Plan Review Details - Permit 17031144
Plan Review Stops For Permit 17031144
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-10 Cont ID  
Sent By jwitmer Date 2017-04-10 Time 13:40 Rev Time 0.00
Received By jwitmer Date 2017-04-10 Time 10:28 Sent To  
Notes
2017-04-10 13:40:41BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17031144
 ADD: 2711 EXCHANGE COURT
 CONT: TO BE DETERMINED
 TEL: 561-358-5080
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. APRIL 10/ 2017
 ACTION: DENIED
  
 1) PLEASE NOTE THIS IS A CHANGE OF OCCUPANCY FROM THE
 LAST KNOWN PERMITTED USE. NEITHER THE COVERSHEET NOR
 SHEET A-1.00 SHOW THIS IS A CHANGE OF OCCUPANCY. IT
 APPEARS THIS IS A 2ND TRY FROM THE EXPIRED PERMIT :
 14110421 TO CHANGE THE OCCUPANCY FROM A BUSINESS USE TO
 A DAYCARE OCCUPANCY. THERE IS NOT ENOUGH INFORMATION
 SUPPLIED TO DO AN ADEQUATE PLANS REVIEW, A THOROUGH
 REVIEW CANNOT BE MADE AT THIS TIME, AS A RESULT OF THE
 ADDITIONAL INFORMATION REQUESTED ADDITIONAL COMMENTS
 MAY APPEAR THAT WERE NOT PART OF THIS REVIEW.
 THE DESIGNER OF RECORD HAS NOT DECLARED WHICH METHOD
 THE CHANGE OF OCCUPANCY WAS DESIGNED TO? 2014
 FBC-EXISTING BUILDING CODE SECTION 301.1. CHANGE OF
 OCCUPANCY, ADDITION OR RELOCATION OF ALL EXISTING
 BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS LISTED
 IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE
 APPLICANT. APPLICATION OF A METHOD SHALL BE THE SOLE
 BASIS FOR ASSESSING THE COMPLIANCE OF WORK PERFORMED
 UNDER A SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE
 CODE OFFICIAL.
  
  
 1A) SITE PLAN SUBMITTED DOES NOT SHOW THE PROPERTY
 LINES, THE DISTANCE FROM THE BUILDING TO THE PROPERTY
 LINE. THE SITE PLANS DOESN?T INDICATE THE MINIMUM
 BUILDING TYPE, IF SPRINKLERED OR NOT.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (3) MINIMUM TYPE OF CONSTRUCTION FBC-B TABLE 503 .
 (5) BUILDING IS FIRE SPRINKLERED OR NOT?/ IS IT
 REQUIRED?
  
 1B) THE COVERSHEET INDICATES AN EXISTING OUTDOOR PLAY
 AREA, BOTH THE PROPERTY APPRAISERS AND GOGGLE BOTH SHOW
 ON BOTH SIDE OF THE BUILDING EXISTING PARKING LOTS.
 PLAY GROUND, AND 12 X 16 SHADE STRUCTURE WILL BE
 CONSIDERED NEW STRUCTURES AND WILL NEED FURTHER
 INFORMATION ON BOTH. 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 1C)(1) ON THE COVER SHEET AS-1.00 THERE IS HAND WRITTEN
 THE AMOUNT OF 3 YEAR OLDS (35), THE AMOUNT OF 4 YEAR
 OLDS (30), TEACHERS AND ADMINISTRATION, PLEASE PROVIDE
 COMPLIANCE WITH FBC-B TABLE 1004.1.2 PROVIDE THE
 REQUIRED SQUARE FEET PER OCCUPANT AND THE TOTAL SQUARE
 FOOTAGE FOR THE BUILDING. DAYCARE @ 35 NET.
  
 1C)(2) ON THE COVER SHEET AS-1.00 THERE IS HAND WRITTEN
 THE AMOUNT OF 3 YEAR OLDS (35), THE AMOUNT OF 4 YEAR
 OLDS TO BE ENROLLED IN THE DAYCARE. ON THE RIGHT SIDE
 OF THE SHEET UNDER THE HEADING OUTDOOR PLAY AREAS, IS
 LISTED PRE-K THREE?S AND PRE-K FOURS. WITH A PRE- K
 PROGRAM THE OCCUPANTS ARE IN ORGANIZED TEACHING
 SESSIONS WHERE NOT ONLY THE REQUIREMENTS OF:
 FBC-B 466 DAYCARE NEED TO BE MET BUT ALSO 468 FOR
 SCHOOLS. THERE ALSO IS A NOTE THAT STATES THESE
 STUDENTS ARE NON-INFANTS. WILL THERE BE ANY CHILDREN 2
 ? AGE OR LESS THAT ARE NOT CAPABLE OF SELF
 PRESERVATION. 308.6 308.6 INSTITUTIONAL GROUP I-4, DAY
 CARE FACILITIES (CHILD DAYCARE).
  
