Plan Review Details - Permit 17040199
Plan Review Stops For Permit 17040199
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2017-09-27 Time 11:13 Sent To  
Notes
2017-09-27 12:40:552014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17040199
 ADD: 1515 N. FLAGLER DR. SUITE 100 & 700
 CONT: LB DEVELOPMENT & ENGINEERING
 TEL: 954-881-5693
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 5TH REVIEW
 DATE: WED. SEPT. 27/ 2017
 ACTION: BUILDING PROVISO
  
 1A) SHEET A4.23 DETAIL 1 THE AMBULATORY ACCESSIBLE
 COMPARTMENT DOOR WILL NEED TO SHOW COMPLIANCE WITH 2014
 FBC-ACCESSIBILITY CODE 604.8.2.2 DOORS. TOILET
 COMPARTMENT DOORS, INCLUDING DOOR HARDWARE, SHALL
 COMPLY WITH 404, EXCEPT THAT IF THE APPROACH IS TO THE
 LATCH SIDE OF THE COMPARTMENT DOOR, CLEARANCE BETWEEN
 THE DOOR SIDE OF THE COMPARTMENT AND ANY OBSTRUCTION
 SHALL BE 42 INCHES MINIMUM. THE DOOR SHALL BE
 SELF-CLOSING. A DOOR PULL COMPLYING WITH 404.2.7 SHALL
 BE PLACED ON BOTH SIDES OF THE DOOR NEAR THE LATCH.
  
 1B) 2014 ACCESSIBILITY CODE 404.2.3 CLEAR WIDTH. DOOR
 OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS
 SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE
 STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-08-09 Cont ID  
Sent By   Date 2017-08-09 Time 09:45 Rev Time 0.00
Received By jwitmer Date 2017-08-09 Time 09:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-07-19 Cont ID  
Sent By jwitmer Date 2017-07-19 Time 15:30 Rev Time 0.00
Received By jwitmer Date 2017-07-18 Time 13:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-08 Cont ID  
Sent By jwitmer Date 2017-06-08 Time 10:48 Rev Time 0.00
Received By jwitmer Date 2017-06-08 Time 10:10 Sent To  
Notes
2017-06-08 10:48:042014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17040199
 ADD: 1515 N. FLAGLER DR. SUITE 100 & 700
 CONT: LB DEVELOPMENT & ENGINEERING
 TEL: 954-881-5693
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. JUNE 08/ 2017
 ACTION: DENIED
  
 PLEASE READ!!!!!! THE RESUBMITTED NEW SET OF PLANS WAS
 NOT COLLATED WITH THE OLD PLAN SETS. THE NEW PLAN SETS
 WERE NOT COMPLETE SET OF PLANS!!!!! MISSING PLANS ONLY
 FOR ARCHITECTURE ARE:
  
 A0.04-A0.12 MISSING
 A0.14 MISSING
 A0.17-A4.21 MISSING
 A4.25-A5.51 MISSING
  
 A COMPLETE PLAN REVIEW CAN NOT BE COMPLETED UNTIL THE
 CONTRACTOR COLLATES THE PLANS!
  
 1) SHEET A0.13 THE DOOR SCHEDULE SHOWS THE ENTRY DOOR #
 18 WITH HARDWARE GROUP # 1 VANDAL ENTRANCE LOCK NOT
 PANIC HARDWARE, THIS IS ALLOWED, CODE COMPLIANT ON THE
 MAIN ENTRY DOOR BY EXCEPTION . 1008.1.9.3, ITEM 2. IF:
 2. IN BUILDINGS IN OCCUPANCY GROUP A HAVING AN OCCUPANT
 LOAD OF 300 OR LESS, GROUPS B, F, M AND S, AND IN
 PLACES OF RELIGIOUS WORSHIP, THE MAIN EXTERIOR DOOR OR
 DOORS ARE PERMITTED TO BE EQUIPPED WITH KEY-OPERATED
 LOCKING DEVICES FROM THE EGRESS SIDE PROVIDED:
 2.1. THE LOCKING DEVICE IS READILY DISTINGUISHABLE AS
 LOCKED;
 2.2. A READILY VISIBLE DURABLE SIGN IS POSTED ON THE
 EGRESS SIDE ON OR ADJACENT TO THE DOOR STATING: THIS
 DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. THE
 SIGN SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A
 CONTRASTING BACKGROUND; AND
 2.3. THE USE OF THE KEY-OPERATED LOCKING DEVICE IS
 REVOKABLE BY THE BUILDING OFFICIAL FOR DUE CAUSE.
  
