Plan Review Details - Permit 17040865
Plan Review Stops For Permit 17040865
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-07-24 Cont ID  
Sent By jwitmer Date 2017-07-14 Time 06:42 Rev Time 0.00
Received By jwitmer Date 2017-07-14 Time 06:17 Sent To  
Notes
2017-07-24 15:42:367/24/2017 RAMP SUBMITTED UNDER PERMIT 17070240 PASSED
 BY C. TROOP MAKING A ACCESSIBLE FRONT ENTRY AND SAME
 PATH TO THE RECEPTIONIST. JW.
2017-07-14 06:44:132014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17040865
 ADD: 101 N. CLEMATIS ST. SUITE: 110
 CONT: TBD TO BE DETERMINED
 TEL: [email protected]
 E-MAIL: 954-914-9848
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JULY 14/ 2017
 ACTION: DENIED.
  
 1E) REQUESTED AS A DEFERRED SUBMITTAL. SHEET A-110.00
 SHOWS A PROPOSED NEW ACCESSIBLE RAMP LOCATION THAT WILL
 SATISFY BOTH COMMENTS 1E & COMMENT 2. THIS RAMP
 LOCATION WILL ALSO NEED ZONING APPROVAL. THE DESIGNER
 OF RECORD HAS NOT MET THE ZONING REQUIREMENT THAT THE
 RAMP HAS NOT MET THE MINIMUM 16 FOOT SETBACK AS
 MEASURED FROM THE BACK OF THE EXISTING CURB ALONG
 CLEMATIS ST.
  
 1F) PLEASE NOTE THE PROPOSED RAMP DESIGN WILL NEED TO
 SHOW COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE
 405.7.4 CHANGE IN DIRECTION.
 405.7.4 CHANGE IN DIRECTION. RAMPS THAT CHANGE
 DIRECTION BETWEEN RUNS AT LANDINGS SHALL HAVE A CLEAR
 LANDING 60 INCHES (1525 MM) MINIMUM BY 60 INCHES (1525
 MM) MINIMUM.
  
 1ST ROUND OF COMMENTS. EGRESS REQUIREMENTS INDICATE (2)
 ARE REQUIRED AND 4 ARE PROVIDED. IN THE SCOPING
 REQUIREMENTS CHAPTER 2 OF THE ACCESS. CODE SECTION
 206.4.1. PUBLIC ENTRANCES. IN ADDITION TO ENTRANCES
 REQUIRED BY 206.4.2 THROUGH 206.4.9, AT LEAST 60
 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY WITH 404.
 BARRIERS AT COMMON OR EMERGENCY ENTRANCES AND EXITS OF
 BUSINESS ESTABLISHMENTS CONDUCTING BUSINESS WITH THE
 GENERAL PUBLIC THAT ARE EXISTING, UNDER CONSTRUCTION,
 OR UNDER CONTRACT FOR CONSTRUCTION WHICH WOULD PREVENT
 A PERSON FROM USING SUCH ENTRANCES OR EXITS SHALL BE
 REMOVED. PLEASE NOTE IN SPEAKING WITH THE BUILDING
 OFFICIAL WE ARE CONSIDERING THE FRONT ENTRY DOORS AS
 ONE ENTRANCE, 3 X 0.6 = 1.8 OR (2) ACCESSIBLE MEANS OF
 EGRESS ARE REQUIRED, PLEASE SHOW ON THE PLANS .
  
 2) NOT SATISFIED UNTIL COMMENT (1E) IS SATISFIED. SHEET
 A-110.00 PLEASE REVIEW THE LAYOUT OF THE FRONT ENTRY,
 RECEPTION AND WAITING AREAS AND SHOW HOW COMPLIANCE
 WITH SECTION 206.3 OF THE ACCESS. CODE IS TO BE
 COMPLIED WITH. 206.3 LOCATION.
 ACCESSIBLE ROUTES SHALL COINCIDE WITH OR BE LOCATED IN
 THE SAME AREA AS GENERAL CIRCULATION PATHS. WHERE
 CIRCULATION PATHS ARE INTERIOR, REQUIRED ACCESSIBLE
 ROUTES SHALL ALSO BE INTERIOR.
 ADVISORY 206.3 LOCATION. THE ACCESSIBLE ROUTE MUST BE
 IN THE SAME AREA AS THE GENERAL CIRCULATION PATH. THIS
 MEANS THAT CIRCULATION PATHS, SUCH AS VEHICULAR WAYS
 DESIGNED FOR PEDESTRIAN TRAFFIC, WALKS, AND UNPAVED
 PATHS THAT ARE DESIGNED TO BE ROUTINELY USED BY
 PEDESTRIANS MUST BE ACCESSIBLE OR HAVE AN ACCESSIBLE
 ROUTE NEARBY. ADDITIONALLY, ACCESSIBLE VERTICAL
 INTERIOR CIRCULATION MUST BE IN THE SAME AREA AS STAIRS
 AND ESCALATORS, NOT ISOLATED IN THE BACK OF THE
 FACILITY.
  
