Plan Review Details - Permit 17040384
Plan Review Stops For Permit 17040384
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-02 Cont ID  
Sent By jgomez Date 2017-05-02 Time 10:22 Rev Time 0.00
Received By jgomez Date 2017-05-02 Time 09:40 Sent To  
Notes
2017-05-02 09:52:41 
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-17 Cont ID  
Sent By destabro Date 2017-05-01 Time 14:03 Rev Time 0.00
Received By jgomez Date 2017-04-17 Time 18:43 Sent To  
Notes
2017-04-17 18:52:15RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- SPECIFY SIZE AND TYPE OF EXISTING WINDOWS TO BE
 REPLACED TO VERIFY COMPLIANCE WITH EGRESS REQUIREMENTS.
 SEC. 704 FBC-EXISTING BUILDING, 5TH EDITION (2014).
  
 2- SPECIFY SIZE OF EXISTING FRENCH DOORS TO BE REPLACED
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- CLEARLY SPECIFY SIZE OF WINDOW MULLIONS TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- CLEARLY MARK WHICH ARE THE WINDOWS TO BE REPLACED.
 HIGHLIGHTED WINDOWS ON THE PLANS SUBMITTED DON'T ADD UP
 TO 23 WINDOWS AS SPECIFIED ON THE PERMIT APPLICATION.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND
 CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. UPDATE VALUATION AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-05-01 Cont ID  
Sent By destabro Date 2017-04-12 Time 15:50 Rev Time 0.00
Received By destabro Date 2017-05-01 Time 14:02 Sent To B
Notes
2017-05-01 14:02:595/1/2017 - APPLICANT PROVIDED UPDATED PRODUCT APPROVALS
 TO MATCH CONDITIONS OF HPB CASE NO. 17-21. DLE
2017-04-12 15:52:264/12/17 - APPLICANT RECIEVED LEVEL 2 APPROVAL TO
 REPLACE EXISTING WOOD WINDOWS (WHICH WERE PROVEN BEYOND
 REPAIR), BUT MUST USE ALUMINUM IMPACT PRODUCTS. VINYL
 OR PVC WINDOWS ARE NOT PERMITTED IN HISTORIC DISTRICTS
 WITHOUT HISTORIC PRESERVATION BOARD APPROVAL. PLEASE
 REVISE PRODUCT APPROVALS TO AN ALUMINUM PRODUCT TO PASS
 AT PERMIT LEVEL. DLE
2017-04-11 16:22:15ROUTED TO DESIREE ESTABROOK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-02 Cont ID  
Sent By jgomez Date 2017-05-02 Time 10:22 Rev Time 0.00
Received By jgomez Date 2017-05-02 Time 09:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-17 Cont ID  
Sent By jgomez Date 2017-04-17 Time 18:52 Rev Time 0.00
Received By jgomez Date 2017-04-10 Time 12:15 Sent To  
Notes
2017-04-11 12:16:03ROUTED TO HISTORIC VIA ZONING INBOX