 2) SHEET A0.13 THE DOOR SCHEDULE SHOWS THE DOOR TO THE
 TRAINING ROOM, DOOR # 20 ALSO WITH A VANDAL ENTRY LOCK.
 THIS DOOR SHOULD HAVE PANIC HARDWARE IN ACCORDANCE WITH
 1008.1.10.
  
 3) THE DESIGNER OF RECORD INDICATES 1 HOUR FIRE RATED
 WALLS BETWEEN THE TENANT SPACE AND COMMON AREAS AS WELL
 AS THE TRAINING ROOM 707. PLEASE REVIEW THE MECHANICAL
 COMMENT # 5 MISSING FIRE DAMPERS IN FIRE RATED WALLS
 AND COMPLIANCE WITH 2014 FBC-B 714.1.1 DUCTS AND AIR
 TRANSFER OPENINGS.
 PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS BY DUCTS
 THAT ARE NOT PROTECTED WITH DAMPERS SHALL COMPLY WITH
 SECTIONS 714.2 THROUGH 714.3.3. MISSING FIRE DAMPERS
 SEE M2.2.1. 10X8 O/A DUCT PENETRATING THE TRAINING/
 CORRIDOR WALL, 16X12 O/A DUCT PENETRATING THE TRAINING
 ROOM/ CORRIDOR WALL, TRAINING ROOM/ VESTIBULE/ MENS
 RESTROOM AND THE 8X8 SUPPLY DUCT PENETRATING THE COPY
 ROOM/ ELEVATOR LOBBY WALL.
  
 4) THE NEW OUTSIDE AIR DUCT WILL REQUIRE AN OUTSIDE AIR
 LOUVER ON THE EXTERIOR OF THE BUILDING. PLEASE PROVIDE
 COMPLIANCE WITH: 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31(C) PANEL WALLS: WALL LOUVERS
  
 5) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 6) THE RESTROOM DETAIL 1/ A4.23 IN BOTH RESTROOMS SHOWS
 6 OR MORE WATER CLOSETS AND OR COMBINATION OF WATER
 CLOSETS AND URINALS THEN COMPLIANCE WITH SECTION
 213.3.1 OF THE 2014 ACCESSIBILITY CODE IS REQUIRED.
 ALSO SEE:
 604.8.2 AMBULATORY ACCESSIBLE COMPARTMENTS. AMBULATORY
 ACCESSIBLE COMPARTMENTS SHALL COMPLY WITH 604.8.2.
 604.8.2.2 DOORS. TOILET COMPARTMENT DOORS, INCLUDING
 DOOR HARDWARE, SHALL COMPLY WITH 404, EXCEPT THAT IF
 THE APPROACH IS TO THE LATCH SIDE OF THE COMPARTMENT
 DOOR, CLEARANCE BETWEEN THE DOOR SIDE OF THE
 COMPARTMENT AND ANY OBSTRUCTION SHALL BE 42 INCHES
 (1065 MM) MINIMUM. THE DOOR SHALL BE SELF-CLOSING. A
 DOOR PULL COMPLYING WITH 404.2.7 SHALL BE PLACED ON
 BOTH SIDES OF THE DOOR NEAR THE LATCH. TOILET
 COMPARTMENT DOORS SHALL NOT SWING INTO THE MINIMUM
 REQUIRED COMPARTMENT AREA.
  
