Plan Review Details - Permit 17030974
Plan Review Stops For Permit 17030974
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-16 Cont ID  
Sent By cthroop Date 2017-06-16 Time 15:16 Rev Time 0.00
Received By cthroop Date 2017-06-16 Time 15:15 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-04-11 Cont ID  
Sent By cthroop Date 2017-04-11 Time 16:17 Rev Time 0.00
Received By cthroop Date 2017-04-11 Time 16:13 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-06-14 Cont ID  
Sent By jleahy Date 2017-06-14 Time 17:22 Rev Time 0.00
Received By jleahy Date 2017-06-14 Time 17:21 Sent To G
Notes
2017-06-14 17:22:42WIRE SIZE MAY BE TO SMALL FOR LOAD CONTRACTOR TO VERIFY
 JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-03-31 Cont ID  
Sent By jleahy Date 2017-03-31 Time 09:20 Rev Time 0.00
Received By jleahy Date 2017-03-31 Time 09:20 Sent To G
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-19 Cont ID  
Sent By pleduc Date 2017-06-19 Time   Rev Time 0.00
Received By pleduc Date 2017-06-19 Time 14:17 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-04-13 Cont ID  
Sent By pleduc Date 2017-04-13 Time   Rev Time 0.00
Received By pleduc Date 2017-04-12 Time 15:07 Sent To PC
Notes
2017-04-12 15:19:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET SK 1 - THERE IS AN INDICATION OF A FUEL TANK
 WHILE SHEET E 1 COMMENT NOTE # 5 INDICATES NATURAL GAS.
  
 CONFLICT, PLEASE CORRECT OR CLARIFY.
  
  
  
 2) INFORMATION REQUEST - WILL THIS GENERATOR SUPPLY
 BACK-UP POWER TO A FIRE ALARM OR OTHER LIFE SAFETY
 SYSTEM?
  
 PROVIDE APPLICABLE NOTE
  
  
  
 3) IF YES TO # 2, PLEASE ENSURE COMPLIANCE WITH NFPA
 110 STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS
 2010 EDITION
  
 PROVIDE APPLICABLE NOTE
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2017-06-16 Cont ID  
Sent By gjohnson Date 2017-06-16 Time 13:21 Rev Time 0.00
Received By gjohnson Date 2017-06-16 Time 13:21 Sent To  
Notes
2017-06-16 13:22:47GAS APPROVED UNDER PERMIT 17060362

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-04-03 Cont ID  
Sent By gjohnson Date 2017-04-03 Time 11:08 Rev Time 0.00
Received By gjohnson Date 2017-04-03 Time 11:08 Sent To  
Notes
2017-04-03 11:09:421ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-19 Cont ID  
Sent By pleduc Date 2017-06-19 Time   Rev Time 0.00
Received By pleduc Date 2017-06-09 Time 11:27 Sent To  
Notes
2017-06-12 11:27:55RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-06-12 Cont ID  
Sent By lmarchan Date 2017-06-12 Time 11:16 Rev Time 0.00
Received By lmarchan Date 2017-03-24 Time 12:57 Sent To  
Notes
2017-03-27 12:57:19ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2017-06-14 Cont ID  
Sent By njwira Date 2017-06-14 Time 11:51 Rev Time 0.00
Received By njwira Date 2017-06-12 Time 16:48 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-03-30 Cont ID  
Sent By njwira Date 2017-03-30 Time 16:43 Rev Time 0.00
Received By njwira Date 2017-03-28 Time 14:59 Sent To E
Notes
***NONE***