 3) COMPLIED.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-23 Cont ID  
Sent By jwitmer Date 2017-06-23 Time 08:38 Rev Time 0.00
Received By jwitmer Date 2017-06-23 Time 06:58 Sent To  
Notes
2017-06-23 08:38:062014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17040865
 ADD: 101 N. CLEMATIS ST. SUITE: 110
 CONT: TBD TO BE DETERMINED
 TEL: [email protected]
 E-MAIL: 954-914-9848
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JUNE 23/ 2017
 ACTION: BUILDING PROVISO/ PLANS TO BE STAMPED AFTER
 ZONING APPROVAL.
  
 1) BUILDING PROVISO: COMMENT 1E) REQUESTED AS A
 DEFERRED SUBMITTAL. SHEET A-110.00 SHOWS A PROPOSED NEW
 ACCESSIBLE RAMP LOCATION THAT WILL SATISFY BOTH
 COMMENTS 1E & COMMENT 2. THIS RAMP LOCATION WILL ALSO
 NEED ZONING APPROVAL. PLEASE NOTE THE PROPOSED RAMP
 DESIGN WILL NEED TO SHOW COMPLIANCE WITH 2014
 FBC-ACCESSIBILITY CODE 405.7.4 CHANGE IN DIRECTION.
 405.7.4 CHANGE IN DIRECTION. RAMPS THAT CHANGE
 DIRECTION BETWEEN RUNS AT LANDINGS SHALL HAVE A CLEAR
 LANDING 60 INCHES (1525 MM) MINIMUM BY 60 INCHES (1525
 MM) MINIMUM.
  
 1ST ROUND OF COMMENTS. EGRESS REQUIREMENTS INDICATE (2)
 ARE REQUIRED AND 4 ARE PROVIDED. IN THE SCOPING
 REQUIREMENTS CHAPTER 2 OF THE ACCESS. CODE SECTION
 206.4.1. PUBLIC ENTRANCES. IN ADDITION TO ENTRANCES
 REQUIRED BY 206.4.2 THROUGH 206.4.9, AT LEAST 60
 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY WITH 404.
 BARRIERS AT COMMON OR EMERGENCY ENTRANCES AND EXITS OF
 BUSINESS ESTABLISHMENTS CONDUCTING BUSINESS WITH THE
 GENERAL PUBLIC THAT ARE EXISTING, UNDER CONSTRUCTION,
 OR UNDER CONTRACT FOR CONSTRUCTION WHICH WOULD PREVENT
 A PERSON FROM USING SUCH ENTRANCES OR EXITS SHALL BE
 REMOVED. PLEASE NOTE IN SPEAKING WITH THE BUILDING
 OFFICIAL WE ARE CONSIDERING THE FRONT ENTRY DOORS AS
 ONE ENTRANCE, 3 X 0.6 = 1.8 OR (2) ACCESSIBLE MEANS OF
 EGRESS ARE REQUIRED, PLEASE SHOW ON THE PLANS .
  
 2) BUILDING PROVISO: NOT SATISFIED UNTIL COMMENT (1E)
 IS SATISFIED. SHEET A-110.00 PLEASE REVIEW THE LAYOUT
 OF THE FRONT ENTRY, RECEPTION AND WAITING AREAS AND
 SHOW HOW COMPLIANCE WITH SECTION 206.3 OF THE ACCESS.
 CODE IS TO BE COMPLIED WITH. 206.3 LOCATION.
 ACCESSIBLE ROUTES SHALL COINCIDE WITH OR BE LOCATED IN
 THE SAME AREA AS GENERAL CIRCULATION PATHS. WHERE
 CIRCULATION PATHS ARE INTERIOR, REQUIRED ACCESSIBLE
 ROUTES SHALL ALSO BE INTERIOR.
 ADVISORY 206.3 LOCATION. THE ACCESSIBLE ROUTE MUST BE
 IN THE SAME AREA AS THE GENERAL CIRCULATION PATH. THIS
 MEANS THAT CIRCULATION PATHS, SUCH AS VEHICULAR WAYS
 DESIGNED FOR PEDESTRIAN TRAFFIC, WALKS, AND UNPAVED
 PATHS THAT ARE DESIGNED TO BE ROUTINELY USED BY
 PEDESTRIANS MUST BE ACCESSIBLE OR HAVE AN ACCESSIBLE
 ROUTE NEARBY. ADDITIONALLY, ACCESSIBLE VERTICAL
 INTERIOR CIRCULATION MUST BE IN THE SAME AREA AS STAIRS
 AND ESCALATORS, NOT ISOLATED IN THE BACK OF THE
 FACILITY.
  
