Plan Review Details - Permit 17030678
Plan Review Stops For Permit 17030678
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-04-28 Cont ID  
Sent By ccole Date 2017-04-28 Time 09:29 Rev Time 0.00
Received By ccole Date 2017-04-21 Time 12:33 Sent To  
Notes
2017-04-24 12:34:00RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-17 Cont ID  
Sent By ccole Date 2017-04-17 Time 16:34 Rev Time 0.00
Received By ccole Date 2017-04-10 Time 13:30 Sent To  
Notes
2017-04-11 13:30:53RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-23 Cont ID  
Sent By ccole Date 2017-03-23 Time 08:30 Rev Time 0.00
Received By ccole Date 2017-03-16 Time 11:00 Sent To  
Notes
2017-03-17 11:01:02ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-04-28 Cont ID  
Sent By ccole Date 2017-04-28 Time 09:29 Rev Time 0.00
Received By ccole Date 2017-04-28 Time 09:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-04-17 Cont ID  
Sent By ccole Date 2017-04-17 Time 16:18 Rev Time 0.00
Received By ccole Date 2017-04-17 Time 16:18 Sent To  
Notes
2017-04-17 16:34:513RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17030678
 4/17/17
  
 1) TWO SETS OF ENERGY AND AC CALCULATIONS ARE REQUIRED
 PER SECTION 107.1 WPB AMENDMENTS TO THE FBC. ONLY ONE
 SET OF EACH WAS SUBMITTED.
  
 2) THE SUBMITTED ENERGY CALCULATION FORM R405-2014 WAS
 NOT SIGNED AND DATED BY THE PERSON WHO PREPARED THE
 CALCULATION, AND BY THE OWNER. THE BUILDER'S OR
 CONTRACTOR'S NAME AND PERMIT OFFICE MUST BE ENTERED IN
 THE TOP RIGHT HAND COLUMN OF THE DOCUMENT.
  
 3) THE CONTRACTOR MUST PROVIDE A SIGNATURE ON THE AC
 LAYOUT PLANS PER SECTION 107.2.1.
  
 4) THE SUBMITTAL FOR THE HURRICANE PAD IS UNACCEPTABLE
 BECAUSE THE PRINT IS SO FAINT IT IS BARELY LEGIBLE. IN
 ADDITION TWO COPIES ARE REQUIRED- ONLY ONE WAS
 SUBMITTED.
  
 5) PLEASE CLARIFY WHY AN NOA FOR A ROOF STAND IS
 SUBMITTED. THE PLANS SHOW THE CODENSER IS TO BE
 GROUND-MOUNTED.
  
 6) AS NOTED IN THE PREVIOUS REVIEW, THE BEDROOM
 TRANSFER GRILLS ARE UNDERSIZED- A MINIMUM OF 75 SQ.
 INCHES IS REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-23 Cont ID  
Sent By ccole Date 2017-03-23 Time 08:30 Rev Time 0.00
Received By ccole Date 2017-03-23 Time 08:30 Sent To Z
Notes
2017-03-23 08:55:291ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030678
 3/23/17
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW TRANE SYSTEM- SECTION R403.6.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) REFER TO SECTION R101.4.5 FBC-14 ENERGY
 CONSERVATION: THE PBC PROPERTY APPRAISOR'S REPORT FOR
 THE EXISTING RESIDENCE INDICATES NO HEATING OR AIR
 CONDITIONING, THEREFORE NOW THAT IT IS BEING
 CONDITIONED, FULL COMPLIANCE WITH THE ENERGY CODE IS
 REQUIRED. PLEASE SUBMIT COMPLIANCE DOCUMENTATION AS
 OUTLINED IN SECTIONS R101.5.1.1.
  
 3) IT APPEARS BY THE DRAWING THAT THE AIR HANDLER IS IN
 THE ATTIC. PLEASE SECTION R403.2.4 FBC-14 ENERGY AND
 SHOW COMPLIANCE WITH ITEMS 1-4.
  
 4) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR
 HANDLER- SECTION M1411.3 FBC-14 RESIDENTIAL.
  
 5) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE
 CONDENSER PAD AND MOUNTING DETAILS FOR THE CONDENSER-
 SECTION M1305.1.4.1.
  
 6) PLEASE LABEL ALL ROOMS AND SPACES ON THE DUCT LAYOUT
 PLAN.
  
 7) THE 12X4" RETURN TRANSFER GRILLS FOR THE BEDROOMS
 ARE UNDERSIZED PER SECTION M1602.4- 50 SQ. INCHES OF
 FREE AIR PER 100 CFMS REQUIRED.
  
 8) PROVIDE ELECTRICAL PLANS.
  
 9) BECAUSE OF THE NEW EXTERIOR CONDENSER INSTALLATION,
 THE PLAN HAS BEEN FORWARDED TO PLANNING AND ZONING FOR
 REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2017-04-28 Cont ID  
Sent By njwira Date 2017-04-28 Time 09:30 Rev Time 0.00
Received By njwira Date 2017-04-25 Time 15:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-04-14 Cont ID  
Sent By njwira Date 2017-04-14 Time 17:47 Rev Time 0.00
Received By njwira Date 2017-04-11 Time 16:17 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-03-27 Cont ID  
Sent By njwira Date 2017-03-27 Time 17:14 Rev Time 0.00
Received By njwira Date 2017-03-24 Time 14:16 Sent To I
Notes
2017-03-27 17:14:373/27/17- FAILED
  
 PLEASE PROVIDE TWO(2)COPIES OF A SURVEY SHOWING WHERE
 THE MECHANICAL EQUIPMENT WILL BE LOCATED IN RELATION TO
 REQUIRED SETBACKS.
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442