2017-03-30 11:14:55 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| 1. DETAIL 1-S5.001, OTHER LOCATIONS, STRUCTURAL |
| SHEATHING SHOWN. REVISE PLAN TO SHOW COMPLIANCE WITH |
| FBC B 603.1 (COMBUSTIBLES ALLOWED). |
| |
| 2. G2.001 DOES NOT ADDRESS THE SMOKE CONTROL AND/OR |
| ELEVATOR PRESSURIZATION. NO ELEVATOR LOBBIES ARE SHOWN |
| AS EXISTING OR PROPOSED AND AN ATRIUM IS SHOWN. REVISE |
| PLAN TO ADDRESS (FUNCTIONAL EXISTING SYSTEMS TO |
| REMAIN?) |
| |
| 3. G2.001 STATES THAT EXISTING OCCUPANT LOAD IS "TO |
| REMAIN." PROVIDE THE OCCUPANT LOAD, FBC 107. THIS |
| INFORMATION IS REQUIRED FOR C.O., COMPLIANCE WITH FBC |
| EB 805, FBC B CHAPTER 10. |
| |
| 4. 01-G2.001 SHOWS (EXISTING) EXITING THROUGH A LOADING |
| ZONE. FBC 107, CODE COMPLIANCE SHOULD BE CLEAR TO |
| SOMEONE UNFAMILIAR WITH THE BUILDNG. ALTHOUGH |
| "EXISTING", IT IS NOT CLEAR WHETHER EXITING THROUGH A |
| MORE HAZARDOUS AREA WAS ALLOWED WHEN THE BUILDING WAS |
| PERMITTED. REVISE PLAN TO CLARIFY. INCLUDE A NORTH |
| ARROW. IT IS NOT CLEAR IF THIS IS THE ALLEY OR ANOTHER |
| AREA WHICH IS NOT VISIBLE ON PICTOMETRY AND OTHER |
| AERIALS. |
| |
| 5. S0.00 RAILINGS, REVISE DESIGN CRITERIA TO INCLUDE |
| ALL REQUIREMENTS OF FBC B 1607.8. |
| |
| 6. THIS PERMIT WILL BE ISSUED WITH PROVISO, ENGINEERING |
| AND SHOP DRAWINGS FOR RAILINGS REQUIRED AT INSPECTION. |
| SUBJECT TO INSPECTOR'S DISCRETION, THIS MAY BE REQUIRED |
| TO BE SUBMITTED FOR PLAN REVIEW. DOR TO REVIEW |
| DELEGATED ENGINEERING AND SHOPS PRIOR TO INSPECTION |
| AND/OR SUBMITTAL. |
| |