Plan Review Details - Permit 17030764
Plan Review Stops For Permit 17030764
Review Stop AD ADDRESSING
Rev No 2 Status N Date 2017-11-16 Cont ID  
Sent By shill Date 2017-10-19 Time 17:03 Rev Time 0.00
Received By shill Date 2017-10-19 Time 17:04 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2017-04-26 Cont ID  
Sent By shill Date 2017-04-26 Time 10:26 Rev Time 0.00
Received By shill Date 2017-04-26 Time 10:26 Sent To  
Notes
2017-04-26 10:28:29CONTACT MIKE ORIO REGARDING ADDRESS ISSUES, REAR
 BUILDING
 [email protected]
 561-494-1080
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-06-06 Cont ID  
Sent By jleahy Date 2017-06-06 Time 18:01 Rev Time 0.00
Received By jleahy Date 2017-06-06 Time 18:01 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date   Cont ID  
Sent By   Date 2017-10-19 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-13 Time 12:55 Sent To  
Notes
2017-10-16 12:56:01RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2017-07-17 Time   Rev Time 0.00
Received By cpuell Date 2017-07-13 Time 15:06 Sent To  
Notes
2017-07-14 15:06:44CCOLE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2017-06-20 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-15 Time 11:35 Sent To  
Notes
2017-06-19 11:35:34RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-06-07 Time   Rev Time 0.00
Received By lmarchan Date 2017-06-05 Time 10:38 Sent To  
Notes
2017-06-06 10:39:09RESUB ROUTED TO ELECTRICAL INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-08 Cont ID  
Sent By ccole Date 2017-05-08 Time 08:25 Rev Time 0.00
Received By ccole Date 2017-05-03 Time 10:54 Sent To  
Notes
2017-05-04 10:54:43RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-23 Cont ID  
Sent By ccole Date 2017-03-23 Time 09:35 Rev Time 0.00
Received By ccole Date 2017-03-20 Time 12:55 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2017-10-19 Cont ID  
Sent By ccole Date 2017-10-19 Time 14:34 Rev Time 0.00
Received By ccole Date 2017-10-19 Time 14:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2017-07-17 Cont ID  
Sent By ccole Date 2017-07-17 Time 10:21 Rev Time 0.00
Received By ccole Date 2017-07-17 Time 10:21 Sent To  
Notes
2017-07-17 10:42:444TH REVIEW FBC-2014 MECHANICAL
 PERMIT #17030764
 7/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE CORRECTED AC PLANS INDICATE THEY WERE DRAWN BY
 THE COMPANY THAT PREPARED THE AC CALCULATIONS- ENERGY
 HOUSE TECHNOLOGY. PLEASE NOTE THAT ENERGY HOUSE
 TECHNOLOGY CANNOT DRAW THE AC PLAN FOR THE HOUSE UNLESS
 THE COMPANY IS FL. STATE LICENSED AS AN AC OR
 MECHANICAL CONTRACTOR, AND IS THE INSTALLING CONTRACTOR
 ON THE PROJECT- SECTION 105.3.1 WEST PALM BEACH
 AMENDMENTS TO THE FBC. I PERFORMED A LICENSE SEARCH ON
 THE DPBR WEBSITE AND NO CONTRACTORS LICENSE EXISTS FOR
 EITHER ENERGY HOUSE TECHNOLOGY OR THE COMPANY OWNER
 BRUCE TSCHOSIK.
  
 2) PLEASE PROVIDE DUPLICATE COPIES OF THE AC
 CALCULATIONS FOR LEVELS 1 & 2- ONLY ONE SET WAS
 SUBMITTED.
  
 3) THE SUBMITTAL FOR THE HURRICANE PAD INDICATES AN
 INCORRECT WIND SPEED OF 150 MPH WHICH IS DEFICIENT FOR
 WEST PALM BEACH THE CORRECT ULTIMATE DESIGN WIND SPEED
 FOR RISK CATEGORY II STRUCTURES IN WPB IS 170 MPH-
 SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2017-06-20 Cont ID  
Sent By ccole Date 2017-06-20 Time 10:06 Rev Time 0.00
Received By ccole Date 2017-06-20 Time 10:06 Sent To  
Notes
2017-06-20 10:09:264TH REVIEW FBC-2014 MECHANICAL
 PERMIT #17030764
 6/20/17
  
 RESULTS: DENIED.
  
 1) THE COMPANY ENERGY HOUSE TECHNOLOGY CANNOT DRAW THE
 AC PLAN FOR THE PROJECT UNLESS THEY ARE A FL. STATE
 LICENSED AC OR MECHANICAL CONTRACTOR, AND ARE ALSO THE
 INSTALLING CONTRACTOR ON THE PROJECT- SECTION 105.3.1
 WEST PALM BEACH AMENDMENTS TO THE FBC. AS PREVIOUSLY
 REQUESTED PLEASE SUBMIT AN AC PLAN DRAWN BY EITHER A
 FL. LICENSED ENGINEER OR PHOENIX AIR LLC. PLEASE NOTE
 THAT CONTRACTOR PLANS MUST BEAR THE TITLE BLOCK OF THE
 COMPANY, AND THE CONTRACTOR'S LICENSE NUMBER AND
 SIGNATURE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-06-07 Cont ID  
Sent By ccole Date 2017-06-07 Time 08:09 Rev Time 0.00
Received By ccole Date 2017-06-07 Time 08:09 Sent To  
Notes
2017-06-07 08:12:133RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17030764
 6/7/17
  
 RESULTS: DENIED.
  