 3) COMPLIED.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-15 Cont ID  
Sent By jwitmer Date 2017-05-15 Time 14:00 Rev Time 0.00
Received By jwitmer Date 2017-05-15 Time 10:00 Sent To  
Notes
2017-05-15 14:00:532014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17040865
 ADD: 101 N. CLEMATIS ST. SUITE: 110
 CONT: TBD TO BE DETERMINED
 TEL: [email protected]
 E-MAIL: 954-914-9848
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MAY 15/ 2017
 ACTION: DENIED
  
 1) THE SHEET G-0400.00 CODE SUMMARY SHEET:
 1A) UNDER THE HEADING APPLICABLE CODES, MISSING THE 5TH
 EDITION OF THE FLORIDA EXISTING BUILDING CODE.
  
 1B) THE DESIGNER OF RECORD HAS NOT INDICATED UNDER THE
 2014 EXISTING BUILDING CODE WHICH COMPLIANCE METHOD WAS
 USED IN DEVELOPING THE PLANS. EXISTING BLDG. CODE THE
 CHANGE OF OCCUPANCY OF ALL EXISTING BUILDINGS SHALL
 COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS
 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT.
 FOR THIS REVIEW THE BUILDING PLAN REVIEWER WILL USE THE
 WORK AREA METHOD SINCE 99 % OF ALL DESIGNERS USE THIS
 DESIGN METHOD FOR ALTERATIONS, CHANGE OF OCCUPANCY,
 ADDITION OR RELOCATION OF EXISTING BUILDINGS. CHANGE OF
 OCCUPANCY, 2014 FBC-EXISTING BUILDING CODE CHAPTER 10.
 1001.3.1 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 1012 SHALL APPLY.
  
 1C) UNDER THE HEADING OF OCCUPANCY TYPE: THE PLANS
 INDICATE BUSINESS. PLEASE PROVIDE A MORE DESCRIPTIVE
 USE OF THIS SPACE TO DETERMINE IF THIS TENANT IS TO BE
 CLASSIFIED AS A GENERAL DOCTORS OFFICE, OR SPECIALIZING
 IN THE TREATMENT OF CONDITIONS THAT AFFECT MOBILITY OR
 ONE OF THE SPECIALTY OCCUPANCIES FOUND UNDER CHAPTER 4
 OF THE FBC-B.
  
