Plan Review Details - Permit 17030678
Plan Review Stops For Permit 17030678 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2017-04-28 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-04-28 |
Time |
09:29 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-04-21 |
Time |
12:33 |
Sent To |
|
|
Notes |
2017-04-24 12:34:00 | RESUB ROUTED TO NJWIRA VIA ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2017-04-17 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-04-17 |
Time |
16:34 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-04-10 |
Time |
13:30 |
Sent To |
|
|
Notes |
2017-04-11 13:30:53 | RESUB ROUTED TO NJWIRA VIA ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-03-23 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-03-23 |
Time |
08:30 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-03-16 |
Time |
11:00 |
Sent To |
|
|
Notes |
2017-03-17 11:01:02 | ROUTED TO MECHANICAL INBOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2017-04-28 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-04-28 |
Time |
09:29 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-04-28 |
Time |
09:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2017-04-17 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-04-17 |
Time |
16:18 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-04-17 |
Time |
16:18 |
Sent To |
|
|
Notes |
2017-04-17 16:34:51 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #17030678 | | 4/17/17 | | | | 1) TWO SETS OF ENERGY AND AC CALCULATIONS ARE REQUIRED | | PER SECTION 107.1 WPB AMENDMENTS TO THE FBC. ONLY ONE | | SET OF EACH WAS SUBMITTED. | | | | 2) THE SUBMITTED ENERGY CALCULATION FORM R405-2014 WAS | | NOT SIGNED AND DATED BY THE PERSON WHO PREPARED THE | | CALCULATION, AND BY THE OWNER. THE BUILDER'S OR | | CONTRACTOR'S NAME AND PERMIT OFFICE MUST BE ENTERED IN | | THE TOP RIGHT HAND COLUMN OF THE DOCUMENT. | | | | 3) THE CONTRACTOR MUST PROVIDE A SIGNATURE ON THE AC | | LAYOUT PLANS PER SECTION 107.2.1. | | | | 4) THE SUBMITTAL FOR THE HURRICANE PAD IS UNACCEPTABLE | | BECAUSE THE PRINT IS SO FAINT IT IS BARELY LEGIBLE. IN | | ADDITION TWO COPIES ARE REQUIRED- ONLY ONE WAS | | SUBMITTED. | | | | 5) PLEASE CLARIFY WHY AN NOA FOR A ROOF STAND IS | | SUBMITTED. THE PLANS SHOW THE CODENSER IS TO BE | | GROUND-MOUNTED. | | | | 6) AS NOTED IN THE PREVIOUS REVIEW, THE BEDROOM | | TRANSFER GRILLS ARE UNDERSIZED- A MINIMUM OF 75 SQ. | | INCHES IS REQUIRED. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2017-03-23 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-03-23 |
Time |
08:30 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-03-23 |
Time |
08:30 |
Sent To |
Z |
|
Notes |
2017-03-23 08:55:29 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17030678 | | 3/23/17 | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | NEW TRANE SYSTEM- SECTION R403.6.1 FBC-14 ENERGY | | CONSERVATION. | | | | 2) REFER TO SECTION R101.4.5 FBC-14 ENERGY | | CONSERVATION: THE PBC PROPERTY APPRAISOR'S REPORT FOR | | THE EXISTING RESIDENCE INDICATES NO HEATING OR AIR | | CONDITIONING, THEREFORE NOW THAT IT IS BEING | | CONDITIONED, FULL COMPLIANCE WITH THE ENERGY CODE IS | | REQUIRED. PLEASE SUBMIT COMPLIANCE DOCUMENTATION AS | | OUTLINED IN SECTIONS R101.5.1.1. | | | | 3) IT APPEARS BY THE DRAWING THAT THE AIR HANDLER IS IN | | THE ATTIC. PLEASE SECTION R403.2.4 FBC-14 ENERGY AND | | SHOW COMPLIANCE WITH ITEMS 1-4. | | | | 4) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR | | HANDLER- SECTION M1411.3 FBC-14 RESIDENTIAL. | | | | 5) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE | | CONDENSER PAD AND MOUNTING DETAILS FOR THE CONDENSER- | | SECTION M1305.1.4.1. | | | | 6) PLEASE LABEL ALL ROOMS AND SPACES ON THE DUCT LAYOUT | | PLAN. | | | | 7) THE 12X4" RETURN TRANSFER GRILLS FOR THE BEDROOMS | | ARE UNDERSIZED PER SECTION M1602.4- 50 SQ. INCHES OF | | FREE AIR PER 100 CFMS REQUIRED. | | | | 8) PROVIDE ELECTRICAL PLANS. | | | | 9) BECAUSE OF THE NEW EXTERIOR CONDENSER INSTALLATION, | | THE PLAN HAS BEEN FORWARDED TO PLANNING AND ZONING FOR | | REVIEW. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2017-04-28 |
|
|
Cont ID |
|
Sent By |
njwira |
Date |
2017-04-28 |
Time |
09:30 |
Rev Time |
0.00 |
Received By |
njwira |
Date |
2017-04-25 |
Time |
15:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2017-04-14 |
|
|
Cont ID |
|
Sent By |
njwira |
Date |
2017-04-14 |
Time |
17:47 |
Rev Time |
0.00 |
Received By |
njwira |
Date |
2017-04-11 |
Time |
16:17 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2017-03-27 |
|
|
Cont ID |
|
Sent By |
njwira |
Date |
2017-03-27 |
Time |
17:14 |
Rev Time |
0.00 |
Received By |
njwira |
Date |
2017-03-24 |
Time |
14:16 |
Sent To |
I |
|
Notes |
2017-03-27 17:14:37 | 3/27/17- FAILED | | | | PLEASE PROVIDE TWO(2)COPIES OF A SURVEY SHOWING WHERE | | THE MECHANICAL EQUIPMENT WILL BE LOCATED IN RELATION TO | | REQUIRED SETBACKS. | | | | | | PLEASE CONTACT | | NATHAN WIRA- ZONING TECHNICIAN | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING | | DIVISION | | CITY OF WEST PALM BEACH | | 401 CLEMATIS ST. | | WEST PALM BEACH, FL 33402 | | OFFICE HOURS: M-F 8AM - 5PM | | (561)822-1442 | | [email protected] | | |
|
|
|