 604.8.2.3 GRAB BARS. GRAB BARS SHALL COMPLY WITH 609. A
 SIDE-WALL GRAB BAR COMPLYING WITH 604.5.1 SHALL BE
 PROVIDED ON BOTH SIDES OF THE COMPARTMENT.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-05-10 Cont ID  
Sent By jwitmer Date 2017-05-10 Time 07:53 Rev Time 0.00
Received By jwitmer Date 2017-05-09 Time 16:00 Sent To  
Notes
2017-05-10 07:53:392014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17040199
 ADD: 1515 N. FLAGLER DR. SUITE 100 & 700
 CONT: LB DEVELOPMENT & ENGINEERING
 TEL: 954-881-5693
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 10/ 2017
 ACTION: DENIED
  
 1) SHEET A0.13 THE DOOR SCHEDULE SHOWS THE ENTRY DOOR #
 18 WITH HARDWARE GROUP # 1 VANDAL ENTRANCE LOCK NOT
 PANIC HARDWARE, THIS IS ALLOWED, CODE COMPLIANT ON THE
 MAIN ENTRY DOOR BY EXCEPTION . 1008.1.9.3, ITEM 2. IF:
 2. IN BUILDINGS IN OCCUPANCY GROUP A HAVING AN OCCUPANT
 LOAD OF 300 OR LESS, GROUPS B, F, M AND S, AND IN
 PLACES OF RELIGIOUS WORSHIP, THE MAIN EXTERIOR DOOR OR
 DOORS ARE PERMITTED TO BE EQUIPPED WITH KEY-OPERATED
 LOCKING DEVICES FROM THE EGRESS SIDE PROVIDED:
 2.1. THE LOCKING DEVICE IS READILY DISTINGUISHABLE AS
 LOCKED;
 2.2. A READILY VISIBLE DURABLE SIGN IS POSTED ON THE
 EGRESS SIDE ON OR ADJACENT TO THE DOOR STATING: THIS
 DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. THE
 SIGN SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A
 CONTRASTING BACKGROUND; AND
 2.3. THE USE OF THE KEY-OPERATED LOCKING DEVICE IS
 REVOKABLE BY THE BUILDING OFFICIAL FOR DUE CAUSE.
  
 2) SHEET A0.13 THE DOOR SCHEDULE SHOWS THE DOOR TO THE
 TRAINING ROOM, DOOR # 20 ALSO WITH A VANDAL ENTRY LOCK.
 THIS DOOR SHOULD HAVE PANIC HARDWARE IN ACCORDANCE WITH
 1008.1.10.
  
 3) THE DESIGNER OF RECORD INDICATES 1 HOUR FIRE RATED
 WALLS BETWEEN THE TENANT SPACE AND COMMON AREAS AS WELL
 AS THE TRAINING ROOM 707. PLEASE REVIEW THE MECHANICAL
 COMMENT # 5 MISSING FIRE DAMPERS IN FIRE RATED WALLS
 AND COMPLIANCE WITH 2014 FBC-B 714.1.1 DUCTS AND AIR
 TRANSFER OPENINGS.
 PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS BY DUCTS
 THAT ARE NOT PROTECTED WITH DAMPERS SHALL COMPLY WITH
 SECTIONS 714.2 THROUGH 714.3.3. MISSING FIRE DAMPERS
 SEE M2.2.1. 10X8 O/A DUCT PENETRATING THE TRAINING/
 CORRIDOR WALL, 16X12 O/A DUCT PENETRATING THE TRAINING
 ROOM/ CORRIDOR WALL, TRAINING ROOM/ VESTIBULE/ MENS
 RESTROOM AND THE 8X8 SUPPLY DUCT PENETRATING THE COPY
 ROOM/ ELEVATOR LOBBY WALL.
  
 4) THE NEW OUTSIDE AIR DUCT WILL REQUIRE AN OUTSIDE AIR
 LOUVER ON THE EXTERIOR OF THE BUILDING. PLEASE PROVIDE
 COMPLIANCE WITH: 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31(C) PANEL WALLS: WALL LOUVERS
  
 5) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 6) THE RESTROOM DETAIL 1/ A4.23 IN BOTH RESTROOMS SHOWS
 6 OR MORE WATER CLOSETS AND OR COMBINATION OF WATER
 CLOSETS AND URINALS THEN COMPLIANCE WITH SECTION
 213.3.1 OF THE 2014 ACCESSIBILITY CODE IS REQUIRED.
 ALSO SEE:
 604.8.2 AMBULATORY ACCESSIBLE COMPARTMENTS. AMBULATORY
 ACCESSIBLE COMPARTMENTS SHALL COMPLY WITH 604.8.2.
 604.8.2.2 DOORS. TOILET COMPARTMENT DOORS, INCLUDING
 DOOR HARDWARE, SHALL COMPLY WITH 404, EXCEPT THAT IF
 THE APPROACH IS TO THE LATCH SIDE OF THE COMPARTMENT
 DOOR, CLEARANCE BETWEEN THE DOOR SIDE OF THE
 COMPARTMENT AND ANY OBSTRUCTION SHALL BE 42 INCHES
 (1065 MM) MINIMUM. THE DOOR SHALL BE SELF-CLOSING. A
 DOOR PULL COMPLYING WITH 404.2.7 SHALL BE PLACED ON
 BOTH SIDES OF THE DOOR NEAR THE LATCH. TOILET
 COMPARTMENT DOORS SHALL NOT SWING INTO THE MINIMUM
 REQUIRED COMPARTMENT AREA.
  
 604.8.2.3 GRAB BARS. GRAB BARS SHALL COMPLY WITH 609. A
 SIDE-WALL GRAB BAR COMPLYING WITH 604.5.1 SHALL BE
 PROVIDED ON BOTH SIDES OF THE COMPARTMENT.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-08-24 Cont ID  
Sent By jpearson Date 2017-08-24 Time 16:32 Rev Time 0.00
Received By jpearson Date 2017-08-24 Time 16:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2017-07-24 Cont ID  
Sent By jpearson Date 2017-07-24 Time 08:28 Rev Time 0.00
Received By jpearson Date 2017-07-24 Time 08:28 Sent To  
Notes
2017-07-24 08:47:04CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 BASED ON REVISION PROVIDED, NEW ELECTRICAL REVIEW
 COMMENTS:
  
 1. PANEL L1A SHOWS A 225 AMP MAIN BREAKER, WHICH
 EXCEEDS THE PERMITTED RATING PER CODE. PROVIDE
 CORRECTION. NEC TABLE 450.3(B)
 2. PROVIDE PANEL SCHEDULE FOR BYPASS PANEL AND PANEL
 UPS. NEC 215.5, 408.4, 408.30; FBC 107.2.1
 3. PROVIDE SHORT CIRCUIT CALCULATIONS FOR SERVICES ON
 1ST AND 7TH FLOOR TO CONFIRM AIC RATINGS OF PANELS IS
 SUFFICIENT, INCLUDE THE TRANSFORMER SECONDARY
 CALCULATION OF 75KVA TRANSFORMER FEEDING PANEL IT.
 PROVIDE NOTE THAT SERVICE EQUIPMENT SHALL BE MARKED PER
 NEC 110.24. NEC 110.9, 110.10, 110.24
 4. LOAD FOR PANEL H EXCEEDS THE OVERCURRENT PROTECTION
 AND AMPACITY OF WIRE STATED ON PLAN. PROVIDE
 CORRECTION. NEC 215.2, 215.3, 310.15(B)(16), 240.4
 5. PROVIDE LIGHTING CONTROL PANEL DETAIL, INCLUDE ALL
 CIRCUITS CONTROLLED BY PANEL. FBC 107.2.1, C405.2
 6. SHEET E3.2 AND E3.2.1, KEY NOTE #2, STATES THERE IS
 A DETAIL OF TIME CLOCK CONTACTOR C-1 ON SHEET E5.1.
 THIS DETAIL IS NOT ON ANY OF THE SHEETS. PROVIDE DETAIL
 OF ALL CONTACTOR CONTROL PANELS USED FOR RECEPTACLE
 CONTROL. REVIEWER NOTED SEVERAL CIRCUITS FROM PANELS
 NOT ON ANY OF THE CONTACTOR DETAILS PROVIDED. FBC
 107.2.1, C405.7.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-06-26 Cont ID  
Sent By jleahy Date 2017-06-26 Time 14:23 Rev Time 0.00
Received By jleahy Date 2017-06-26 Time 14:22 Sent To  
Notes
2017-06-26 14:26:24CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 REVISIONS NOT COLLATED BACK INTO THE SETS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-07-24 Cont ID  
Sent By jleahy Date 2017-05-05 Time 10:17 Rev Time 0.00
Received By jpearson Date 2017-05-05 Time 10:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-06-29 Cont ID  
Sent By pleduc Date 2017-06-29 Time   Rev Time 0.00
Received By pleduc Date 2017-06-29 Time 14:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-06-06 Cont ID  
Sent By pleduc Date 2017-06-06 Time   Rev Time 0.00
Received By pleduc Date 2017-06-05 Time 16:00 Sent To  
Notes
2017-06-05 16:51:132ND REVIEW
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) COMPLIED
  
