16 17:08:33BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-07-21 Cont ID  
Sent By hmoser Date 2017-07-21 Time 12:07 Rev Time 0.00
Received By hmoser Date 2017-07-21 Time 11:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-05-22 Cont ID  
Sent By hmoser Date 2017-05-22 Time 10:35 Rev Time 0.00
Received By hmoser Date 2017-05-19 Time 15:29 Sent To  
Notes
2017-05-22 10:35:05PLAN DENIED
 1) PROVIDE MANUFACTURE SPECKS ON KITCHEN HOOD
 PER SECTION M1301.3 FBC RESIDENTIAL 2014
 2) PROVIDE THE MANUFACTURE ON THE EQUIPMENT
 SCHEDULE SECTION 107 FBC.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-07-13 Cont ID  
Sent By gjohnson Date 2017-07-13 Time 09:49 Rev Time 0.00
Received By gjohnson Date 2017-07-12 Time 17:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-22 Cont ID  
Sent By gjohnson Date 2017-05-22 Time 16:15 Rev Time 0.00
Received By gjohnson Date 2017-05-22 Time 16:15 Sent To  
Notes
2017-05-22 16:24:391ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: DENIED
  
 1. PLEASE PROVIDE DETAIL AND SIZING CALC FOR OVERFLOW
 SCUPPER ON ROOF TO SHOW COMPLIANCE WITH. FBC RES
 903.4.1
  
 2. SHT. P-1.0 + P-3.0 THE SOIL STACK SHALL CONNECT TO
 BUILDING DRAIN DOWN STEAM OF TH POWDER ROOM BATHROOM
 GROUP. PER FBC RES P3108.1
  
 3. SHT P-2.0 DETAIL #7 SHOWS A FLOOR MOUNT TANK TYPE
 WATER HEATER THE OTHER DRAWING SHOW A TANKLESS PLEASE
 CLARIFY. WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2017-06-28 Cont ID  
Sent By njwira Date 2017-06-28 Time 16:01 Rev Time 0.00
Received By njwira Date 2017-06-28 Time 14:30 Sent To  
Notes
2017-06-28 16:08:556/28-17- FAILED
  
 PROFESSIONAL OFFICE RESIDENTIAL
  
 FAILED
  
 1. REAR SETBACK IS 10FT. AND DOESN'T MEET 15FT.
 REQUIREMENT
 2. DRIVEWAY CURBCUT IS 26FT. EXCEEDING 25FT. LIMIT
 3. GARAGE APARTMENT IS NOT PERMITTED
 4. STAIRWAY MUST STAY COMPLETLY WITHIN THE BUILDING.
 5. WHAT IS THE TOTAL OPEN SPACE IT MUST BE 60%
 6. WHAT IS THE TOTAL LANDSCAPED AREA 15%?
 7. WHAT IS THE ROOF OVERHANG
 8. LANDSCAPE PLAN REQUIRED PRIOR TO CO
  
 PASSED
 1. MAXIMUM FAR IS 3,137.7 AND PROPSED 2,188SQFT.
 2. ONE KITCHEN IS ONE UNIT
 3. 26FT. HIGH BUILDING MEETS 40FT. HEIGHT LIMIT
 4. FRONT SETBACK IS 37FT. MEETING 25FT. REQUIREMENT
 5. SIDE SETBACK IS 10FT. MEETING 10FT. REQUIREMENT
 6. CORNER SIDE SETBACK IS 27FT. MEETING 15FT.
 REQUIREMENT
 7. SINGLE FAMILY DWELLING UNITS PERMITTED
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-05-05 Cont ID  
Sent By njwira Date 2017-05-05 Time 16:53 Rev Time 0.00
Received By njwira Date 2017-05-05 Time 16:53 Sent To I
Notes
2017-05-05 17:13:595/5/17- FAILED
  
 LANDSCAPE PERMIT REQUIRED PRIOR TO CO
 NO SURVEY
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved