Plan Review Stops For Permit 17040028 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2017-04-11 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2017-04-11 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2017-04-11 |
Time |
14:27 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-04-11 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2017-04-11 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2017-04-03 |
Time |
10:44 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2017-04-11 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2017-04-11 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2017-04-11 |
Time |
11:32 |
Sent To |
E |
|
Notes |
2017-04-11 11:46:39 | PASS PROVISO | | 1) PROVIDE A ENGINEER DETAIL ON CURB TO ROOF | | AND RTU TO CURB TIE DOWN. AT FIRST INSPECTION. | | PER SECTION 301.15 WIND RESISTANCE 2014 FBC (M) | | 2) FAN SHUT DOWN REQUIRED FOR RTU 1 AND 2 | | PER SECTION 606.2.1 RETURN AIR SYSTEM. 2014 FBC (M) | | 3) REFER TO SECTION 606.4.1 SUPERVISION AND SECTION | | 606.3 INSTALLATION 2014 FBC (M) | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|
|
|