  
 2) COMPLIED
  
  
  
 3) DENIED - SHEET A 1.11 AND SHEETS A 5.11 & 5.12, WERE
 NOT ATTACHED TO THE RE-SUBMITTED PACKET.
  
 HOWEVER, ON REVIEW OF THE VOIDED SHEET A 5.11 THAT UL
 LISTING WAS FOUND.
  
 PLEASE ATTACHED ALL APPLICABLE SHEETS TO THE
 RESUBMITTAL.
  
  
  
  
 4) DENIED - THE NOTE COMMENT REMIANS. THIS NOTE
 COMMENTS NEEDS TO BE REVIEWED AS THERE ARE NO FA
 DEVICES OF THE ELECTRICAL SHEETS.
  
 FA DEVICES SHALL BE INSTALLED PER NFPA 72 UNDER
 SEPARATE SHOP DRAWINGS.
  
  
 PLEASE CORRECT..
  
  
  
 5) DENIED - THE "NOT" SHALL BE PLACED AFTER THE SHALL.
 CARD READERS SHALL "NOT" DELAY OR INTERFERE WITH ANY
 EXIT DOOR AND SHALL COMPLY WITH NFPA 101, CHAPTER 7,
 MEANS OF EGRESS AND SHALL BE INSTALLED UNDER SEPARATE
 SHOP DRAWINGS.
  
 PLEASE CORRECT.
  
  
  
 6) COMPLIED
  
  
  
 7) COMPLIED
  
  
  
 8) COMMENT REMAINS - WHEN RESUBMITTING, PLEASE PROVIDE
 PLAN SHEET REVISION CLOUDS OR NUMBERED NARRATIVE
 RESPONSES TO THE ABOVE.
  
  
  
 9) COMMENT REMAINS - ADDITIONAL COMMENTS MAY BE
 PROVIDED ON THE RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-04-12 Cont ID  
Sent By pleduc Date 2017-04-12 Time   Rev Time 0.00
Received By pleduc Date 2017-04-11 Time 15:19 Sent To  
Notes
2017-04-11 16:51:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1)
 SHEET A 0.01 - THERE INCORRECT REFERENCES INDICATED FOR
 THE CURRENT EDITIONS OF THE FLORIDA FIRE PREVENTION
 CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH
 NFPA 110, 2013 EDITION.
 AIR CONDITION WORK SHALL COMPLY WITH NFPA 90 A & B,
 2012 EDITION
  
 PLEASE CORRECT ALL THE APPLICABLE CODE EDITIONS.
  
  
  
 2)
 SHEETS A 0.0. & 0.03 - NOTE # 7 MAKES REFERENCE TO AND
 INCORRECT NFPA 13 EDITION.
  
 PLEASE CORRECT AS NOTED ON # 1 ABOVE.
  
  
  
  
 3)
 SHEET A 1.11 - THERE ARE INDICATIONS OF WALL TYPE
 REFERENCE OF A BOX AROUND, S1, TO WALLS CONTAINING FIRE
 RATED DOORS. ON SHEETS A 5.11 & 5.12 THERE ARE NO
 INDICATORS MATHCING THAT REFERENCE OR ANY OTHER LISTED
 WALL RATING.
  
 PLEASE PROVIDE THE APPLICABLE LISTED WALL RATING FOR
 THAT REFERENCE.
  
  
  
  
 4)
 SHEET A 0.02 & 0.03 - NOTE # 4 INDICATES REFERNCES TO
 LIFE SAFETY DEVICES ON THE ELECTICAL SHEETS. THERE ARE
 NO INDICATORS OF ANY FIRE ALARM DEVICES ON ANY
 ELECTICAL SHEET.
  
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
  
 THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
 PLEASE PROVIDE AN APLLICABLE NOTE.
  
