2017-05-03 08:46:19 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 17040955 |
| W.P.B. PERMIT: 15081109- MASTER BUILD-OUT |
| W. P. B. PERMIT: 15081111-FOUNDATION |
| ADD: 444 BUNKER RANCH RD. |
| CONT: CURY BUILDING & DESIGN |
| TEL: (561)718-1398 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. 03/ 2017 |
| ACTION: DENIED |
| |
| 1) THE SUBMITTED PLANS IN THE PLOT DATE SHOW NEW |
| REVISIONS BY DELTA 10, 11 & 14 THE PLANS ARE NOT |
| BUBBLED SHOW THESE LOCATIONS ON THE PLANS NOR IS THERE |
| A NARRATIVE SUBMITTED EXPLAINING THE CHANGES. |
| 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN |
| DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 2) SHEETS L1 & L2 BOTH SHOW 1 HOUR FIRE RATED |
| STAIRWELLS. THE ORIGINAL PERMITTED SET OF PLANS ON |
| SHEET M2 SHOWS INDEPENDENT SYSTEMS #16 & 17. THE |
| REVISED DRAWINGS NOW SHOW A SHARED SYSTEM WITH THE |
| REMAINDER OF THE FLOOR WITH RADIANT DAMPERS. PLEASE |
| SHOW COMPLIANCE WITH SECTION 1022.5 OF THE 2014 FBC-B. |
| 2014 FBC-B 1022.5 PENETRATIONS. PENETRATIONS INTO AND |
| OPENINGS THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE |
| PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT |
| AND DUCTWORK NECESSARY FOR INDEPENDENT VENTILATION OR |
| PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, |
| ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION |
| SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR |
| EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX |
| NOT EXCEEDING 16 SQUARE INCHES. SUCH PENETRATIONS SHALL |
| BE PROTECTED IN ACCORDANCE WITH SECTION 714. THERE |
| SHALL BE NO PENETRATIONS OR COMMUNICATING OPENINGS, |
| WHETHER PROTECTED OR NOT, BETWEEN ADJACENT INTERIOR |
| EXIT STAIRWAYS AND RAMPS. |
| |
| 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |