Plan Review Details - Permit 17030989
Plan Review Stops For Permit 17030989
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-04-21 Cont ID  
Sent By skennedy Date 2017-04-21 Time 13:53 Rev Time 0.00
Received By skennedy Date 2017-04-21 Time 13:53 Sent To  
Notes
2017-04-21 13:54:45ALL WORK SUBJECT TO INSPECTOR. REPORTS SUBMITTED BY
 ENGINEER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-04-19 Cont ID  
Sent By skennedy Date 2017-04-19 Time 16:40 Rev Time 0.00
Received By skennedy Date 2017-04-19 Time 16:33 Sent To  
Notes
2017-04-19 16:35:472ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 2ND REVIEW FBC 2014 EXISTING BUILDING
  
 THE RESUBMITTAL DOES NOT MEET THE REQUIREMENTS OF THE
 FIRST REVIEW.
  
 NO PRODUCT APPROVAL INFORMATION WAS SUBMITTED FOR THE
 WINDOWS OR DOORS. ALTHOUGH A PRODUCT APPROVAL WAS
 SUBMITTED FOR STORM PANELS, THERE IS NO ADDITIONAL
 INSTALLATION PLAN AS REQUIRED BY CITY POLICY. PROVIDE
 AN INSTALLATION SCHEDULE AND KEY PLAN. FBC 107.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-12 Cont ID  
Sent By skennedy Date 2017-04-12 Time 09:58 Rev Time 0.00
Received By skennedy Date 2017-04-12 Time 09:58 Sent To  
Notes
2017-04-12 10:08:151ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 1ST REVIEW FBC 2014 EXISTING BUILDING
  
 RESULT FAIL
  
 THIS APPLICATION IS TO RESOLVE WORK DONE WITHOUT A
 PERMIT AS DESCRIBED IN CE16060098 AS "REAR BUILDING
 REMODEL (FRAMING, INSULATION, DRYWALL, DOOR, WINDOWS &
 ELECTRICAL WORK). AN ENGINEER'S EVALUATION DATED
 12/15/2016 WAS SUBMITTED BUT IS DOES NOT ADEQUATELY
 ADDRESS ALL OF THE POTENTIAL BUILDING ISSUES AND DID
 NOT ADDRESS ELECTRICAL. ELECTRICAL WILL BE ADDRESSES BY
 A LICENSED ELECTRICIAN.
  
 PLEASE PROVIDE THE ADDITIONAL FOLLOWING SUBMITTALS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3.
 SPECIFICALLY, PROVIDE STORM PANEL, WINDOW, AND DOOR
 SUBMITTALS.
  
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
 FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-04-21 Cont ID  
Sent By skennedy Date 2017-04-21 Time 13:51 Rev Time 0.00
Received By skennedy Date 2017-04-21 Time 13:51 Sent To  
Notes
2017-04-21 13:55:02REPORT SUBMITTED BY ELECTRICAL CONTRACTOR. ALL WORK
 SUBJECT TO ELECTRICAL INSPECTOR.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-04-19 Cont ID  
Sent By skennedy Date 2017-04-19 Time 16:40 Rev Time 0.00
Received By skennedy Date 2017-04-19 Time 16:40 Sent To  
Notes
2017-04-19 16:43:292ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 2ND REVIEW FBC 2014 EXISTING BUILDING
  
 RESULT FAIL - AN APPLICATION WAS SUBMITTED BUT NO
 INSPECTION REPORT WAS PROVIDED. PLEASE COMPLIY WITH THE
 REMAINING COMMENTS BELOW AS PROVIDED IN THE 1ST REVIEW.
  
 THIS APPLICATION IS TO RESOLVE WORK DONE WITHOUT A
 PERMIT AS DESCRIBED IN CE16060098. NO ELECTRICAL
 INFORMATION HAS BEEN PROVIDED. PLEASE HAVE THE PROPERTY
 INSPECTED BY A LICENSED ELECTRICIAN. THE ELECTRICIAN
 SHOULD INSPECT THE PROPERTY INCLUDING DESTRUCTIVE
 INSPECTION IF NEEDED AND BE PREPARED TO PROVIDE A
 REPORT SPECIFYING CORRECTIONS NEEDED AND FURTHER BE
 PREPARED TO CERTIFY COMPLIANCE WITH APPLICABLE
 REQUIREMENTS.
  
 IN ADDITION TO GENERAL CONFORMANCE TO THE REQUIREMENTS
 OF APPLICABLE CODE, THE FOLLOWING MAY BE REQUIRED IF
 NOT CURRENTLY PROVIDED.
  
 FBC- 107.3.5.3 SMOKE DETECTORS PURSUANT TO FBC-R
 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
 FBCRE 3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET.
  
 FBCRE 3703.2 KITCHEN AND DINING AREA RECEPTACLES.
 A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL
 BE PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA,
 DINING AREA OR SIMILAR AREA OF A DWELLING. THE KITCHEN
 COUNTERTOP RECEPTACLES SHALL BE SERVED BY A MINIMUM OF
 TWO 20-AMPERE-RATED BRANCH CIRCUITS, EITHER OR BOTH OF
 WHICH SHALL ALSO BE PERMITTED TO SUPPLY OTHER
 RECEPTACLE OUTLETS IN THE SAME KITCHEN, PANTRY,
 BREAKFAST AND DINING AREA INCLUDING RECEPTACLE OUTLETS
 FOR REFRIGERATION APPLIANCES.
  