 308.6.1. . 308.6.1 CLASSIFICATION AS GROUP E. A CHILD
 DAY CARE FACILITY THAT PROVIDES CARE FOR MORE THAN FIVE
 BUT NO MORE THAN 100 CHILDREN 21/2 YEARS OR LESS OF
 AGE, WHERE THE ROOMS IN WHICH THE CHILDREN ARE CARED
 FOR ARE LOCATED ON A LEVEL OF EXIT DISCHARGE SERVING
 SUCH ROOMS AND EACH OF THESE CHILD CARE ROOMS HAS AN
 EXIT DOOR DIRECTLY TO THE EXTERIOR, SHALL BE CLASSIFIED
 AS GROUP E.
  
 1D) ON THE COVER SHEET AS-1.00 THERE IS HAND WRITTEN
 THE AMOUNT OF 3 YEAR OLDS (35), THE AMOUNT OF 4 YEAR
 OLDS (30), TEACHERS AND ADMINISTRATION, PLEASE ONLY THE
 DESIGNER OF RECORD CAN ALTER THE PLANS SINCE THEY HAVE
 A TITLEBLOCK WITH THE ARCHITECTURAL FIRM WEST
 ARCHITECTURAL & DESIGN.
 NO ARCHITECT HAS NOT TAKEN RESPONSIBILITY FOR THESE
 PLANS, NOT SIGNED AND SEALED. PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC RECORD SHALL
 HAVE THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL
 AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS
 PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE
 ARCHITECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST
 AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC
 61G1-16.003
  
 1E) 4) FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 2010 FBC-B 436.1(2) STORAGE ROOMS 1 HR FIRE RATED /
 TABLE 715.4 3/4 HR OPENING PROTECTIVES.
  
 1F) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 107.3.5.1.1.(7) OCCUPANCY LOAD/EGRESS REQUIREMENTS
 SHALL INCLUDE:
 OCCUPANCY LOAD, MISSING OCCUPANT LOADS IN SECURITY &
 STORAGE ROOM, BREAK ROOM, ART & MUSIC CENTER, COMPUTER
 ROOM, FIRST AID ROOM, FILE ROOM, RECEPTION, CONFERENCE
 ROOM, FAMILY & CHILDREN ROOM, ADULT READING AND
 RESEARCH ROOM & ADMINISTRATORS OFFICE.
 GROSS
 NET
 MEANS OF EGRESS;
 EXIT ACCESS PLANS FAIL TO IDENTIFY FIRE RATED CORRIDORS
 FOR A DAYCARE OCCUPANCY :
 2014 FBC-B 1037.2.2
 1G) WHERE THE TWO EXIT ACCESSES FROM A DAY CARE
 OCCUPANCY IN AN APARTMENT BUILDING ENTER THE SAME
 CORRIDOR AS THE APARTMENT OCCUPANCY, THE EXIT ACCESSES
 SHALL BE SEPARATED IN THE CORRIDOR BY A SMOKE BARRIER
 HAVING NOT LESS THAN A 1-HOUR FIRE-RESISTANCE RATING
 CONSTRUCTED IN ACCORDANCE WITH SECTION 710. THE SMOKE
 BARRIER SHALL BE LOCATED SO THAT IT HAS AN EXIT ON EACH
 SIDE.
  
  
 1H) EXIT/ EXIT DISCHARGE / DOORS SEE 2014 FBC-B 1037.1
 PANIC & FIRE EXIT HARDWARE OCCUPANT LOAD WILL BE OVER
 100. NOTE DOOR SIZES ARE NOT PROVIDED: 2014 FBC-B
 1008.1.1/ FBC-ACCESS. CODE 404.2.3 & 404.2.4.
  
 1I) EMERGENCY LIGHTING AND EXIT SIGNS: 1024
 ILLUMINATION AND MARKING OF MEANS OF EGRESS.
 ILLUMINATION AND MARKING OF MEANS OF EGRESS SHALL
 COMPLY WITH SECTION 1006.
  
 1J) 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS SEE COMMENT # 1
 ACCESSIBLE ROUTE
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS : NOT SHOWN SHOW COMPLIANCE WITH
 2010 FBC-ACCESS. 211.2.
  
 1K) 4) 2014 FBC-B COMPLY WITH THIS CHAPTER. DAY CARE
 OCCUPANCIES WILL ALSO NEED TO COMPLY WITH THE 2014
 FBC-B CHAPTER 466.
  
 1L)) SHOW COMPLIANCE. 466.2 CLOSET DOORS. EVERY CLOSET
 DOOR LATCH SHALL BE SUCH THAT CLIENTS CAN OPEN THE DOOR
 FROM INSIDE THE CLOSET.
  
 1M) SHOW COMPLIANCE. 466.3 BATHROOM DOORS. EVERY
 BATHROOM DOOR LOCK SHALL BE DESIGNED TO PERMIT OPENING
 OF THE LOCKED DOOR FROM THE OUTSIDE IN AN EMERGENCY.
 THE OPENING DEVICE SHALL BE READILY ACCESSIBLE TO THE
 STAFF.
  
 1N) SHOW COMPLIANCE 466.4 DOOR CLOSURE. FOR THE NEWLY
 RATED CORRIDORS. ANY EXIT DOOR DESIGNED TO BE NORMALLY
 CLOSED SHALL BE KEPT CLOSED AND SHALL COMPLY WITH
 SECTION 715.3.
  
 1O) THE PLEASE PROVIDE THE ACTUAL WINDOW SIZE AND TYPE
 OF WINDOW, SINGLE HUNG, CASEMENT OR STOREFRONT.
 2014 FBC-B EMERGENCY ESCAPE AND RESCUE
 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND RESCUE
 OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7
 SQUARE FEET (0.53 M2).
 1029.4.1
 EVERY ROOM OR SPACE GREATER THAN 250 SQUARE FEET (23.2
 M2) IN EDUCATIONAL OCCUPANCIES USED FOR CLASSROOM OR
 OTHER EDUCATIONAL PURPOSES OR NORMALLY SUBJECT TO
 STUDENT OCCUPANCY AND EVERY ROOM OR SPACE NORMALLY
 SUBJECT TO CLIENT OCCUPANCY, OTHER THAN BATHROOMS, IN
 GROUP D OCCUPANCIES SHALL HAVE NOT LESS THAN ONE
 OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT COMPLIES WITH
 THE FOLLOWING:
  
 1. SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH,
 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE FEET (0.53
 M2) IN AREA.
  
 2. THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING
 DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM NOT MORE
 THAN 54 INCHES (1372 MM) ABOVE THE FINISHED FLOOR.
  
 1P) 2014 EXST. BLDG. CODE 1002.2.2 FIRE ALARM AND
 DETECTION SYSTEM. WHERE A CHANGE IN OCCUPANCY
 CLASSIFICATION OCCURS THAT REQUIRES A FIRE ALARM AND
 DETECTION SYSTEM TO BE PROVIDED BASED ON THE NEW
 OCCUPANCY IN ACCORDANCE WITH CHAPTER 10 OF THE FLORIDA
 BUILDING CODE, BUILDING, SUCH SYSTEM SHALL BE PROVIDED
 THROUGHOUT THE AREA WHERE THE CHANGE OF OCCUPANCY
 OCCURS. EXISTING ALARM NOTIFICATION APPLIANCES SHALL BE
 AUTOMATICALLY ACTIVATED THROUGHOUT THE BUILDING. WHERE
 THE BUILDING IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM,
 ALARM NOTIFICATION APPLIANCES SHALL BE PROVIDED
 THROUGHOUT THE AREA WHERE THE CHANGE OF OCCUPANCY
 OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED.
  
 FBC-B 466.7.2 DETECTION.
 A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 72, WITH PLACEMENT OF DETECTORS IN
 EACH STORY IN FRONT OF DOORS TO THE STAIRWAYS AND IN
 THE CORRIDORS OF ALL FLOORS OCCUPIED BY THE DAY CARE
 OCCUPANCY. DETECTORS ALSO SHALL BE INSTALLED IN
 LOUNGES, RECREATION AREAS AND SLEEPING ROOMS IN THE DAY
 CARE OCCUPANCY.
  