 1) COMMENTS FROM THE PREVIOUS REVIEWS STILL EXIST-
 PLEASE SEE REPRINTED COMMENTS BELOW AND COMPLY.
  
 2ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17030764
 5/8/17
  
 RESULTS: DENIED.
 PLEASE ADDRESS THE COMMENTS LISTED BELOW.
  
 1) THE ENERGY FORM R405-2014 MUST BE SIGNED AND DATED
 BY THE OWNER/AGENT.
  
 2) THE CLIMATE ZONE 2 LISTED ON FORM R405 IS INCORRECT:
 PALM BEACH COUNTY IS CLIMATE ZONE 1A- SEE TABLE R301.1
 FBC-14 ENERGY CONSERVATION.
  
 3) COMMENTS #3- #7 FROM THE1ST REVIEW STILL EXIST. SEE
 THE REPRINTED LIST BELOW:
  
 1ST REVIEW
  
 3) PROVIDE A PLAN THAT SHOWS THE LOCATIONS OF THE NEW
 AIR HANDLER AND EXTERIOR CONDENSER, AND PROVIDE AN AC
 EQUIPMENT SCHEDULE.
  
 4) REMOVE THE AC CHANGE-OUT FORM FROM THE PERMIT FILE-
 IT IS NOT APPLICABLE TO THIS PROJECT.
  
 5) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR
 HANDLER- SECTION M1411.3 FBC-14 RESIDENTIAL.
  
 6) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE
 CONDENSER PAD AND MOUNTING DETAILS FOR THE CONDENSER-
 SECTION M1305.1.4.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-05-08 Cont ID  
Sent By ccole Date 2017-05-08 Time 08:02 Rev Time 0.00
Received By ccole Date 2017-05-08 Time 08:02 Sent To  
Notes
2017-05-08 08:21:082ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17030764
 5/8/17
  
 RESULTS: DENIED.
 PLEASE ADDRESS THE COMMENTS LISTED BELOW.
  
 1) THE ENERGY FORM R405-2014 MUST BE SIGNED AND DATED
 BY THE OWNER/AGENT.
  
 2) THE CLIMATE ZONE 2 LISTED ON FORM R405 IS INCORRECT:
 PALM BEACH COUNTY IS CLIMATE ZONE 1A- SEE TABLE R301.1
 FBC-14 ENERGY CONSERVATION.
  
 3) COMMENTS #3- #7 FROM THE1ST REVIEW STILL EXIST. SEE
 THE REPRINTED LIST BELOW:
  
 1ST REVIEW
  
 3) PROVIDE A PLAN THAT SHOWS THE LOCATIONS OF THE NEW
 AIR HANDLER AND EXTERIOR CONDENSER, AND PROVIDE AN AC
 EQUIPMENT SCHEDULE.
  
 4) REMOVE THE AC CHANGE-OUT FORM FROM THE PERMIT FILE-
 IT IS NOT APPLICABLE TO THIS PROJECT.
  
 5) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR
 HANDLER- SECTION M1411.3 FBC-14 RESIDENTIAL.
  
 6) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE
 CONDENSER PAD AND MOUNTING DETAILS FOR THE CONDENSER-
 SECTION M1305.1.4.1.
  
 7) PROVIDE ELECTRICAL PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-23 Cont ID  
Sent By ccole Date 2017-03-23 Time 09:35 Rev Time 0.00
Received By ccole Date 2017-03-23 Time 09:35 Sent To  
Notes
2017-03-23 09:49:161ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030764
 3/23/17
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW MINI-SPLIT SYSTEM- SECTION R403.6.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) REFER TO SECTION R101.4.5 FBC-14 ENERGY
 CONSERVATION: THE PBC PROPERTY APPRAISOR'S REPORT FOR
 THE EXISTING RESIDENCE INDICATES BUILDING 2 HAS NO
 HEATING OR AIR CONDITIONING, THEREFORE NOW THAT IT IS
 BEING CONDITIONED, FULL COMPLIANCE WITH THE ENERGY CODE
 IS REQUIRED. PLEASE SUBMIT COMPLIANCE DOCUMENTATION AS
 OUTLINED IN SECTIONS R101.5.1.1.
  
 3) PROVIDE A PLAN THAT SHOWS THE LOCATIONS OF THE NEW
 AIR HANDLER AND EXTERIOR CONDENSER, AND PROVIDE AN AC
 EQUIPMENT SCHEDULE.
  
 4) REMOVE THE AC CHANGE-OUT FORM FROM THE PERMIT FILE-
 IT IS NOT APPLICABLE TO THIS PROJECT.
  
 5) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR
 HANDLER- SECTION M1411.3 FBC-14 RESIDENTIAL.
  
 6) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE
 CONDENSER PAD AND MOUNTING DETAILS FOR THE CONDENSER-
 SECTION M1305.1.4.1.
  
 7) PROVIDE ELECTRICAL PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  