Plan Review Details - Permit 17030927
Plan Review Stops For Permit 17030927
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-04-20 Cont ID  
Sent By shill Date 2017-04-20 Time 11:11 Rev Time 0.00
Received By shill Date 2017-04-20 Time 11:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-30 Cont ID  
Sent By shill Date 2017-03-30 Time 11:14 Rev Time 0.00
Received By shill Date 2017-03-29 Time 07:53 Sent To  
Notes
2017-03-30 11:14:55****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. DETAIL 1-S5.001, OTHER LOCATIONS, STRUCTURAL
 SHEATHING SHOWN. REVISE PLAN TO SHOW COMPLIANCE WITH
 FBC B 603.1 (COMBUSTIBLES ALLOWED).
  
 2. G2.001 DOES NOT ADDRESS THE SMOKE CONTROL AND/OR
 ELEVATOR PRESSURIZATION. NO ELEVATOR LOBBIES ARE SHOWN
 AS EXISTING OR PROPOSED AND AN ATRIUM IS SHOWN. REVISE
 PLAN TO ADDRESS (FUNCTIONAL EXISTING SYSTEMS TO
 REMAIN?)
  
 3. G2.001 STATES THAT EXISTING OCCUPANT LOAD IS "TO
 REMAIN." PROVIDE THE OCCUPANT LOAD, FBC 107. THIS
 INFORMATION IS REQUIRED FOR C.O., COMPLIANCE WITH FBC
 EB 805, FBC B CHAPTER 10.
  
 4. 01-G2.001 SHOWS (EXISTING) EXITING THROUGH A LOADING
 ZONE. FBC 107, CODE COMPLIANCE SHOULD BE CLEAR TO
 SOMEONE UNFAMILIAR WITH THE BUILDNG. ALTHOUGH
 "EXISTING", IT IS NOT CLEAR WHETHER EXITING THROUGH A
 MORE HAZARDOUS AREA WAS ALLOWED WHEN THE BUILDING WAS
 PERMITTED. REVISE PLAN TO CLARIFY. INCLUDE A NORTH
 ARROW. IT IS NOT CLEAR IF THIS IS THE ALLEY OR ANOTHER
 AREA WHICH IS NOT VISIBLE ON PICTOMETRY AND OTHER
 AERIALS.
  
 5. S0.00 RAILINGS, REVISE DESIGN CRITERIA TO INCLUDE
 ALL REQUIREMENTS OF FBC B 1607.8.
  
 6. THIS PERMIT WILL BE ISSUED WITH PROVISO, ENGINEERING
 AND SHOP DRAWINGS FOR RAILINGS REQUIRED AT INSPECTION.
 SUBJECT TO INSPECTOR'S DISCRETION, THIS MAY BE REQUIRED
 TO BE SUBMITTED FOR PLAN REVIEW. DOR TO REVIEW
 DELEGATED ENGINEERING AND SHOPS PRIOR TO INSPECTION
 AND/OR SUBMITTAL.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-04-24 Cont ID  
Sent By jleahy Date 2017-04-24 Time 09:33 Rev Time 0.00
Received By jleahy Date 2017-04-24 Time 09:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-04-03 Cont ID  
Sent By jleahy Date 2017-04-03 Time 12:00 Rev Time 0.00
Received By jleahy Date 2017-04-03 Time 12:00 Sent To  
Notes
2017-04-03 12:10:23FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
 FBC EC C405.5.2 INTERIOR LIGHTING POWER ALLOWANCES
 REQUIRED.
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 BN1165, BU1753, PX163
 561-805-6713
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-04-27 Cont ID  
Sent By scaldero Date 2017-04-27 Time 11:04 Rev Time 0.00
Received By scaldero Date 2017-04-27 Time 11:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-03-27 Cont ID  
Sent By scaldero Date 2017-03-27 Time 12:05 Rev Time 0.00
Received By scaldero Date 2017-03-27 Time 11:50 Sent To  
Notes
2017-03-27 12:05:12PERMIT # 17030927
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2017-05-01 Cont ID  
Sent By rsklarew Date 2017-05-01 Time 12:48 Rev Time 0.00
Received By rsklarew Date 2017-05-01 Time 12:48 Sent To  
Notes
2017-04-14 11:39:44C01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-06 Cont ID  
Sent By shill Date 2017-04-03 Time 14:41 Rev Time 0.00
Received By shill Date 2017-03-23 Time 10:14 Sent To  
Notes
2017-03-24 10:15:10C01

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-04-07 Cont ID  
Sent By ccole Date 2017-03-31 Time 09:23 Rev Time 0.00
Received By ccole Date 2017-03-31 Time 09:23 Sent To  
Notes
2017-03-31 09:25:22MECHANICAL PROVISO:
  
 PROVIDE TEST AND BALANCE REPORT AT FINAL INSPECTION.