 1Q) PLEASE NOTE THIS IS A DAYCARE OCCUPANCY, WITH PRE-K
 4 YEAR OLDS, WHEN ANY EDUCATIONAL ACTIVITIES SUCH AS
 TEACHING THE ALPHABET THIS WILL TRIGGER THE
 REQUIREMENTS FOR EDUCATIONAL OCCUPANCY AND CORRIDOR
 WIDTHS OF 72 INCHES FOR 100 OCCUPANTS OR MORE. 2014
 FBC-B 1018.2. THEN THE SECOND ISSUE IS OCCUPANCY
 SEPARATION BETWEEN OCCUPANCIES, SEPARATED OR NOT?
  
 2) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-04-05 Cont ID  
Sent By jleahy Date 2017-04-05 Time 12:48 Rev Time 0.00
Received By jleahy Date 2017-04-05 Time 12:48 Sent To  
Notes
2017-04-05 12:53:11FLORIDA BUILDING CODE 2014 5TH EDITION
 NFPA 70 2011 EDITION
  
 NO ELECTRIC SHOWN.
 NEC 2011 406.14 ALL 15 AND 20 AMPERE NON-LOCKING
 RECEPTACLES SHALL BE LISTED AS TAMPER RESISTANT.
  
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 BN1165, BU1753, PX163
 561-805-6713
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-04-03 Cont ID  
Sent By pleduc Date 2017-04-04 Time   Rev Time 0.00
Received By pleduc Date 2017-04-03 Time 11:30 Sent To  
Notes
2017-04-03 16:03:29THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1)
 SHEET AC 1.00 - THERE IS A NOTE INDICATING EGRESS
 WINDOW INFORMATION. THERE IS ALSO A NOTE INDICATING A
 2' 2" X 50" WINDOW DIMENSION. THERE IS INSUFFICIENT
 INFOMATION DEMONSTRATING COMPLIANCE FOR EGRESS WINDOWS.
  
 PER NFPA 101, CHAPTER 16, NEW DAYCARE OCCUPANCIES
  
 16.2.11 SPECIAL MEANS OF EGRESS FEATURES.
 16.2.11.1 WINDOWS FOR RESCUE.
 16.2.11.1.1 EVERY ROOM OR SPACE NORMALLY SUBJECT TO
 CLIENT OCCUPANCY, OTHER THAN BATHROOMS, SHALL HAVE NOT
 LESS THAN ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT
 COMPLIES WITH ALL OF THE FOLLOWING, UNLESS OTHERWISE
 PERMITTED BY 16.2.11.1.2:
 (1) SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20 IN. (510 MM) IN WIDTH, 24
 IN. (610 MM) IN HEIGHT, AND 5.7 FT2 (0.5 M2) IN AREA.
 (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 IN. (1120 MM) ABOVE THE FLOOR.
 (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID,
 WITH A WIDTH AND HEIGHT THAT PROVIDES NOT LESS THAN THE
 REQUIRED 5.7 FT2 (0.5 M2) OPENING AND A DEPTH OF NOT
 LESS THAN 20 IN. (510 MM), TO PASS FULLY THROUGH THE
 OPENING.
  
 PLEASE PROVIDE SPECIFIC WINDOW DETAIL
 SHOWING/INDICATING COMPLIANCE WITH ALL 3 REQUIREMENTS.
  
  
  
  
 2)
 SHEET AC 1.00 - THERE IS NO DOOR SCHEDULE TO
 INDICATE/CONFIRM DOOR AND OPENING SIZE,INCLUDING
 BATHROOM DOORS, EXIT HARDWARE, LOCKS AND LATCHING, ETC.
  
