Plan Review Details - Permit 17040313
Plan Review Stops For Permit 17040313
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-04-12 Cont ID  
Sent By jgomez Date 2017-04-12 Time 13:25 Rev Time 0.00
Received By jgomez Date 2017-04-12 Time 13:25 Sent To  
Notes
2017-04-12 13:26:54YAILEN CALLED TO SAY THEY WILL USE SYSTEM W58 FOR ALL
 ROOF ZONES.
 W58 DESIGN PRESSURES IS -105.0 P.S.F.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-04-12 Cont ID  
Sent By jgomez Date 2017-04-12 Time 08:57 Rev Time 0.00
Received By jgomez Date 2017-04-12 Time 08:43 Sent To  
Notes
2017-04-12 09:07:33RE-ROOF SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- FLORIDA PRODUCT APPROVAL FL2533-R17 SUBMITTED: THE
 DESIGN PRESSURES FOR THE SELECTED ASSEMBLY W-57 ARE
 -75.0. THE DESIGN PRESSURES FOR THE CORNER AREAS OF
 THIS BUILDING ARE HIGHER. NEED TO SELECT ANOTHER
 ASSEMBLY THAT MEETS THE DESIGN PRESSURES FOR ALL ROOF
 ZONES OR NEED TO PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY NOTE #8 ON PAGE 2 OF 57 TO
 MEET THE DESIGN PRESSURES FOR THE CORNER AREAS. NEED
 THE CALCULATIONS TO COMPLY WITH THE DESIGN PRESSURES
 REQUIRED BY SEC. 1609.1 FBC, 5TH EDITION (2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-10 Cont ID  
Sent By jgomez Date 2017-04-10 Time 17:44 Rev Time 0.00
Received By jgomez Date 2017-04-10 Time 17:21 Sent To  
Notes
2017-04-10 17:57:18RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- FLORIDA PRODUCT APPROVAL FL2533-R11 SUBMITTED IS TOO
 OLD. THIS PRODUCT APPROVAL HAVE BEING REVISED SEVERAL
 TIMES AND THE SELECTED ASSEMBLY W-52 IS NO LONGER THE
 SAME. THE CURRENT FLORIDA PRODUCT APPROVAL IS
 FL2533-R-17. PROVIDE CURRENT FLORIDA PRODUCT APPROVAL
 AND MARK PROPOSED ASSEMBLY TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. 1609.1
 FBC, 5TH EDITION (2014).
  
 2- THIS IS A VERY LARGE BUILDING. THERE ARE SEVERAL
 FLAT ROOFS IN THIS BUILDING. PROVIDE SKETCH SHOWING
 LOCATION AND DIMENSIONS OF THE FLAT AREA TO BE
 RE-ROOFED. SEC. 107.2.1 AND SEC. 109.3 CITY AMENDMENTS
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-04-12 Cont ID  
Sent By jgomez Date 2017-04-12 Time 13:23 Rev Time 0.00
Received By jgomez Date 2017-04-12 Time 13:23 Sent To  
Notes
2017-04-12 13:25:18YAILEN CALLED TO SAY THEY WILL USE SYSTEM W58 FOR ALL
 ROOF ZONES. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-12 Cont ID  
Sent By jgomez Date 2017-04-12 Time 08:42 Rev Time 0.00
Received By jgomez Date 2017-04-12 Time 08:42 Sent To  
Notes
2017-04-12 08:43:36RECEIVED E-MAIL FROM YAILEN ENRIQUEZ.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-10 Cont ID  
Sent By jgomez Date 2017-04-10 Time 17:57 Rev Time 0.00
Received By jgomez Date 2017-04-07 Time 09:38 Sent To  
Notes
2017-04-10 09:38:58JGOMEZ'S DESK