Plan Review Details - Permit 17030741
Plan Review Stops For Permit 17030741
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-03-27 Cont ID  
Sent By jgomez Date 2017-03-27 Time 19:43 Rev Time 0.00
Received By jgomez Date 2017-03-27 Time 19:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-20 Cont ID  
Sent By jgomez Date 2017-03-20 Time 11:33 Rev Time 0.00
Received By jgomez Date 2017-03-20 Time 11:29 Sent To  
Notes
2017-03-20 11:39:44RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) AS REQUIRED BY GENERAL LIMITATION #7 ON LAST
 PAGE OF NOA 14-1030.02 SUBMITTED. NEED THE CALCULATIONS
 TO MEET THE DESIGN PRESSURES AT PERIMETER AND CORNER
 AREAS REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-27 Cont ID  
Sent By jgomez Date 2017-03-27 Time 19:43 Rev Time 0.00
Received By jgomez Date 2017-03-24 Time 13:09 Sent To  
Notes
2017-03-27 13:09:29RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-20 Cont ID  
Sent By jgomez Date 2017-03-20 Time 11:39 Rev Time 0.00
Received By jgomez Date 2017-03-17 Time 08:54 Sent To  
Notes
2017-03-20 08:54:43JGOMEZ'S DESK