 16.2.2.2 DOORS.
 16.2.2.2.1 GENERAL. DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 16.2.2.2.2 PANIC HARDWARE OR FIRE EXIT HARDWARE. ANY
 DOOR IN A REQUIRED MEANS OF EGRESS FROM AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR LOCK IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE COMPLYING WITH 7.2.1.7.
 16.2.2.2.3 SPECIAL LOCKING ARRANGEMENTS.
 16.2.2.2.3.1 DELAYED-EGRESS LOCKING SYSTEMS COMPLYING
 WITH 7.2.1.6.1 SHALL BE PERMITTED.
 16.2.2.2.3.2 ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES
 COMPLYING WITH 7.2.1.6.2 SHALL BE PERMITTED.
 16.2.2.2.3.3 ELEVATOR LOBBY EXIT ACCESS DOOR ASSEMBLIES
 LOCKING IN ACCORDANCE WITH 7.2.1.6.3 SHALL BE
 PERMITTED.
 16.2.2.2.4* DOOR LATCHES. EVERY DOOR LATCH TO CLOSETS,
 STORAGE AREAS, KITCHENS, AND OTHER SIMILAR SPACES OR
 AREAS SHALL BE SUCH THAT CLIENTS CAN OPEN THE DOOR FROM
 INSIDE THE SPACE OR AREA.
 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK
 SHALL BE DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR
 FROM THE OUTSIDE BY AN OPENING DEVICE THAT SHALL BE
 READILY ACCESSIBLE TO THE STAFF.
  
 PLEASE PROVIDE SPECIFIC DETAILS MEETING THE
 REQUIREMENTS.
  
  
  
  
 3)
 SHEET AC 1.00 - THERE APPEARS TO BE A KITCHEN ROOM. ANY
 COOKING EQUIPMENT SHALL MEET THE REQUIRMETS OF NFPA 96
  
 16.3.2.3 COOKING FACILITIES SHALL BE PROTECTED IN
 ACCORDANCE WITH 9.2.3, UNLESS OTHERWISE PERMITTED BY
 16.3.2.4 OR 16.3.2.5.
 16.3.2.4 OPENINGS SHALL NOT BE REQUIRED TO BE PROTECTED
 BETWEEN FOOD PREPARATION AREAS AND DINING AREAS.
 16.3.2.5 APPROVED DOMESTIC COOKING EQUIPMENT USED FOR
 FOOD WARMING OR LIMITED COOKING SHALL NOT BE REQUIRED
 TO BE PROTECTED.
  
 PLEASE PROVIDE A NOTE WITH INTENTIONS OR COMPLIANCE.
  
  
  
 4)
 SHEET AC 1.00 - THERE IS AN INCORRECT"2015" REFERENCE
 TO THE CURRENT FFPC.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE, EFFECTIVE
 DECEMBER 31, 2014, INCLUDING THE 2012 EDITION OF NFPA 1
 AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR
 STANDARDS.
  
  
  
 5)
 SHEET AC 1.00 - THERE IS NO SITE PLAN SUBMITTED. A SITE
 PLAN IS REQUIRED SHOWING THE ENTIRE PROPERTY CONFIRMING
 ALL EXTS LEAD TO A PUBLIC WAY.
  
 16.2.7 DISCHARGE FROM EXITS. DISCHARGE FROM EXITS SHALL
 BE ARRANGED IN ACCORDANCE WITH SECTION 7.7.
  
 7.7 DISCHARGE FROM EXITS.
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC WAY OR AT AN EXTERIOR EXIT
 DISCHARGE, UNLESS OTHERWISE PROVIDED IN 7.7.1.2 THROUGH
 7.7.1.4.
 7.7.1.1 YARDS, COURTS, OPEN SPACES, OR OTHER PORTIONS
 OF THE EXIT DISCHARGE SHALL BE OF THE REQUIRED WIDTH
 AND SIZE TO PROVIDE ALL OCCUPANTS WITH A SAFE ACCESS TO
 A PUBLIC WAY.
  
 PLEASE PROVIDE A DETAILED SITE PLAN.
  
  
  
 6)
 SHEET AC 1.00 - THERE IS A REFERENCE TO AN ELECRICAL
 SHEET FOR EMERGENCY LIGHTING. NO ELECTRICAL SHEET
 SUBMITTED.
  
