Plan Review Details - Permit 17041008
Plan Review Stops For Permit 17041008
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-04 Cont ID  
Sent By rmcdouga Date 2017-05-04 Time 07:09 Rev Time 0.00
Received By rmcdouga Date 2017-05-04 Time 06:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-24 Cont ID  
Sent By rmcdouga Date 2017-04-24 Time 18:30 Rev Time 0.00
Received By rmcdouga Date 2017-04-24 Time 17:38 Sent To  
Notes
2017-04-24 18:30:08PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ONE STORY STRUCTURE HAS A 6:12 SLOPED ROOF AND
 IS LOCATED IN EXPOSURE CATEGORY C WITH A 170 MPH VULT
 WINDSPEED. THE PRODUCT APPROVAL FOR THE TRI-BUILT SELF
 ADHERED UNDERLAYMENT SPECIFIES THE MAXIMUM DESIGN
 PRESSURE OF -60.0 PSF FOR A MIN. 19/32 " PLYWOOD DECK.
 THIS IS NOT ADEQUATE FOR THE CORNER AREAS OF THE ROOF.
 FBC-R 301.2.1
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-04 Cont ID  
Sent By rmcdouga Date 2017-05-04 Time 07:09 Rev Time 0.00
Received By rmcdouga Date 2017-04-26 Time 14:47 Sent To  
Notes
2017-04-27 14:47:56RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-24 Cont ID  
Sent By rmcdouga Date 2017-04-24 Time 18:30 Rev Time 0.00
Received By rmcdouga Date 2017-04-24 Time 13:34 Sent To  
Notes
2017-04-24 13:34:47RMCDOUGAL