  
  
 5)
 SHEET E - THE ELECTRICAL SHEETS INDICATE CARD READERS
 ON EXIT DOORS. THESE CARD READERS SHALL DELAY OR
 INTERFERE WITH ANY EXIT DOOR AND SHALL COMPLY WITH NFPA
 101, CHAPTER 7, MEANS OF EGRESS AND SHALL BE INSTALLED
 UNDER SEPARATE SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE.
  
  
  
 6)
 SHEET A 0.01 - NOTE # 7 REFERENCES WORK ON THE FIRE
 SPRINKLER SYSTEMS. THE FIRE SPRINKLER SHALL REMAIN
 ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD. ANY TIME
 THAT WORK ON THE FIRE SPRINKLER SYSTEM EXCEEDS 4 HOURS,
 A FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL
 FULL AND COMPLETE PROTECTION IS RETURNED.
  
 PLEASE PROVIDE AND APPLICABLE NOTE.
  
  
 7)
 SHEET A 0.02 & 0.03 - FOR INFORMATIONAL PURPOSES, THERE
 IS A MISSPELLED WORD; "OCCUYPANCY", INDICATED IN THE
 TABLE HEADER.
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-09-27 Cont ID  
Sent By   Date 2017-09-27 Time   Rev Time 0.00
Received By cpuell Date 2017-09-19 Time 17:56 Sent To  
Notes
2017-09-19 17:56:21GJOHNSON'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2017-08-28 Time   Rev Time 0.00
Received By lmarchan Date 2017-07-31 Time 11:05 Sent To  
Notes
2017-08-02 11:05:17C04

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-24 Cont ID  
Sent By gjohnson Date 2017-07-24 Time 12:41 Rev Time 0.00
Received By gjohnson Date 2017-06-26 Time 16:18 Sent To  
Notes
2017-06-27 16:19:05C18

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-26 Cont ID  
Sent By jleahy Date 2017-06-26 Time 14:23 Rev Time 0.00
Received By jleahy Date 2017-06-01 Time 08:47 Sent To  
Notes
2017-06-02 08:48:01C18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-05-10 Time   Rev Time 0.00
Received By lmarchan Date 2017-04-05 Time 15:26 Sent To  
Notes
2017-04-06 15:26:11C04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-05-10 Time   Rev Time 0.00
Received By jwitmer Date 2017-05-10 Time 07:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-08-30 Cont ID  
Sent By ccole Date 2017-08-30 Time 11:11 Rev Time 0.00
Received By ccole Date 2017-08-30 Time 10:46 Sent To  
Notes
2017-08-30 11:12:57MECHANICAL PROVISO;
  
 PROVIDE A COMMISSIONING REPORT FOR THE REPLACED
 SYSTEMS.
  
 CCOLE- 8/30/17

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-07-24 Cont ID  
Sent By ccole Date 2017-07-24 Time 10:22 Rev Time 0.00
Received By ccole Date 2017-07-24 Time 10:13 Sent To  
Notes
2017-07-24 10:25:383RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17040199
 7/24/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIRD REQUEST FOR AC COOLING AND HEATING
 CALCULATONS- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-06-12 Cont ID  
Sent By ccole Date 2017-06-12 Time 16:22 Rev Time 0.00
Received By ccole Date 2017-06-12 Time 16:14 Sent To  
Notes
2017-06-12 16:25:221ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040199
 6/12/17
  
 1) THE REQUESTED COOLING AND HEATING CALCULATIONS FOR
 THE HEAT PUMPS WERE NOT SUBMITTED- PLEASE COMPLY
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-11 Cont ID  
Sent By ccole Date 2017-04-11 Time 09:11 Rev Time 0.00
Received By ccole Date 2017-04-11 Time 09:11 Sent To  
Notes
2017-04-11 09:14:161ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040199
 4/11/17
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW HEAT PUMPS- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION
  
 2) PROVIDE EQUIPMENT SCHEDULES FOR EF-1 & 2.
  
 3) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE
 WOMEN'S AND MEN'S RESTROOMS.
  
 4) M6.2: PLEASE CLARIFY HOW THE O/A UNITS WERE SIZED
 AND FOR WHAT AREAS THEY ARE SERVING.
  
