Plan Review Details - Permit 17041031
Plan Review Stops For Permit 17041031
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-04-27 Cont ID  
Sent By rlecky Date 2017-04-27 Time 12:11 Rev Time 0.00
Received By rlecky Date 2017-04-27 Time 11:26 Sent To  
Notes
2017-04-27 12:15:33PROVISO:
 MINIMUM # 8 ALUMINUM GROUND IS REQUIRED FOR A 50 AMP
 BRANCH CIRCUIT. THIS REQUIREMENT WAS NOTED ON THE
 REVISED PLAN. NEC T. 250.122

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2017-05-15 Time 10:21 Sent To  
Notes
2017-05-17 10:21:51RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-27 Cont ID  
Sent By ccole Date 2017-04-27 Time 15:09 Rev Time 0.00
Received By ccole Date 2017-04-24 Time 11:01 Sent To  
Notes
2017-04-27 11:01:42ROUTED TO RLECKY

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-05-17 Cont ID  
Sent By ccole Date 2017-05-17 Time 11:45 Rev Time 0.00
Received By ccole Date 2017-05-17 Time 11:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-27 Cont ID  
Sent By ccole Date 2017-04-27 Time 15:09 Rev Time 0.00
Received By ccole Date 2017-04-27 Time 15:09 Sent To  
Notes
2017-04-27 15:16:471ST REVIEW FBC-2014 MECHANICAL
 REVISION #17041031
 MASTER #14120431
 4/27/17
  
 1) SHEET M-4.03: THE PLAN INDICATES THE TRASH ROOM
 EXHAUST FAN HAS BEEN RELOCATED APPARENTLY TO THE ROOF.
 PLEASE REVISE THE PLANS TO SHOW THE LOCATION OF THE FAN
 AND WHATEVER CHANGES HAVE BEEN MADE TO THE FAN
 EQUIPMENT SCHEDULE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  