Plan Review Details - Permit 17040620
Plan Review Stops For Permit 17040620
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2017-06-28 Cont ID  
Sent By jwitmer Date 2017-06-28 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2017-06-28 Time 07:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2017-06-15 Cont ID  
Sent By cthroop Date 2017-06-15 Time 10:15 Rev Time 0.00
Received By cthroop Date 2017-06-12 Time 08:26 Sent To  
Notes
2017-06-15 10:20:16BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 5TH REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. 4X FEE HAS BEEN ASSESSED.
 F.S. 553.80 (2) (B)
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 2. PROVIDE TEST REPORT FOR SURFACE BURNING
 CHARACTERISTICS OF BUILDING MATERIALS PER ASTM E-84 FOR
 THE PROPOSED LVT FLOORING.
 FBC 603.1 FLAME SPREAD ? ASTM E-84
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2017-06-01 Cont ID  
Sent By jwitmer Date 2017-06-01 Time 08:35 Rev Time 0.00
Received By jwitmer Date 2017-06-01 Time 08:07 Sent To  
Notes
2017-06-01 08:35:352014 FBC- BUILDING PLAN REVIEW BUILDING
 W. P. B. PERMIT: 17040620
 ADD: 780 S. SAPODILLA AVE. SUITE # 214
 CONT: LOWES HOME CENTERS
 TEL: 561-721-5611
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4 X FEE HAS BEEN ADDED TO PERMIT!!!!!!!
 ************ 4X FEE NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B) ************* WITH RESPECT TO EVALUATION
 OF DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL
 GOVERNMENT FINDS IT NECESSARY, IN ORDER TO ENFORCE
 COMPLIANCE WITH THE FLORIDA BUILDING CODE AND ISSUE A
 PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY THE CODE
 THREE OR MORE TIMES FOR FAILURE TO CORRECT A CODE
 VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH
 REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE
 PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 4TH REVIEW
 DATE: THURS. JUNE 01/ 2017
 ACTION: DENIED
  
 THIS REVIEW A SALES BROCHURE FOR SMARTCORE ENGINEERED
 LUXURY FLOORS WAS SUBMITTED. PLEASE SHOW COMPLIANCE
 WITH:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE, WOOD FLOORING AND VINYL
 FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT
 TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND
 MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE
 STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO
 DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1A) 4TH REQUEST. FBC-B 2014 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) 4TH REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) 4TH REQUEST. FLAME SPREAD- FBC-B 2014 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-05-18 Cont ID  
Sent By jwitmer Date 2017-05-18 Time 07:17 Rev Time 0.00
Received By jwitmer Date 2017-05-18 Time 07:01 Sent To  
Notes
2017-05-18 07:17:532014 FBC- BUILDING PLAN REVIEW BUILDING
 W. P. B. PERMIT: 17040620
 ADD: 780 S. SAPODILLA AVE. SUITE # 214
 CONT: LOWES HOME CENTERS
 TEL: 561-721-5611
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 ************ 4X FEE NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B) ************* WITH RESPECT TO EVALUATION
 OF DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL
 GOVERNMENT FINDS IT NECESSARY, IN ORDER TO ENFORCE
 COMPLIANCE WITH THE FLORIDA BUILDING CODE AND ISSUE A
 PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY THE CODE
 THREE OR MORE TIMES FOR FAILURE TO CORRECT A CODE
 VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH
 REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE
 PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 3RD REVIEW
 DATE: THURS. MAY 18/ 2017
 ACTION: DENIED
  
 THE SUBMITTED TEST REPORTS FOR FLOOR SOUND INSULATION
 SELITBLOCK 2 TEST ASTM E 492-09 & ASTM E 90 BOTH ARE
 CODE COMPLIANT FOR A 6 INCH CONCRETE SLAB.
 MISSING IS THE FLAME SPREAD TESTING REPORT.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 3RD REQUEST!!!!! C) FLAME SPREAD- FBC-B 2014 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 COMPLIED. FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 COMPLIED. FBC-B 2014 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-05-04 Cont ID  
Sent By jwitmer Date 2017-05-04 Time 14:10 Rev Time 0.00
Received By jwitmer Date 2017-05-04 Time   Sent To  
Notes
2017-05-04 14:09:142014 FBC- BUILDING PLAN REVIEW BUILDING
 W. P. B. PERMIT: 17040620
 ADD: 780 S. SAPODILLA AVE. SUITE # 214
 CONT: LOWES HOME CENTERS
 TEL: 561-721-5611
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 ************ 4X FEE NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B) ************* WITH RESPECT TO EVALUATION
 OF DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL
 GOVERNMENT FINDS IT NECESSARY, IN ORDER TO ENFORCE
 COMPLIANCE WITH THE FLORIDA BUILDING CODE AND ISSUE A
 PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY THE CODE
 THREE OR MORE TIMES FOR FAILURE TO CORRECT A CODE
 VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH
 REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE
 PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 2ND REVIEW
 DATE: THURS. MAY 04/ 2017
 ACTION: DENIED
  
 THE SUBMITTED TEST REPORTS FOR FLOOR SOUND INSULATION
 SELITBLOCK 2 TEST ASTM E 492-09 & ASTM E 90 BOTH ARE
 FOR DROPPED CEILINGS WITH INSULATION, NOT CODE
 COMPLIANT, THAT IS NOT HOW SOUTH FLORIDA BUILDS
 HIGHRISES.
 NO FLAME SPREAD TESTING SUBMITTED.
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-18 Cont ID  
Sent By jwitmer Date 2017-04-18 Time 10:07 Rev Time 0.00
Received By jwitmer Date 2017-04-18 Time 10:00 Sent To  
Notes
2017-04-18 10:07:442014 FBC- BUILDING PLAN REVIEW BUILDING
 W. P. B. PERMIT: 17040620
 ADD: 780 S. SAPODILLA AVE. SUITE # 214
 CONT: LOWES HOME CENTERS
 TEL: 561-721-5611
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date   Cont ID  
Sent By   Date 2017-06-28 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-26 Time 13:35 Sent To  
Notes
2017-06-27 13:35:39RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-06-15 Cont ID  
Sent By cthroop Date 2017-06-15 Time 10:15 Rev Time 0.00
Received By cthroop Date 2017-06-08 Time 14:03 Sent To  
Notes
2017-06-09 14:12:25RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2017-06-01 Time   Rev Time 0.00
Received By lmarchan Date 2017-05-30 Time 10:51 Sent To  
Notes
2017-05-31 10:52:10RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-05-18 Time   Rev Time 0.00
Received By lmarchan Date 2017-05-15 Time 10:50 Sent To  
Notes
2017-05-16 10:50:30RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-04 Cont ID  
Sent By jwitmer Date 2017-05-04 Time 14:10 Rev Time 0.00
Received By jwitmer Date 2017-04-26 Time 13:07 Sent To  
Notes
2017-04-27 13:07:31RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-04-18 Time   Rev Time 0.00
Received By lmarchan Date 2017-04-13 Time 10:44 Sent To  
Notes
2017-04-14 10:44:12BLDG <5K