Plan Review Details - Permit 17030699
Plan Review Stops For Permit 17030699
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-03-21 Cont ID  
Sent By pleduc Date 2017-03-21 Time   Rev Time 0.00
Received By pleduc Date 2017-03-21 Time 12:13 Sent To M
Notes
2017-03-21 12:18:33THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) TEST AT 200 PSI FOR 2 HOURS PER NFPA 13.
  
 24.2 ACCEPTANCE REQUIREMENTS.
 24.2.1* HYDROSTATIC TESTS.
 24.2.1.1 UNLESS PERMITTED BY 24.2.1.2 THROUGH 24.2.1.8,
 ALL PIPING AND ATTACHED APPURTENANCES SUBJECTED TO
 SYSTEM WORKING PRESSURE SHALL BE HYDROSTATICALLY TESTED
 AT 200 PSI (13.8 BAR) AND SHALL MAINTAIN THAT PRESSURE
 WITHOUT LOSS FOR 2 HOURS.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-23 Cont ID  
Sent By ccole Date 2017-03-23 Time 12:10 Rev Time 0.00
Received By ccole Date 2017-03-16 Time 12:46 Sent To  
Notes
2017-03-17 12:46:48ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-03-23 Cont ID  
Sent By ccole Date 2017-03-23 Time 12:10 Rev Time 0.00
Received By ccole Date 2017-03-23 Time 12:10 Sent To  
Notes
***NONE***