 1D) UNDER THE HEADING CONSTRUCTION TYPE THE PLANS STATE
 CONFIRM AND CODE SECTION, THIS SECTION IS NOT FOUND IN
 EITHER THE 2014 FBC-B NOR EXISTING BUILDING CODE. THE
 OTHER ISSUE WITH TRYING TO IDENTIFY A BUILDING
 CONSTRUCTION TYPE WE CAN GO TO FBC-B TABLE 601 FIRE
 RESISTANCE RATINGS BUT THE RATINGS DO NOT MATCH ANY OF
 THE BUILDING TYPES. THE CLOSEST IS A BUILDING TYPE
 CONSTRUCTION IA BUT MORE RESTRICTIVE WITH 3 HOUR FIRE
 RATING ON THE EXTERIOR BEARING WALLS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 1E) EGRESS REQUIREMENTS INDICATE (2) ARE REQUIRED AND 4
 ARE PROVIDED. IN THE SCOPING REQUIREMENTS CHAPTER 2 OF
 THE ACCESS. CODE SECTION 206.4.1. PUBLIC ENTRANCES. IN
 ADDITION TO ENTRANCES REQUIRED BY 206.4.2 THROUGH
 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES
 SHALL COMPLY WITH 404. BARRIERS AT COMMON OR EMERGENCY
 ENTRANCES AND EXITS OF BUSINESS ESTABLISHMENTS
 CONDUCTING BUSINESS WITH THE GENERAL PUBLIC THAT ARE
 EXISTING, UNDER CONSTRUCTION, OR UNDER CONTRACT FOR
 CONSTRUCTION WHICH WOULD PREVENT A PERSON FROM USING
 SUCH ENTRANCES OR EXITS SHALL BE REMOVED. PLEASE NOTE
 IN SPEAKING WITH THE BUILDING OFFICIAL WE ARE
 CONSIDERING THE FRONT ENTRY DOORS AS ONE ENTRANCE, 3 X
 0.6 = 1.8 OR (2) ACCESSIBLE MEANS OF EGRESS ARE
 REQUIRED, PLEASE SHOW ON THE PLANS .
 2) SHEET A-110.00 PLEASE REVIEW THE LAYOUT OF THE FRONT
 ENTRY, RECEPTION AND WAITING AREAS AND SHOW HOW
 COMPLIANCE WITH SECTION 206.3 OF THE ACCESS. CODE IS TO
 BE COMPLIED WITH. 206.3 LOCATION.
 ACCESSIBLE ROUTES SHALL COINCIDE WITH OR BE LOCATED IN
 THE SAME AREA AS GENERAL CIRCULATION PATHS. WHERE
 CIRCULATION PATHS ARE INTERIOR, REQUIRED ACCESSIBLE
 ROUTES SHALL ALSO BE INTERIOR.
  
 ADVISORY 206.3 LOCATION. THE ACCESSIBLE ROUTE MUST BE
 IN THE SAME AREA AS THE GENERAL CIRCULATION PATH. THIS
 MEANS THAT CIRCULATION PATHS, SUCH AS VEHICULAR WAYS
 DESIGNED FOR PEDESTRIAN TRAFFIC, WALKS, AND UNPAVED
 PATHS THAT ARE DESIGNED TO BE ROUTINELY USED BY
 PEDESTRIANS MUST BE ACCESSIBLE OR HAVE AN ACCESSIBLE
 ROUTE NEARBY. ADDITIONALLY, ACCESSIBLE VERTICAL
 INTERIOR CIRCULATION MUST BE IN THE SAME AREA AS STAIRS
 AND ESCALATORS, NOT ISOLATED IN THE BACK OF THE
 FACILITY.
  
 3) DISCREPANCY IN PLANS SHEET S-301 DETAIL # 5
 INDICATING THE NEW ROOF TOP A/C UNIT TO SIT ON A NEW
 W4X13 BEAM PER THE MANUFACTURERS REQUIREMENT. THE PLANS
 SHOW THE NEW BEAM TO BE WELDED TO AN EXISTING BEAM. THE
 M1.2 NOTE # 1 INDICATES THE NEW ROOF TOP UNIT IS TO SIT
 ON TOP OF A NOA APPROVED ROOF RACK TO BE DESIGNED BY
 THE STRUCTURAL ENGINEER? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-07-21 Cont ID  
Sent By jpearson Date 2017-07-21 Time 07:29 Rev Time 0.00
Received By jpearson Date 2017-07-21 Time 07:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-23 Cont ID  
Sent By jleahy Date 2017-06-23 Time 14:05 Rev Time 0.00
Received By jleahy Date 2017-06-23 Time 14:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-05-23 Cont ID  
Sent By jleahy Date 2017-05-23 Time 10:38 Rev Time 0.00
Received By jleahy Date 2017-05-23 Time 10:37 Sent To  
Notes
2017-05-23 11:06:46JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1ST REVIEW: FBC 2014
  
 PAGE E0.1, E1.1, E1.2
  
 NEED A REFERENCE TO NEC CODE SECTION 517.13(B)(C) FOR
 INSULATED EQUIPMENT GROUNDING IN PATIENT CARE AREAS
 FOR ALL WIRING IN THESE AREASUP TO7-1/2' FROM THE
 FLOOR.
  