 FBCE 3902.3 OUTDOOR RECEPTACLES.
 ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED OUTDOORS SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
  
 FBCRE 3902.1 BATHROOM RECEPTACLES.
 ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED IN BATHROOMS SHALL HAVE
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
  
 FBCE 3902.6 KITCHEN RECEPTACLES.
 ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES THAT SERVE COUNTERTOP SURFACES SHALL HAVE
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
  
 FBCE 3902.7 SINK RECEPTACLES.
 ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES THAT ARE LOCATED WITHIN 6 FEET (1829 MM) OF
 THE OUTSIDE EDGE OF A SINK THAT IS LOCATED IN AN AREA
 OTHER THAN A KITCHEN, SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
 RECEPTACLE OUTLETS SHALL NOT BE INSTALLED IN A FACE-UP
 POSITION IN THE WORK SURFACES OR COUNTERTOPS.
  
 FBCRE 3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
  
 FBCRE 4002.14 TAMPER-RESISTANT RECEPTACLES.
 IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT RECEPTACLES.
  
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
 FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-04-12 Cont ID  
Sent By skennedy Date 2017-04-12 Time 09:20 Rev Time 0.00
Received By skennedy Date 2017-04-12 Time 09:20 Sent To  
Notes
2017-04-12 09:39:531ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 1ST REVIEW FBC 2014 EXISTING BUILDING
  
 RESULT FAIL
  
 THIS APPLICATION IS TO RESOLVE WORK DONE WITHOUT A
 PERMIT AS DESCRIBED IN CE16060098. NO ELECTRICAL
 INFORMATION HAS BEEN PROVIDED. PLEASE HAVE THE PROPERTY
 INSPECTED BY A LICENSED ELECTRICIAN AND COORDINATE THE
 ELECTRICIAN TO APPIY FOR AN ELECTRICAL PERMIT AS A SUB
 PERMIT TO THIS APPLICATION. THE ELECTRICIAN SHOULD
 INSPECT THE PROPERTY INCLUDING DESTRUCTIVE INSPECTION
 IF NEEDED AND BE PREPARED TO PROVIDE A REPORT
 SPECIFYING CORRECTIONS NEEDED AND FURTHER BE PREPARED
 TO CERTIFY COMPLIANCE WITH APPLICABLE REQUIREMENTS.
  
 IN ADDITION TO GENERAL CONFORMANCE TO THE REQUIREMENTS
 OF APPLICABLE CODE, THE FOLLOWING MAY BE REQUIRED IF
 NOT CURRENTLY PROVIDED.
  
 FBC- 107.3.5.3 SMOKE DETECTORS PURSUANT TO FBC-R
 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
 FBCRE 3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET.
  
 FBCRE 3703.2 KITCHEN AND DINING AREA RECEPTACLES.
 A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL
 BE PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA,
 DINING AREA OR SIMILAR AREA OF A DWELLING. THE KITCHEN
 COUNTERTOP RECEPTACLES SHALL BE SERVED BY A MINIMUM OF
 TWO 20-AMPERE-RATED BRANCH CIRCUITS, EITHER OR BOTH OF
 WHICH SHALL ALSO BE PERMITTED TO SUPPLY OTHER
 RECEPTACLE OUTLETS IN THE SAME KITCHEN, PANTRY,
 BREAKFAST AND DINING AREA INCLUDING RECEPTACLE OUTLETS
 FOR REFRIGERATION APPLIANCES.
  
 FBCE 3902.3 OUTDOOR RECEPTACLES.
 ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED OUTDOORS SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
  
 FBCRE 3902.1 BATHROOM RECEPTACLES.
 ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED IN BATHROOMS SHALL HAVE
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
  
 FBCE 3902.6 KITCHEN RECEPTACLES.
 ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES THAT SERVE COUNTERTOP SURFACES SHALL HAVE
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
  
 FBCE 3902.7 SINK RECEPTACLES.
 ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES THAT ARE LOCATED WITHIN 6 FEET (1829 MM) OF
 THE OUTSIDE EDGE OF A SINK THAT IS LOCATED IN AN AREA
 OTHER THAN A KITCHEN, SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
 RECEPTACLE OUTLETS SHALL NOT BE INSTALLED IN A FACE-UP
 POSITION IN THE WORK SURFACES OR COUNTERTOPS.
  
 FBCRE 3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
  
 FBCRE 4002.14 TAMPER-RESISTANT RECEPTACLES.
 IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT RECEPTACLES.
  
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
 FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-04-12 Cont ID  
Sent By fmittner Date 2017-04-12 Time 09:57 Rev Time 0.00
Received By fmittner Date 2017-04-12 Time 09:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-04-21 Cont ID  
Sent By skennedy Date 2017-04-21 Time 13:55 Rev Time 0.00
Received By skennedy Date 2017-04-20 Time 10:38 Sent To  
Notes
2017-04-21 10:38:40RESUB ROUTED TO SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-19 Cont ID  
Sent By skennedy Date 2017-04-19 Time 16:43 Rev Time 0.00
Received By skennedy Date 2017-04-19 Time 16:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-12 Cont ID  
Sent By skennedy Date 2017-04-12 Time 10:08 Rev Time 0.00
Received By skennedy Date 2017-03-24 Time 10:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2017-04-12 Cont ID  
Sent By fmittner Date 2017-04-12 Time 09:57 Rev Time 0.00
Received By fmittner Date 2017-04-12 Time 09:57 Sent To  
Notes
***NONE***