Plan Review Details - Permit 17040955
Plan Review Stops For Permit 17040955
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-26 Cont ID  
Sent By jwitmer Date 2017-05-26 Time 07:56 Rev Time 0.00
Received By jwitmer Date 2017-05-26 Time 07:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-03 Cont ID  
Sent By jwitmer Date 2017-05-03 Time 08:46 Rev Time  
Received By jwitmer Date 2017-05-03 Time 07:45 Sent To  
Notes
2017-05-03 08:46:19BUILDING PLAN REVIEW
 W. P. B. REVISION: 17040955
 W.P.B. PERMIT: 15081109- MASTER BUILD-OUT
 W. P. B. PERMIT: 15081111-FOUNDATION
 ADD: 444 BUNKER RANCH RD.
 CONT: CURY BUILDING & DESIGN
 TEL: (561)718-1398
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. 03/ 2017
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS IN THE PLOT DATE SHOW NEW
 REVISIONS BY DELTA 10, 11 & 14 THE PLANS ARE NOT
 BUBBLED SHOW THESE LOCATIONS ON THE PLANS NOR IS THERE
 A NARRATIVE SUBMITTED EXPLAINING THE CHANGES.
 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 2) SHEETS L1 & L2 BOTH SHOW 1 HOUR FIRE RATED
 STAIRWELLS. THE ORIGINAL PERMITTED SET OF PLANS ON
 SHEET M2 SHOWS INDEPENDENT SYSTEMS #16 & 17. THE
 REVISED DRAWINGS NOW SHOW A SHARED SYSTEM WITH THE
 REMAINDER OF THE FLOOR WITH RADIANT DAMPERS. PLEASE
 SHOW COMPLIANCE WITH SECTION 1022.5 OF THE 2014 FBC-B.
 2014 FBC-B 1022.5 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE
 PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR
 EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQUARE INCHES. SUCH PENETRATIONS SHALL
 BE PROTECTED IN ACCORDANCE WITH SECTION 714. THERE
 SHALL BE NO PENETRATIONS OR COMMUNICATING OPENINGS,
 WHETHER PROTECTED OR NOT, BETWEEN ADJACENT INTERIOR
 EXIT STAIRWAYS AND RAMPS.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-05-31 Cont ID  
Sent By jleahy Date 2017-05-31 Time 10:40 Rev Time 0.00
Received By jleahy Date 2017-05-31 Time 10:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2017-04-25 Cont ID  
Sent By vperez Date 2017-04-25 Time 08:50 Rev Time 0.00
Received By vperez Date 2017-04-25 Time 08:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-05-31 Cont ID  
Sent By pleduc Date 2017-05-31 Time   Rev Time 0.00
Received By pleduc Date 2017-05-30 Time 14:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-04-28 Cont ID  
Sent By pleduc Date 2017-04-28 Time   Rev Time 0.00
Received By pleduc Date 2017-04-28 Time 09:19 Sent To  
Notes
2017-04-28 13:28:18THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET M2 - A/C DUCT PENETRATION ARE INDICATED IN THE
 STAIRWELLS.
  
 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS.
 7.2.2.5.1 ENCLOSURES.
 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR
 EXIT COMPONENT SHALL BE ENCLOSED IN ACCORDANCE WITH
 7.1.3.2.
  
 7.1.3.2 EXITS.
 7.1.3.2.1 WHERE THIS CODE REQUIRES AN EXIT TO BE
 SEPARATED FROM OTHER PARTS OF THE BUILDING, THE
 SEPARATING CONSTRUCTION SHALL MEET THE REQUIREMENTS OF
 SECTION 8.2 AND THE FOLLOWING:
 (1)* THE SEPARATION SHALL HAVE A MINIMUM 1-HOUR FIRE
 RESISTANCE RATING WHERE THE EXIT CONNECTS THREE OR
 FEWER STORIES.
 (2) THE SEPARATION SPECIFIED IN 7.1.3.2.1(1), OTHER
 THAN AN EXISTING SEPARATION, SHALL BE SUPPORTED BY
 CONSTRUCTION HAVING NOT LESS THAN A 1-HOUR FIRE
 RESISTANCE RATING.
  
 (9)* OPENINGS IN EXIT ENCLOSURES SHALL BE LIMITED TO
 DOOR ASSEMBLIES FROM NORMALLY OCCUPIED SPACES AND
 CORRIDORS AND DOOR ASSEMBLIES FOR EGRESS FROM THE
 ENCLOSURE, UNLESS ONE OF THE FOLLOWING CONDITIONS
 EXISTS:
 (A) OPENINGS IN EXIT PASSAGEWAYS IN MALL BUILDINGS AS
 PROVIDED IN CHAPTERS 36 AND 37 SHALL BE PERMITTED.
 (B) IN BUILDINGS OF TYPE I OR TYPE II CONSTRUCTION, AS
 DEFINED IN NFPA 220, STANDARD ON TYPES OF BUILDING
 CONSTRUCTION (SEE 8.2.1.2), EXISTING FIRE PROTECTION
 ?RATED DOOR ASSEMBLIES TO INTERSTITIAL SPACES SHALL BE
 PERMITTED, PROVIDED THAT SUCH SPACES MEET ALL OF THE
 FOLLOWING CRITERIA:
 I. THE SPACE IS USED SOLELY FOR DISTRIBUTION OF PIPES,
 DUCTS, AND CONDUITS.
 II. THE SPACE CONTAINS NO STORAGE.
 III. THE SPACE IS SEPARATED FROM THE EXIT ENCLOSURE IN
 ACCORDANCE WITH SECTION 8.3.
  