 PAGE E0.2 RISER DIAGRAM
  
 PROVIDE THE FAULT CURRENT CALCULATION FOR ALL NEW
 PANELS "H", "LA", "LB", AND "IDF" PER 110.24 (A)(B)

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-07-12 Cont ID  
Sent By pleduc Date 2017-07-12 Time   Rev Time 0.00
Received By pleduc Date 2017-07-11 Time 15:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-16 Cont ID  
Sent By pleduc Date 2017-06-16 Time   Rev Time 0.00
Received By pleduc Date 2017-06-16 Time 09:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-04-27 Cont ID  
Sent By pleduc Date 2017-04-27 Time   Rev Time 0.00
Received By pleduc Date 2017-04-27 Time 09:46 Sent To  
Notes
2017-04-27 11:21:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET G 010.00 - THE SUITE # (110) IS NOT INDICATED
 IN THE TITLE BLOCK.
  
 THE PROPER ADDRESS IS REQUIRED IN THE TITLE BLOCK.
 PLEASE CORRECT.
  
  
  
 2) SHEET G 030.00 - THE OCCUPANCY IS INDICATED AS
 BUSINESS; HOWEVER, THERE IS NO SCOPE PROVIDED FOR THE
 SERVICES PROVIDED.
  
 3.3.188.1* AMBULATORY HEALTH CARE OCCUPANCY. AN
 OCCUPANCY USED TO PROVIDE SERVICES OR TREATMENT
 SIMULTANEOUSLY TO FOUR OR MORE PATIENTS THAT PROVIDES,
 ON AN OUTPATIENT BASIS, ONE OR MORE OF THE FOLLOWING:
 (1) TREATMENT FOR PATIENTS THAT RENDERS THE PATIENTS
 INCAPABLE OF TAKING ACTION FOR SELFPRESERVATION UNDER
 EMERGENCY CONDITIONS WITHOUT THE ASSISTANCE OF OTHERS;
 (2) ANESTHESIA THAT RENDERS THE PATIENTS INCAPABLE OF
 TAKING ACTION FOR SELF-PRESERVATION UNDER EMERGENCY
 CONDITIONS WITHOUT THE ASSISTANCE OF OTHERS; (3)
 EMERGENCY OR URGENT CARE FOR PATIENTS WHO, DUE TO THE
 NATURE OF THEIR INJURY OR ILLNESS, ARE INCAPABLE OF
 TAKING ACTION FOR SELF-PRESERVATION UNDER EMERGENCY
 CONDITIONS WITHOUT THE ASSISTANCE OF OTHERS.
  
 6.1.6 AMBULATORY HEALTH CARE. FOR REQUIREMENTS, SEE
 CHAPTERS 20 AND 21.
 6.1.6.1* DEFINITION ? AMBULATORY HEALTH CARE OCCUPANCY.
 AN OCCUPANCY USED TO PROVIDE SERVICES OR TREATMENT
 SIMULTANEOUSLY TO FOUR OR MORE PATIENTS THAT PROVIDES,
 ON AN OUTPATIENT BASIS, ONE OR MORE OF THE FOLLOWING:
 (1) TREATMENT FOR PATIENTS THAT RENDERS THE PATIENTS
 INCAPABLE OF TAKING ACTION FOR SELF-PRESERVATION UNDER
 EMERGENCY CONDITIONS WITHOUT THE ASSISTANCE OF OTHERS
 (2) ANESTHESIA THAT RENDERS THE PATIENTS INCAPABLE OF
 TAKING ACTION FOR SELF-PRESERVATION UNDER EMERGENCY
 CONDITIONS WITHOUT THE ASSISTANCE OF OTHERS
 (3) EMERGENCY OR URGENT CARE FOR PATIENTS WHO, DUE TO
 THE NATURE OF THEIR INJURY OR ILLNESS, ARE INCAPABLE OF
 TAKING ACTION FOR SELF-PRESERVATION UNDER EMERGENCY
 CONDITIONS WITHOUT THE ASSISTANCE OF OTHERS
  
 A.6.1.6.1 AMBULATORY HEALTH CARE OCCUPANCY. IT IS NOT
 THE INTENT THAT OCCUPANTS BE CONSIDERED TO BE INCAPABLE
 OF SELFPRESERVATION JUST BECAUSE THEY ARE IN A
 WHEELCHAIR OR USE ASSISTIVEWALKING DEVICES, SUCH AS A
 CANE, A WALKER, OR CRUTCHES.
 RATHER, IT IS THE INTENT TO ADDRESS EMERGENCY CARE
 CENTERS THAT RECEIVE PATIENTS WHO HAVE BEEN RENDERED
 INCAPABLE OF SELFPRESERVATION DUE TO THE EMERGENCY,
 SUCH AS BEING RENDERED UNCONSCIOUS AS A RESULT OF AN
 ACCIDENT OR BEING UNABLE TO MOVE DUE TO SUDDEN ILLNESS.
  
