Plan Review Details - Permit 17041058
Plan Review Stops For Permit 17041058
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-05 Cont ID  
Sent By jwitmer Date 2017-06-05 Time 10:44 Rev Time 0.00
Received By jwitmer Date 2017-06-05 Time 10:08 Sent To  
Notes
2017-06-05 10:44:032014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17041058
 ADD: 525 S. FLAGLER DR. SUITE # 18C
 CONT: BUTLER
 TEL: 561-832-9700
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 05/ 2017
 ACTION: BUILDING PROVISO
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-05 Cont ID  
Sent By jwitmer Date 2017-05-05 Time 10:36 Rev Time 0.00
Received By jwitmer Date 2017-05-05 Time 10:23 Sent To  
Notes
2017-05-05 10:36:542014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17041058
 ADD: 525 S. FLAGLER DR. SUITE # 18C
 CONT: BUTLER
 TEL: 561-832-9700
 E-MAIL: ???????????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 05/ 2017
 ACTION: DENIED
  
 1) THE PLANS MAY BE DRAWN TO AT LEAST 1/8 INCH SCALE
 BUT THE WORDING IS TOO SMALL TO BE LEGIBLE WHEN
 SCANNING IN FOR RECORD RETENTION.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.4 QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 2) THE DESIGNER OF RECORD NEEDS TO ADD THEIR LICENSE
 NUMBER TO THE PLANS THEY HAVE CREATED.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-06-22 Cont ID  
Sent By jpearson Date 2017-06-22 Time 08:33 Rev Time 0.00
Received By jpearson Date 2017-06-22 Time 08:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-06-07 Cont ID  
Sent By jpearson Date 2017-06-07 Time 08:56 Rev Time 0.00
Received By jpearson Date 2017-06-07 Time 08:56 Sent To  
Notes
2017-06-07 09:13:08CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW. ELECTRICAL PLAN
 REQUIRED TO BE SIGNED BY ELECTRICAL QUALIFIER OR DESIGN
 PROFESSIONAL. FBC 107.3.5, FS 471.003(2)(H), 471.025
 2. PROVIDE FLOOR PLAN INDICATING LOCATION OF REQUIRED
 SMOKE ALARMS. IF NONE ARE EXISTING, OR NOT TO CODE,
 SHOW AS NEW INSTALLATION. FBC 907.2.11
 3. PROVIDE LOCATION ON PLAN OF ALL OUTLETS IN KITCHEN
 PER CODE. SHOW AS EXISTING OR NEW AS REQUIRED. NEC
 210.52
 4. PROVIDE PANEL SCHEDULE, INDICATE ANY NEW OR ALTERED
 CIRCUITS, AFCI OR GFCI PROTECTION WHERE APPLICABLE. NEC
 408.4, 210.8, 210.12(B)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-08 Cont ID  
Sent By jleahy Date 2017-05-08 Time 14:53 Rev Time 0.00
Received By jleahy Date 2017-05-08 Time 14:53 Sent To  
Notes
2017-05-08 14:55:02JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 COMPLY WITH FIRE DEPT COMMENTS.
 IF YOU ARE RELOCATING OR DELETING ITEMS PLEASE NOTE ON
 DRAWINGS

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-05 Cont ID  
Sent By pleduc Date 2017-06-05 Time   Rev Time 0.00
Received By pleduc Date 2017-06-05 Time 11:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-04-27 Cont ID  
Sent By pleduc Date 2017-04-27 Time   Rev Time 0.00
Received By pleduc Date 2017-04-27 Time 09:49 Sent To  
Notes
2017-04-27 14:55:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE IS NO TITLE BLOCK ON THE SUBMITTED SHEET THAT
 INCLUDE THE ADDRESS, APT # AND DESIGN PROFESSIONAL.
  
 PLEASE CORRECT.
  
  
  
  
 2) THE PRINT IS TOO SMALL AND UNREADABLE IN SOME AREAS.
  
 PLEASE ENLARGE
  
  
  
  
 3) THERE IS APPEARS TO WALLS BEING REMOVED AND CEILING
 WORK PROPOSED IN THE KITCHEN AREA.
  
 IT IS UNCLEAR WHAT IS EXSITING AND WHAT IS NEW.
  
 PLEASE CLARIFY OR PROVIDE BETTER DETAIL.
  
  
  
  
 4) ANY REMOVAL OR CONSTRUCTION OF NEW WALLS OR CEILING
 SPACES REQUIRES AN EVALUATION OF THE FIRE SPRINKLER
 COVERAGE AND PROTECTION. THERE IS NO INDICATION OF
 EXISTING SPRINKLERS OR ANY WORK BEING DONE.
  
 ANY FIRE SPRINKLER OR FIRE ALARM WORK SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ALL APPLICABLE
 INFORMATION AND COMPLIANCE.
  
  
  
  
 5) THERE APPEAR TO BE BE NEW WORK IN THE BATHROOM
 CEILING AREA.
  
 IT IS UNCLEAR WHAT IS EXSITING AND WHAT IS NEW.
  
 PLEASE CLARIFY OR PROVIDE BETTER DETAIL.
  
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-22 Cont ID  
Sent By jpearson Date 2017-06-22 Time 08:34 Rev Time 0.00
Received By jpearson Date 2017-06-20 Time 12:56 Sent To  
Notes
2017-06-21 12:56:39RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-13 Cont ID  
Sent By gjohnson Date 2017-06-13 Time 15:25 Rev Time 0.00
Received By gjohnson Date 2017-06-01 Time 14:32 Sent To  
Notes
2017-06-01 14:37:13B04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-11 Cont ID  
Sent By shill Date 2017-05-08 Time 07:10 Rev Time 0.00
Received By shill Date 2017-04-24 Time 14:26 Sent To  
Notes
2017-04-25 14:26:35B07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-05-05 Cont ID  
Sent By jwitmer Date 2017-05-05 Time 10:37 Rev Time 0.00
Received By jwitmer Date 2017-05-05 Time 10:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-08-28 Cont ID  
Sent By skennedy Date 2017-08-28 Time 16:17 Rev Time 0.00
Received By skennedy Date 2017-08-28 Time 16:17 Sent To  
Notes
2017-08-28 16:17:25ROUTE TO ME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-06-13 Cont ID  
Sent By gjohnson Date 2017-06-13 Time 15:25 Rev Time 0.00
Received By gjohnson Date 2017-06-13 Time 12:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-08 Cont ID  
Sent By gjohnson Date 2017-05-08 Time 09:31 Rev Time 0.00
Received By gjohnson Date 2017-05-08 Time 08:09 Sent To  
Notes
2017-05-08 09:33:131ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE COMPLY WITH BUILDING AND FIRES COMMENTS. PER
 WPB AMEND TO FBC 107.2.1
  
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  