Plan Review Details - Permit 17040657
Plan Review Stops For Permit 17040657
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-11 Cont ID  
Sent By jwitmer Date 2017-05-11 Time 15:12 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2017-05-11 15:12:372014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17040657
 ADD: 2800 N FLAGLER DR. SUITE # 1003 (FIRST FLOOR
 LEVEL)
 CONT: RGL HOMES
 TEL: 954-540-3219
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MAY 11/ 2017
 ACTION: BUILDING PROVISO
  
 1) PLEASE NOTE THIS UNIT IS ON THE 1ST FLOOR AND IS
 EXEMPT FORM THE SOUND REQUIREMENT FOR FLOOR
 UNDERLAYMENT. IF THE DESIGNER OF RECORD AND OR THE
 CONTRACTOR ELECT TO INSTALL SOUND UNDERLAYMENT THEY
 WILL STILL NEED TO PROVIDE TESTING IN COMPLIANCE WITH:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-20 Cont ID  
Sent By jwitmer Date 2017-04-20 Time 15:10 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2017-04-20 15:09:502014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17040657
 ADD: 2800 N FLAGLER DR. SUITE # 1003
 CONT: RGL HOMES
 TEL: 954-540-3219
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: APRIL 20/ 2017
 ACTION: DENIED
  
 1) THE FLOOR PLAN INDICATES THE REMOVAL OF FLOOR TILE
 AND NEW 24 X24 PORCELAIN TILE CREMA MARFIL.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-05-02 Cont ID  
Sent By vperez Date 2017-05-02 Time 10:51 Rev Time 0.00
Received By vperez Date 2017-05-02 Time 10:51 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-11 Cont ID  
Sent By jwitmer Date 2017-05-11 Time 15:12 Rev Time 0.00
Received By jwitmer Date 2017-05-01 Time 09:31 Sent To  
Notes
2017-05-02 09:32:19ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-25 Cont ID  
Sent By gjohnson Date 2017-04-25 Time 11:55 Rev Time 0.00
Received By gjohnson Date 2017-04-14 Time 15:27 Sent To  
Notes
2017-04-14 15:27:45BLDG MISC 2

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-09 Cont ID  
Sent By gjohnson Date 2017-05-09 Time 10:02 Rev Time 0.00
Received By gjohnson Date 2017-05-09 Time 10:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-04-25 Cont ID  
Sent By gjohnson Date 2017-04-25 Time 11:48 Rev Time 0.00
Received By gjohnson Date 2017-04-25 Time 11:48 Sent To  
Notes
2017-04-25 11:55:011ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. THE SCOPE OF PLUMBING WORK INDICATES THE SINK,
 DISHWASHER AND REFRIGERATOR ICE LINE ARE BEING
 RELOCATED PLEASE PROVIDE AN EXISTING FLOOR PLAN AND A
 PROPOSED FLOOR PLAN IF MOVING PLUMING STACK PROVIDE A
 RISER DIAGRAM. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  