 5) M2.21: MISSING FIRE DAMPERS- A) 10X8 O/A DUCT
 PENETRATING THE TRAINING/CORRIDOR WALL. B) 16X12 O/A
 DUCT PENETRATING THE TRAINING/CORRIDOR WALL, AND THE
 TRAINING/VESTIBULE/MEN'S RESTROOM WALLS. C) 8X8 SUPPLY
 DUCT PENETRATING THE COPY ROOM/ELEVATOR LOBBY WALL.
  
 6) SUBMIT AN APPROVED FL. PRODUCT APPROVAL AND/OR
 MIAMI-DADE NOA FOR THE LOUVERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2017-09-22 Cont ID  
Sent By gjohnson Date 2017-09-22 Time 11:48 Rev Time 0.00
Received By gjohnson Date 2017-09-22 Time 11:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2017-08-30 Cont ID  
Sent By tklarge Date 2017-08-30 Time 10:55 Rev Time 0.00
Received By tklarge Date 2017-08-29 Time 08:18 Sent To  
Notes
2017-08-30 09:51:251) PROVIDE A FIRESTOPPING DETAIL FOR PVC PIPE THROUGH
 FIRE RATED WALLS. THE PIPE FIRESTOPPING DETAILS ON
 SHEET A0.05 ARE ONLY FOR FERRROUS AND NON-FERROUS PIPE.
 2014 FBC SEC. 714.3.1.
 2) THE WALL FINISH AROUND THE MOP/SERVICE SINK SHALL
 COMPLY WITH THE 2015 FBC SEC.1210.2.2.
 3) SHT. A4.23 - THE DOORS ON THE AMBULATORY ACCESSIBLE
 STALLS IN THE MEN'S AND WOMEN'S RESTROOMS SHALL NOT
 SWING INTO THE MINIMUM REQUIRED COMPARTMENT AREA. 2014
 FBC-ACCESS. SEC. 604.8.2.2.
 4) SHT.A4.23 - DETAIL #1 - ENLARGED TOILET ROOM - THE
 HANDICAPPED ACCESSIBLE TOILET STALLS SHOW THE WATER
 CLOSETS AT 1'-7" FROM THE ADJACENT WALL TO THE
 CENTERLINE OF THE WATER CLOSET. THE WATER CLOSETS SHALL
 BE LOCATED 16 INCHES MINIMUM TO 18 INCHES MAXIMUM TO
 THE SIDE WALL.
 2014 FBC-ACCESS. SEC.604.2.
 5) SHT. A4.23 - DETAIL #3 - NOTE ON THE PLAN THAT THE
 SHOWER CONTROLS SHALL BE LOCATED 15 INCHES MAXIMUM FRON
 THE CENTERLINE OF THE SEAT TOWARD THE SHOWER
 OPENING.2014 FBC-ACCESS SEC.608.5.1.
 6) A FIXED SHOWER HEAD LOCATED 48 INCHES MAXIMUM ABOVE
 THE SHOWER FINISH FLOOR SHALL BE PERMITTED INSTEAD OF A
 HAND-HELD SPRAY UNIT PER 2014 FBC-ACCESS SEC.608.6.
 SHOW COMPLIANCE ON THE PLANS OR SUPPLY A SHOWER SPRAY
 UNIT IN COMPLIANCE WITH 2014 FBC-ACCESS. SEC. 608.6.
 7) SHT. P0.1 - WATER HEATER DETAIL - DELETE THE
 REFERENCE TO THE RELIEF LINE BEING PIPED TO THE
 EXTERIOR AND CHANGE THE CODE TO 2014 FBC, NOT 2010.
 8) SHT. P5.1 - SANITARY RISER - WHERE DOES THE VENT FOR
 THE THE DRINKING FOUNTAIN/SK-1 / MOP SINK TERMINATE?
 WHERE IS THE VENT THROUGH THE ROOF? THIS ALSO OCCURS ON
 THE VENT FOR THE GANG TOILETS. CLARIFY.
 9) SUBMIT AN EXPANDED SANITARY AND WATER RISER FOR
 REVIEW. A COMPREHENSIVE REVIEW CANNOT BE DONE AS THE
 DRAWING IS TOO CCOMPRESSED. WPB AMEND. TO FBC SEC.
 107.2.1.
 10) SHT.P5.1 - THE SANITARY RISER SHOWS 6 LAVATORIES IN
 A ROW IN THE MEN'S RESTROOM AND THE FLOOR PLAN ON P
 2.2.1 SHOWS 5 LAVATORIES. CLARIFY. 11)
 11) THE SANITARY RISER FOR THE MEN''S & WOMEN'S
 RESTROOM DOES NOT COMPLY WITH 2014 FBC-PLUMBING
 SEC.914.1, 914.2 FOR A CIRCUIT VENT. CLARIFY.
 12) SIZE THE TYPICAL VENT STACK FFOR THE LAVATORIES ON
 THE SANITARY RISER.COMPLY WITH 2014 FBC-PLUMBING
 SEC.906.1 & TABLE 906.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-07-24 Cont ID  
Sent By gjohnson Date 2017-07-24 Time 12:29 Rev Time 0.00
Received By gjohnson Date 2017-07-24 Time 10:32 Sent To  
Notes
2017-07-24 12:41:253RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 3RD REQUEST PREVIOUS COMMENT NOT COMPLIED 2. PER FBC
 ACC 213.3.1 AT LEAST ONE OF THE TOILET COMPARTMENTS IN
 EACH BATHROOM SHALL BE AN AMBULATORY STALL PER FBC
 604.8.2 ( YOU ARE MISSING THE GRAB BARS)
 213.3.1 TOILET COMPARTMENTS.
 WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE
 TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN
 ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH
 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH
 604.8.2 WHERE SIX OR MORE TOILET COMPARTMENTS ARE
 PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER
 CLOSETS TOTALS SIX OR MORE FIXTURES.
 THIS CODE REQUIREMENT IS FOR THE FIXTURES PROVIDED NOT
 FIXTURES REQUIRED.
  