 (10) PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT
 ENCLOSURE ASSEMBLY SHALL BE LIMITED TO THE FOLLOWING:
 (A) DOOR ASSEMBLIES PERMITTED BY 7.1.3.2.1(9)
 (B)* ELECTRICAL CONDUIT SERVING THE EXIT ENCLOSURE
 (C) REQUIRED EXIT DOOR OPENINGS
 (D) DUCTWORK AND EQUIPMENT NECESSARY FOR INDEPENDENT
 STAIR PRESSURIZATION
 (E) WATER OR STEAM PIPING NECESSARY FOR THE HEATING OR
 COOLING OF THE EXIT ENCLOSURE
 (F) SPRINKLER PIPING
 (G) STANDPIPES
 (H) EXISTING PENETRATIONS PROTECTED IN ACCORDANCE WITH
 8.3.5
 (I) PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE
 CIRCUITS ARE INSTALLED IN METAL CONDUIT AND THE
 PENETRATIONS ARE PROTECTED IN ACCORDANCE WITH 8.3.5
  
  
 PLEASE PROVIDE FOR THE COMPLIANCE OF THE REQUIRERMENTS
 TO PROTECT THE EXIT STAIRWELLS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-31 Cont ID  
Sent By jleahy Date 2017-05-31 Time 10:41 Rev Time 0.00
Received By jleahy Date 2017-05-22 Time 10:20 Sent To  
Notes
2017-05-23 10:20:19C18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-03 Cont ID  
Sent By skennedy Date 2017-05-03 Time 13:13 Rev Time 0.00
Received By skennedy Date 2017-04-21 Time 12:51 Sent To  
Notes
2017-04-24 12:51:46C09

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-05-26 Cont ID  
Sent By ccole Date 2017-05-26 Time 15:24 Rev Time 0.00
Received By ccole Date 2017-05-26 Time 15:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-25 Cont ID  
Sent By ccole Date 2017-04-25 Time 15:57 Rev Time 0.00
Received By ccole Date 2017-04-25 Time 15:57 Sent To  
Notes
2017-04-25 16:09:311ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040955
 4/25/17
  
 1) THE REVISED PLAN SHOWS DUCTWORK FROM AHU'S #9 & 11
 PENETRATING INTO THE INTERIOR EXIT STAIRWAYS WHICH IS
 PROHIBITED PER SECTION 1022.6 FBC-14 BUILDING. THE
 ORIGINAL PLAN SHOWED INDEPENDENT SYSTEMS #16 & 17
 OPERATING IN THE STAIRWAYS WHICH HAVE NOW BEEN
 ELIMINATED- PLEASE CORRECT.
  
 2) THE REVISED PLAN SHOWS A NEW SPLIT SYSTEM WHICH IS
 ALSO LABELED #18 LIKE THE EXISTING HEAT PUMP AHU.
 PLEASE SHOW THE LOCATION OF THE NEW SYSTEM AND PROVIDE
 AC COOLING AND HEATING CALCULATIONS IN COMPLIANCE WITH
 SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 3) REVISE THE ENERGY CALCULATIONS TO INCORPORATE THE
 CHANGES TO THE APPROVED AC SYSTEMS.
  
 4) PROVIDE A NARRATIVE FRROM THE DESIGN PROFESSIONAL
 ITEMIZING ALL CHANGES TO THE APPROVED MECHANICAL PLANS,
 AND ALL CORRECTIONS MADE TO THE NEW REVISED PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-24 Cont ID  
Sent By gjohnson Date 2017-05-24 Time 12:19 Rev Time 0.00
Received By gjohnson Date 2017-05-24 Time 11:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-04-27 Cont ID  
Sent By gjohnson Date 2017-04-27 Time 16:01 Rev Time 0.00
Received By gjohnson Date 2017-04-27 Time 15:27 Sent To  
Notes
2017-04-27 16:05:361ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE A NARRATIVE DETAILING THE PLUMBING
 REVISIONS AND INDICATE AND LABEL ON THE PLAN ALL NEW
 REVISIONS. PER WPB AMEND TO FBC 107.2.1
  
 2. PER INSPECTORS NOTE: PRIOR TO FINAL.
 SIGNED AND SEALED LETTER FROM ENGINEER OF
 RECORD REQD. FOR 3" LINE THROUGH
 FOUNDATION WALL AND 3" LINE THROUGH
 POURED COLUMN ON FIRST FLOOR.
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  