 6.1.11.1* DEFINITION ? BUSINESS OCCUPANCY. AN OCCUPANCY
 USED FOR THE TRANSACTION OF BUSINESS OTHER THAN
 MERCANTILE.
 A.6.1.11.1 BUSINESS OCCUPANCY. BUSINESS OCCUPANCIES
 INCLUDE THE FOLLOWING:
 (1) AIR TRAFFIC CONTROL TOWERS (ATCTS)
 (2) CITY HALLS
 (3) COLLEGE AND UNIVERSITY INSTRUCTIONAL BUILDINGS,
 CLASSROOMS UNDER 50 PERSONS, AND INSTRUCTIONAL
 LABORATORIES
 (4) COURTHOUSES
 (5) DENTISTS? OFFICES
 (6) DOCTORS? OFFICES
 (7) GENERAL OFFICES
 (8) OUTPATIENT CLINICS (AMBULATORY)
 (9) TOWN HALLS
  
 PLEASE PROVIDE A DETAILED DESCRIPTION OF THE SERVICES
 PROVIDED TO ENSURE APPLICABLE OCCUPANCY CLASSIFICATION.
  
  
  
  
 3) SHEET A 110.00 & A 610.00 - THE IT ROOM DOOR, A-11
 IS INDICATED AS BEING RATED, HOWEVER, THE WALLS OF THE
 IT ROOM ARE NOT. THIS IS CONFUSING.
  
 PLEASE REVIEW, CORRECT OR CLARIFY.
  
  
  
 4) SHEET M 1.1 - IF THE IT ROOM DOOR AND WALLS ARE
 PROPOSED TO BE RATED, THE A/C VENT DUCT IS REQUIRED TO
 BE PROVIDED WITH A FIRE OR SMOKE DAMPER ?
  
 PLEASE REVIEW, CORRECT OR CLARIFY.
  
  
  
 5) SHEET A 610.00 - THE DOOR SCHEDULE INDICATES NUMERIC
 HARDWARE SETS. A HARDWARE SET TABLE COULD NOT BE
 READIDLY LOCATED.
  
 PLEASE PROVIDE THE APPLICABLE TABLE AND ENSURE
 COMPLIANCE WITH NFPA 101, CHAPTER 7, MEANS OF EGRESS
 AND/OR THE APPLICABLE OCCUPANCY CHAPTER FOR ALL OTHER
 DOORS.
  
  
  
 6) SHEET A 130.00 - THERE ARE NO NOTES OR MAUNUFACTURES
 SPECIFICATION SHEETS INDICATING COMPLIANCE WITH THE
 INTERIOR FINISH RATINGS PER THE APPLICABLE OCCUPACNY
 CHAPTER.
  
 PER NFPA 101, CHAPTER 38, NEW BUSINESS OCCUPANCIES
 38.3.3 INTERIOR FINISH.
 38.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH SECTION 10.2.
 38.3.3.2 INTERIOR WALL AND CEILING FINISH.
 38.3.3.2.1 INTERIOR WALL AND CEILING FINISH MATERIAL
 COMPLYING WITH SECTION 10.2 SHALL BE CLASS A OR CLASS B
 IN EXITS AND IN EXIT ACCESS CORRIDORS.
 38.3.3.2.2 INTERIOR WALL AND CEILING FINISHES SHALL BE
 CLASS A, CLASS B, OR CLASS C IN AREAS OTHER THAN THOSE
 SPECIFIED IN 38.3.3.2.1.
 38.3.3.3 INTERIOR FLOOR FINISH.
 38.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
 38.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES
 SHALL BE CLASS I OR CLASS II.
 38.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7.1 OR 10.2.7.2, AS APPLICABLE.
  
  
 PLEASE PROVIDE ALL APPLICABLE NOTES OR SPEC SHHETS IN
 COMPLIANCE WITH THE ABOVE CODE OR OTHER APPLICABLE CODE
 PER # 1 ABOVE.
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-31 Cont ID  
Sent By cpuell Date 2017-07-31 Time 09:50 Rev Time 0.00
Received By cpuell Date 2017-07-07 Time 13:26 Sent To  
Notes
2017-07-28 15:32:40TO CAROLINE FOR PROCESSING.
2017-07-10 13:27:02C33

