| THIS OFFICE HAS REVIEWED THE INFORMATIO PROVIDED BY THE |
| APPLICANT, VIA EMAIL, AS WELL AS THE INTENDED LOCATION |
| (THE PARKING AREA BETWEEN THE TWO WAREHOUSES LISTED AS |
| 432 25TH STREET) . AT THIS TIME, OUR POSITION REMAINS |
| UNCHANGED REGARDING THE DENIAL OF THE EVENT APPLICATION |
| FOR NON-COMPLIANCE WITH THE REQUIREMENTS OF THE FLORIDA |
| FIRE PREVENTION CODE FOR ASSEMBLY OCCUPANCIES, AS |
| LISTED BELOW. |
| |
| PER NFPA 101, CHAPTER 12 - NEW ASSEMBLY OCCUPANCIES |
| 12.2.4.4 ?? A FENCED OUTDOOR ASSEMBLY OCCUPANCY SHALL |
| HAVE NOT LESS THAN TWO REMOTE MEANS OF EGRESS FROM THE |
| ENCLOSURE IN ACCORDANCE WITH 7.5.1.3. |
| 12.2.8 MEANS OF EGRESS, OTHER THAN FOR PRIVATE PARTY |
| TENTS NOT EXCEEDING 1200 FT2, SHALL BE ILLUMINATED IN |
| ACCORDANCE WITH SECTION 7.8. |
| 12.2.9.1 ?? EMERGENCY LIGHTING SHALL BE PROVIDED IN |
| ACCORDANCE WITH SECTION 7.9. |
| |
| PER NFPA 101, CHAPTER 7 - MEANS OF EGRESS |
| 7.5.1.3.1 ?? WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR |
| EXIT DISCHARGE IS REQUIRED FROM A BUILDING OR PORTION |
| THEREOF, SUCH EXITS, EXIT ACCESSES, OR EXIT DISCHARGES |
| SHALL BE REMOTELY LOCATED FROM EACH OTHER AND BE |
| ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE |
| HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR |
| OTHER EMERGENCY CONDITION. |
| 7.5.1.3.2* ?? WHERE TWO EXITS, EXIT ACCESSES, OR EXIT |
| DISCHARGES ARE REQUIRED, THEY SHALL BE LOCATED AT A |
| DISTANCE FROM ONE ANOTHER NOT LESS THAN ONE-HALF THE |
| LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE |
| BUILDING OR AREA TO BE SERVED, MEASURED IN A STRAIGHT |
| LINE BETWEEN THE NEAREST EDGE OF THE EXITS, EXIT |
| ACCESSES, OR EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED |
| IN 7.5.1.3.3 THROUGH 7.5.1.3.5. |
| |
| ADDITIONALLY, THE FOLLOWING QUESTIONS AND/OR DETAILS |
| HAVE NOT BEEN ADDRESSED BY NEITHER THE SUBMITTED HAND |
| DRAWING NOR THE EMAIL BELOW. |
| |
| 1) HOW WILL THE OCCUPANT LOAD OF 250 PERSONS (AS |
| PROVIDED IN THE APPLICATION BY THE APPLICANT) BE |
| ENFORCED? |
| |
| 2) ASSEMBLY OCCUPANCIES ARE REQUIRED TO HAVE ONE |
| PROPERLY TRAINED (1) CROWD MANAGER FOR EVERY 250 |
| PERSONS. |
| |
| 3) THE INFORMATION BELOW, AS WELL AS THE DRAWING |
| SUBMITTED WITH THE INITIAL APPLICATION INDICATES THAT |
| THIS PROPERTY HAS 2 DOORS AND/OR GATES AT THE FRONT OF |
| THE PROPERTY. A REVIEW OF THE PROPERTY SHOWS 1 MANUAL |
| GATE DOOR, APPROXIMATELY, 10-15 FEET IN WIDTH. THE |
| DETAILS PROVIDED ARE INACCURATE. |
| |
| 4) WILL THERE BE ANY ACCESS TO THE INTERIOR OF THE |
| NEIGHBORING WAREHOUSE SPACES BY STAFF OR THE GENERAL |
| PUBLIC? HOW WILL THIS BE MONITORED? |
| |
| 5) HOW IS THE ELECTRICAL SERVICE TO THE MUSIC STAGE AND |
| THE FOOD TENT BEING SUPPLIED? |
| |
| 6) THE FOOD TENT IS LABELED AS "FINGER FOODS". |
| ADDITIONAL DETAILS REQUIRED? WILL THERE BE ANY COOKING |
| AND/OR WARMING OF FOODS? IF SO, HOW WILL THIS BE |
| ACCOMPLISHED? |
| |
| 7) EMERGENCY NOTIFICATION IS REQUIRED, EVEN FOR OUTDOOR |
| EVENTS. HOW WILL THIS BE ACCOMPLISHED IN A MANNER THAT |
| IS IMMEDIATE, EFFICIENT, AND EFFECTIVE FOR THIS TYPE OF |
| EVENT? |
| |
| 8) DETAILS REGARDING QUANTITY AND LOCATION OF FIRE |
| EXTINGUISHERS HAS NOT BEEN PROVIDED. |
| |
| |