Plan Review Stops For Permit 17031212 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2017-06-23 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-06-23 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-06-23 |
Time |
16:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2017-04-13 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-04-13 |
Time |
07:43 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-04-13 |
Time |
07:22 |
Sent To |
E |
|
Notes |
2017-04-13 07:41:22 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | | | 1ST REVIEW | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. PROVIDE SITE PLAN. | | FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING | | OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA | | AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION | | PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL | | FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING | | DIMENSIONS; AND ALL EXTERIOR ELEVATIONS: | | | | 2. PROVIDE PRODUCT APPROVALS FOR EXT. DOOR AND OHD. | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE AND DOOR SUBMITTALS. | | | | 3. PROVIDE ELECTRICAL PLAN. | | | | 4. PROVIDE A LANDING AT EXT. DOOR. | | R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS. | | THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH | | EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE | | LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A | | MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE | | DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE | | PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT | | VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT). | | | | 5. TRUSS ENGINEERING TO BE DEFERRED SUBMITTAL. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2017-06-09 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2017-06-09 |
Time |
08:58 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2017-06-09 |
Time |
08:58 |
Sent To |
|
|
Notes |
2017-06-09 08:58:51 | NEED ELECTRICAL PERMIT WITH SCOPE AND VALUE OF WORK. | | FBC 105.1, 109.3 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2017-04-13 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2017-04-13 |
Time |
08:03 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2017-04-13 |
Time |
08:02 |
Sent To |
|
|
Notes |
2017-04-13 09:08:04 | FBC 2014 5TH EDITION | | FBC 2014 5TH ED. RESIDENTIAL | | FBC 2014 EXISTING BUILDING | | NFPA 70 2011 EDITION | | | | ELECTRIC REQUIRED BY FBC RESIDENTIAL | | E3901.9 AT LEAST ONE OUTLET SHALL BE INSTALLED IN EACH | | GARAGE | | E3902.3 ALL RECEPTACLES INSTALLED IN GARAGES SHALL BE | | GFCI PROTECTED | | E3903.3 AT LEAST ONE WALL SWITCH CONTROLLED LIGHTING | | OUTLET IN THE GARAGE, AND AT LEAST | | ONE WALL SWITCH CONTROLLED LIGHTING OUTLET TO PROVIDE | | EXTERIOR ILLUMINATION AT | | THE SIDE ENTRANCE. | | | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | BN1165, BU1753, PX163 | | 561-805-6713 | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2017-06-23 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-06-23 |
Time |
16:45 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-06-06 |
Time |
13:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-06-07 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-06-07 |
Time |
13:19 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2017-03-30 |
Time |
16:44 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
N |
Date |
2017-06-23 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-06-23 |
Time |
16:45 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-06-23 |
Time |
16:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2017-04-13 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-04-13 |
Time |
07:35 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-04-13 |
Time |
07:22 |
Sent To |
|
|
Notes |
2017-04-13 07:41:05 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | | | 1ST REVIEW | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, | | ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO | | PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS | | WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID | | RECEIPT MUST BE RETURNED TO THE CITY BUILDING | | DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED. | | FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT | | (561) 233-5025. | | | | | | | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2017-06-23 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-06-23 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-06-23 |
Time |
16:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2017-06-13 |
|
|
Cont ID |
|
Sent By |
njwira |
Date |
2017-06-13 |
Time |
10:00 |
Rev Time |
0.00 |
Received By |
njwira |
Date |
2017-06-12 |
Time |
16:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2017-03-31 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2017-06-07 |
Time |
13:19 |
Rev Time |
0.00 |
Received By |
njwira |
Date |
2017-03-31 |
Time |
15:51 |
Sent To |
B |
|
Notes |
2017-03-31 16:03:43 | 3/31/17- FAILED | | | | PLEASE INCLUDE TWO(2)COPIES OF A SURVEY SHOWING | | ADDITION MEETS SETBACKS. |
|
|