 NEW COMMENT
 1. SHT.4.23 DETAIL #1 THE DIMENSION FOR THE DEPTH OF
 THE TRANSFER SHOWER IS AN EXACT MEASUREMENT NOT A MIN
 PLEASE CLARIFY. PER FBC ACC 608.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-06-23 Cont ID  
Sent By gjohnson Date 2017-06-23 Time 12:52 Rev Time 0.00
Received By gjohnson Date 2017-06-23 Time 12:52 Sent To  
Notes
2017-06-23 12:56:441ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 PREVIOUS COMMENT NOT COMPLIED 2. PER FBC ACC 213.3.1 AT
 LEAST ONE OF THE TOILET COMPARTMENTS IN EACH BATHROOM
 SHALL BE AN AMBULATORY STALL PER FBC 604.8.2
 213.3.1 TOILET COMPARTMENTS.
 WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE
 TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN
 ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH
 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH
 604.8.2 WHERE SIX OR MORE TOILET COMPARTMENTS ARE
 PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER
 CLOSETS TOTALS SIX OR MORE FIXTURES.
 THIS CODE REQUIREMENT IS FOR THE FIXTURES PROVIDED NOT
 FIXTURES REQUIRED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-04 Cont ID  
Sent By gjohnson Date 2017-05-04 Time 10:32 Rev Time 0.00
Received By gjohnson Date 2017-05-03 Time 16:41 Sent To  
Notes
2017-05-04 11:25:351ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. A MIN OF ONE URINAL SHALL BE ACCESSIBLE PER FBC ACC
 213.3.3 PLEASE SHOW ACCESSIBILITY PER FBC ACC 605.2 AND
 605.3
  
 2. PER FBC ACC 213.3.1 AT LEAST ONE OF THE TOILET
 COMPARTMENTS IN EACH BATHROOM SHALL BE AN AMBULATORY
 STALL PER FBC 604.8.2
  
 3. PLEASE PROVIDE ELEVATION DIMENSIONS FOR THE SHOWER
 CONTROLS AND THE SEAT. PER FBC ACC 608.5.1 AND 610.3
 AND 610.3.2
  
 4. SHT. P5.1 ON THE SANITARY RISER THE CIRCUIT VENT
 SHALL BE CONNECTED BETWEEN THE TWO HWC PER FBC PL 914.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  