2017-03-28 08:23:41 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) FBC - R301.2.1.2 PROTECTION OF OPENINGS. GLAZED |
| OPENINGS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS |
| REGIONS SHALL BE PROTECTED FROM WINDBORNE DEBRIS. |
| GLAZED OPENING PROTECTION FOR WINDBORNE DEBRIS SHALL |
| MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST OF ASTM |
| E 1996 AND ASTM E 1886 REFERENCED THEREIN, SSTD 12, TAS |
| 201, 202 AND 203 OR AAMA 506, AS APPLICABLE. FBC |
| 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR |
| THOSE PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 |
| PER FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA |
| NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM |
| DESIGN PRESSURES FOR THE REQUIRED STORM PANELS. |
| |
| 2) FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN |
| INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM |
| PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES, |
| TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL |
| LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO |
| GLASS AND THE APPLICABLE SECTION NUMBER FROM THE |
| INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE |
| CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF |
| THE RELATED FORMS INCLUDING THE SCHEDULE FOR |
| INSTALLATION OF OPENING PROTECTIVE DEVICES. |
| HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/ |
| |
| 3) PROVIDE THE FLORIDA PRODUCT APPROVAL FL NUMBER FOR |
| THE JELD-WEN EXTERIOR DOOR. FBC 107.3.4 & FAC |
| 61G20-3.001 |
| |