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-10 Cont ID  
Sent By cpuell Date 2017-06-29 Time 13:24 Rev Time 0.00
Received By cpuell Date 2017-06-13 Time 13:35 Sent To  
Notes
2017-06-14 14:14:59C33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-05 Cont ID  
Sent By cpuell Date 2017-06-05 Time 15:26 Rev Time 0.00
Received By cpuell Date 2017-04-19 Time 13:42 Sent To  
Notes
2017-04-20 13:44:18C30

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-05-15 Cont ID  
Sent By jwitmer Date 2017-05-15 Time 13:59 Rev Time 0.00
Received By jwitmer Date 2017-05-15 Time 10:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-07-19 Cont ID  
Sent By ccole Date 2017-07-19 Time 11:59 Rev Time 0.00
Received By ccole Date 2017-07-19 Time 09:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-06-20 Cont ID  
Sent By ccole Date 2017-06-20 Time 15:09 Rev Time 0.00
Received By ccole Date 2017-06-20 Time 14:19 Sent To  
Notes
2017-06-20 15:15:30 
 2ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17040865
 6/20/17
  
 COMMENT #6 FROM THE 1ST REVIEW STILL EXISTS. I HAVE
 REPRINTED IT BELOW. IF THE INTENTION IS TO MODIFIY THE
 EXISTING SUPPORT STRUCTURE ON THE ROOF TO SUPPORT THE
 NEW CONDENSER, PLEASE PROVIDE COMPLETE DETAILS AND EDIT
 THE NOTE ON M3.0 THAT IS SPECIFYING A NEW STAND.
  
 6) THE ARCHITECTURAL AND STRUCTURAL PLANS ARE
 CONFLICTING WITH THE MECHANICAL PLAN AS TO HOW THE NEW
 ACCU-1 WILL BE MOUNTED ON THE ROOF- SEE A-111.00,
 S-301, AND M3.0. IF USING THE STAND, PLEASE PROVIDE TWO
 COPIES OF THE NOA BEARING THE APPROVAL STAMP OF THE
 EOR. THE EOR SHALL ALSO CIRCLE, HIGHLIGHT, OR OTHERWISE
 MARK ALL APPLICABLE NOTES, DETAILS, FASTENERS , AND
 DESIGN
  
 PRESSURE TABLES ETC.THAT PERTAIN TO THE INSTALLATION.
 SEE ALSO TABLE 1509.6.5 FBC-14 BUILDING AND SHOW THE
 CLEARANCE HEIGHT FROM THE ROOM SURFACE TO THE BOTTOM OF
 THE CU.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-25 Cont ID  
Sent By ccole Date 2017-04-25 Time 10:39 Rev Time 0.00
Received By ccole Date 2017-04-25 Time 07:26 Sent To  
Notes
2017-04-25 11:50:191ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040865
 4/25/17
  
 1) SHEET G-040.00: THE PROPOSED PROJECT IS CLASSIFIED
 AS A CHANGE OF OCCUPANCY AS DEFINED BY SECTION 202
 FBC-14 EXISTING BUILDING CODE. PLEASE ADD THE REQUIRED
 CODE DATA TO THE GENERAL PROJECT INFORMATION.
  
 2) REVISE THE ENERGY CALCULATIONS TO INDICATE CHANGE OF
 OCCUPANCY UNDER BUILDING CLASSIFICATION.
  
 3) M0.1: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR
 THE TOILET ROOMS AND THE ELECTRICAL AND SOILED ROOMS.
 PLEASE INDICATE HOW THE FANS WILL OPERATE- CONTINUOSLY
 OR INTERMITTENTLY.
  
 4) SHEET M1.1: IT APPEARS RETURN GRILLS ARE MISSING IN
 THE CEILINGS OF OFFICES # 25, 26, 27, 32, 33 & STAFF
 LOUNGE #41.
  
 5) M1.1: PLEASE LABEL THE CONDENSER SHOWN IN THE 2ND
 FLOOR PLAN. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE CONDENSER THAT INDICATE IT CAN BE INSTALLED ON THE
 INTERIOR OF THE BUILDING.
  