  
  
 7)
 THRE IS NO INDICATIONS OF A FIRE ALARM
  
 16.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 16.3.4.1 GENERAL. DAY-CARE OCCUPANCIES, OTHER THAN
 DAY-CARE OCCUPANCIES HOUSED IN ONE ROOM HAVING AT LEAST
 ONE DOOR OPENING DIRECTLY TO THE OUTSIDE AT GRADE PLANE
 OR TO AN EXTERIOR EXIT ACCESS BALCONY IN ACCORDANCE
 WITH 7.5.3, SHALL BE PROVIDED WITH A FIRE ALARM SYSTEM
 IN ACCORDANCE WITH SECTION 9.6.
 16.3.4.2 INITIATION. INITIATION OF THE REQUIRED FIRE
 ALARM SYSTEM SHALL BE BY MANUAL MEANS AND BY OPERATION
 OF ANY REQUIRED SMOKE DETECTORS AND REQUIRED SPRINKLER
 SYSTEMS. (SEE 16.3.4.5.)
  
  
 8)
 THERE IS INSUFFICEINT INFORMATION SUBMITTED TO COMPLETE
 A COMPHRENSIVE FIRE PLAN REVIEW. PLEASE ENSURE THAT THE
 SUBMITTAL MEETS ALL THE REQUIRMENTS OF THE FLORIDA
 STATUTUE AND THE FLORIDA FIRE PREVENTION CODE FOR NEW
 DAY CARES.
  
  
  
  
 9)
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
  
 10)
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
  
  
 11)
 THIS BUILDING DOES NOT MEET THE REQUIREMENTS FOR
 OCCUPANCY AS A DAY CARE AND SHALL NOT BE OCCUPIED UNTIL
 IT DOES AND HAS PASSED ALL APPLICABLE INSPECTIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-27 Cont ID  
Sent By cpuell Date 2017-04-27 Time 11:44 Rev Time 0.00
Received By cpuell Date 2017-03-29 Time 10:23 Sent To  
Notes
2017-03-31 10:24:08B16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-04-10 Cont ID  
Sent By jwitmer Date 2017-04-10 Time 13:41 Rev Time 0.00
Received By jwitmer Date 2017-04-10 Time 10:52 Sent To  
Notes
2017-04-10 13:41:17BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-06 Cont ID  
Sent By ccole Date 2017-04-06 Time 14:46 Rev Time 0.00
Received By ccole Date 2017-04-06 Time 14:46 Sent To  
Notes
2017-04-06 14:54:401ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17031144
 4/6/17
  
 1) A CHANGE OF OCCUPANCY REQUIRES COMPLIANCE WITH
 SECTION1009 FBC-14 EXISTING BUILDING CODE. PLEASE
 PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS
 AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. PROVIDE
 ON THE PLAN A VENTILATION SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 2) SUBMIT MECHANIOCAL ALTERATION PLANS IF APPLICABLE TO
 THE PROPOSED PROJECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-04-11 Cont ID  
Sent By gjohnson Date 2017-04-11 Time 15:27 Rev Time 0.00
Received By gjohnson Date 2017-04-11 Time 15:27 Sent To  
Notes
2017-04-11 15:56:231ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. BATHROOMS AND DRINKING FOUNTAIN SHALL COMPLY WITH:
 FLORIDA BUILDING CODE 5TH EDITION (2014) ACCESSIBILITY.
 THE PLAN SHALL SHOW COMPLIANCE WITH FBC ACC SEC
 602-603-604-605-606-607
  
 2. SERVICE SINK REQUIRED. PER FBC PL TABLE 403.1
  
 3. SHT. AC-1.00 THE PLUMBING FIXTURE CALCULATIONS
 SHOULD BE UNDER 2014 5TH EDITION OF FBC PL
  
 4. WILL THE KITCHEN BE USED FOR COOKING IF SO IS THERE
 AN EXISTING GREASE INTERCEPTOR PROVIDE SIZE AND TYPE
 WITH SIZING CALCULATIONS, AND MUST BE CERTIFIED BY
 ENGINEER OR PLUMBING CONTRACTOR. PER WPB AMEND TO FBC
 107.2.1
  
 5. PLANS SHALL BE SIGN AND SEALED BY ARCHITECT TAKING
 RESPONSIBILITY FOR DESIGN. PER WPB AMEND TO FBC 107.2.1
  
  
  
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-04-18 Cont ID  
Sent By njwira Date 2017-04-18 Time 15:07 Rev Time 0.00
Received By njwira Date 2017-04-18 Time 15:12 Sent To I
Notes
2017-04-18 15:12:484/18/17- FAILED
  
 PLEASE PROVIDE TWO(2) COPIES OF A SURVEY SHOWING WHERE
 THE WORK IS BEING DONE.
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH