2017-05-18 15:37:22 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SUBMIT TWO SETS OF A SITE DRAINAGE PLAN THAT |
| COMPLIES WITH FBC-R R401.3. SURFACE DRAINAGE SHALL BE |
| DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED |
| POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS |
| SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM). |
| EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| PERCENT AWAY FROM THE BUILDING. |
| |
| 2) FBC 107.3.5.3 - INDICATE THE MEANS OF TERMITE |
| PROTECTION PROPOSED PURSUANT TO FBC-R318. |
| |
| 3) R1001.10 WHERE THE FIREPLACE OPENING IS 6 SQUARE |
| FEET (0.6 M2) OR LARGER, THE HEARTH EXTENSION SHALL |
| EXTEND AT LEAST 20 INCHES (508 MM) IN FRONT OF AND AT |
| LEAST 12 INCHES (305 MM) BEYOND EACH SIDE OF THE |
| FIREPLACE OPENING. |
| |
| 4) SPECIFY THE HEIGHT OF THE CHIMNEY ABOVE THE ROOF ON |
| THE PLANS. R1003.9 CHIMNEYS SHALL EXTEND AT LEAST 2 |
| FEET (610 MM) HIGHER THAN ANY PORTION OF A BUILDING |
| WITHIN 10 FEET (3048 MM), BUT SHALL NOT BE LESS THAN 3 |
| FEET (914 MM) ABOVE THE HIGHEST POINT WHERE THE CHIMNEY |
| PASSES THROUGH THE ROOF. |
| |
| 5) SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS |
| WITH INSTALLATION REQUIREMENTS FOR THE 2 HR FIRE RATED |
| INSULATED ALL-FUEL STAINLESS STEEL FLUE. FBC-R 1003.11 |
| |
| 6) SPECIFY THE DOOR TYPES FOR THE DOORS TO BEDROOMS 1 |
| AND 2 THAT ARE LOCATED IN W1-6 AND W1-8 ON THE PLANS. |
| FBC 107.2.1 |
| |
| 7) SPECIFY THE DOOR TYPES FOR D1-1 AND D1-2. THEY WERE |
| NOT IDENTIFIED ON THE PLANS. FBC 107.2.1 |
| |
| 8) THE ENERGY CALCULATIONS SPECIFY A VENTED ATTIC. SHOW |
| COMPLIANCE WITH FBC-R806.1 VENTILATION REQUIRED. |
| ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| ENTRANCE OF RAIN OR SNOW. VENTILATION OPENINGS SHALL |
| HAVE A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM |
| AND 1/4 INCH (6.4 MM) MAXIMUM. VENTILATION OPENINGS |
| HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH (6.4 MM) |
| SHALL BE PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH |
| SCREENING, HARDWARE CLOTH, OR SIMILAR MATERIAL WITH |
| OPENINGS HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM) |
| MINIMUM AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF |
| FRAMING MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF |
| SECTION R802.1.8. REQUIRED VENTILATION OPENINGS SHALL |
| OPEN DIRECTLY TO THE OUTSIDE AIR. R806.2 THE MINIMUM |
| NET FREE VENTILATING AREA SHALL BE 1/150 OF THE AREA OF |
| THE VENTED SPACE. |
| |
| 9) PROVIDE SIZING CALCULATIONS, SPECIFY THE SIZE AND |
| LOCATIONS OF THE OVERFLOW SCUPPERS. FBC-R903.4.1 |
| OVERFLOW DRAINS AND SCUPPERS. WHEN OTHER MEANS OF |
| DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW |
| SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS |
| THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES (102 MM) |
| ABOVE THE FINISHED ROOF COVERING AND SHALL BE LOCATED |
| AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL LEADERS OR |
| DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW |
| SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, PLUMBING. OVERFLOW DRAINS SHALL |
| DISCHARGE TO AN APPROVED LOCATION AND SHALL NOT BE |
| CONNECTED TO ROOF DRAIN LINES. |
| |
| 10) THE ENERGY FORM R405 CONTAINS SOME ERRORS. FBC |
| ENERGY CONSERVATION R101.5.1.1.2, R103.2 AND R405.4.2 |
| -THE NAME OF THE INDIVIDUAL COMPLETING THE COMPLIANCE |
| REPORT IS REQUIRED. |
| - THE RESIDENCE DOES NOT HAVE A METAL ROOF AS LISTED ON |
| THE FORM UNDER ROOF MATERIALS. |
| - THERE ARE THREE SEPARATE HEATING AND COOLING SYSTEMS. |
| THE KBTU/HR HAVE BEEN COMBINED INTO ONE ON THE |
| COMPLIANCE FORM. |
| -THE SYSTEMS HAVE DIFFERENT SEERS AND NEED TO BE LISTED |
| SEPARATELY IN ORDER TO SHOW THIS. |
| |
| 11) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| ROOFING MATERIALS, SKYLIGHTS, WINDOW/GLASS TYPES, |
| STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES. |
| |
| 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |
| |
| |
| |