 6) THE ARCHITECTURAL AND STRUCTURAL PLANS ARE
 CONFLICTING WITH THE MECHANICAL PLAN AS TO HOW THE NEW
 ACCU-1 WILL BE MOUNTED ON THE ROOF- SEE A-111.00,
 S-301, AND M3.0. IF USING THE STAND, PLEASE PROVIDE TWO
 COPIES OF THE NOA BEARING THE APPROVAL STAMP OF THE
 EOR. THE EOR SHALL ALSO CIRCLE, HIGHLIGHT, OR OTHERWISE
 MARK ALL APPLICABLE NOTES, DETAILS, FASTENERS , AND
 DESIGN
  
 PRESSURE TABLES ETC.THAT PERTAIN TO THE INSTALLATION.
 SEE ALSO TABLE 1509.6.5 FBC-14 BUILDING AND SHOW THE
 CLEARANCE HEIGHT FROM THE ROOM SURFACE TO THE BOTTOM OF
 THE CU.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-07-20 Cont ID  
Sent By gjohnson Date 2017-07-20 Time 08:20 Rev Time 0.00
Received By gjohnson Date 2017-07-20 Time 06:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-06-21 Cont ID  
Sent By gjohnson Date 2017-06-21 Time 10:30 Rev Time 0.00
Received By gjohnson Date 2017-06-21 Time 08:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-17 Cont ID  
Sent By gjohnson Date 2017-05-17 Time 15:51 Rev Time 0.00
Received By gjohnson Date 2017-05-17 Time 15:51 Sent To  
Notes
2017-05-17 16:40:451ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHOW KNEE AND TOE CLEARANCE FOR LAVATORY. PER FBC
 ACC 606.2
  
 2. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE GRIPPING SURFACE. PER FBC ACC 609.4
  
 3. ROOM 28 P-TLT THE TOP FOR THE LAVATORY CAN NOT
 ENCROACH INTO THE CLEAR FLOOR SPACE OF THE TOILET. PER
 FBC ACC 604.3.1, 604.3.2,
  
 4. SHT. P0.1 DETAIL P1 A VACUUM RELIEF VALVE IS
 REQUIRED ON A BOTTOM FED WATER HEATER .PER FBC PL 504.2
  
 5. THE BREAKROOM SINK, THE SINK IN THE WAITING ROOM AND
 A MIN OF ONE SINK IN ONE OF THE EXAM ROOMS SHALL COMPLY
 WITH FBC ACC 606, 212.3 SINKS.
 WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT, BUT NO
 FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH
 ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606.
  
 6. THE WATER FOUNTAIN SHALL COMPLY WITH FBC ACC 602.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2017-07-28 Cont ID  
Sent By aaponte Date 2017-07-28 Time 15:31 Rev Time 0.00
Received By aaponte Date 2017-07-28 Time 15:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2017-06-29 Cont ID  
Sent By aaponte Date 2017-06-29 Time 15:22 Rev Time 0.00
Received By aaponte Date 2017-06-29 Time 15:21 Sent To  
Notes
2017-06-29 15:25:42COMMENT ON PREVIOUS REVIEW HAS NOT BEEN ADDRESSED. SEE
 BELOW.
 COMMENT DATED 6/1/17 :PLEASE INCLUDE A DRAWING
 INDICATING THE PROPOSEDL OFFICE FRONTAGE ALONG CLEMATIS
 STREET, AND ITS PERCENTAGE IN RELATION TO THE ENTIRE
 BUILDING FRONTAGE TO CONFIRM COMPLIANCE WITH THE
 MINIMUM RETAIL ACTIVE USE FRONTAGE (SEE TABLE IV:25 FOR
 PERCENTAGE REQUIRED)
 PLEASE CONTACT ANA MARIA APONTE AT 561-822-1439 FOR
 FURTHER INFORMATION.
  
 IF RAMP IS PROPOSED ALONG SIDEWALK PLEASE INCLUDE
 INFORMATION TO CONFIRM COMPLIANCE WITH MINIMUM 16'
 SETBACKS AS MEASURED FROM BACK OF EXISTING CURB ALONG
 CLEMATIS STREET.

Review Stop Z ZONING
Rev No 1 Status F Date 2017-06-01 Cont ID  
Sent By aaponte Date 2017-06-01 Time 14:19 Rev Time 0.00
Received By aaponte Date 2017-06-01 Time 14:19 Sent To  
Notes
2017-06-01 14:24:22PLEASE INCLUDE A DRAWING INDICATING THE PROPOSEDL
 OFFICE FRONTAGE ALONG CLEMATIS STREET, AND ITS
 PERCENTAGE IN RELATION TO THE ENTIRE BUILDING FRONTAGE
 TO CONFIRM COMPLIANCE WITH THE MINIMUM RETAIL ACTIVE
 USE FRONTAGE (SEE TABLE IV:25 FOR PERCENTAGE REQUIRED)