Plan Review Details - Permit 17030757
Plan Review Stops For Permit 17030757
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-24 Cont ID  
Sent By vperez Date 2017-03-24 Time 10:37 Rev Time 0.00
Received By vperez Date 2017-03-24 Time 10:37 Sent To  
Notes
2017-03-24 10:38:16SEE NOTE REGARDING SMOKE DETECTORS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-21 Cont ID  
Sent By vperez Date 2017-03-21 Time 09:05 Rev Time 0.00
Received By vperez Date 2017-03-21 Time 09:05 Sent To  
Notes
2017-03-21 09:08:47PLEASE CLARIFY IF HOT TUB IS NEW? IF SO A REVISED LOAD
 CALCULATION WILL NEE TO BE SUBMITTED. ALSO WHAT IS THE
 MAIN BREAKER SIZE?
  
 GFCI PROTECTION REQUIRED FOR HOT TUB. PROVIDE A NOTE
 AND BREAKER SIZE FEEDING THIS UNIT
  
 PER FBC RES 315 WHEN A PERMIT OCCURS AT A RESIDENCE
 SMOKE DETECTORS ARE TO BE INSTALLED IF NOT EXISTING.
 PLEASE NOTE ON PLANS IF THE ARE EXISTING..
  
 V. PEREZ
 *6717

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-24 Cont ID  
Sent By vperez Date 2017-03-24 Time 10:38 Rev Time 0.00
Received By vperez Date 2017-03-24 Time 10:38 Sent To  
Notes
2017-03-23 11:15:45RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-21 Cont ID  
Sent By vperez Date 2017-03-21 Time 09:08 Rev Time 0.00
Received By vperez Date 2017-03-21 Time 09:08 Sent To  
Notes
2017-03-20 11:27:53ELEC -$5000