Plan Review Details - Permit 17030643
Plan Review Stops For Permit 17030643
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-04-14 Cont ID  
Sent By shill Date 2017-04-14 Time 14:35 Rev Time 0.00
Received By shill Date 2017-04-14 Time 14:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-23 Cont ID  
Sent By shill Date 2017-03-23 Time 16:45 Rev Time 0.00
Received By shill Date 2017-03-23 Time 16:39 Sent To  
Notes
2017-03-23 16:46:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. ADDRESS MECHANICAL COMMENTS (SMOKE CONTROL); FBC
 107.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-04-10 Cont ID  
Sent By shill Date 2017-04-14 Time 14:35 Rev Time 0.00
Received By jleahy Date 2017-04-10 Time 16:12 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-03-22 Cont ID  
Sent By jleahy Date 2017-03-22 Time 16:14 Rev Time 0.00
Received By jleahy Date 2017-03-22 Time 16:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-03-21 Cont ID  
Sent By pleduc Date 2017-03-21 Time   Rev Time 0.00
Received By pleduc Date 2017-03-21 Time 12:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-14 Cont ID  
Sent By shill Date 2017-04-14 Time 14:35 Rev Time 0.00
Received By shill Date 2017-04-07 Time 10:32 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-23 Cont ID  
Sent By shill Date 2017-03-23 Time 16:49 Rev Time 0.00
Received By shill Date 2017-03-15 Time 13:39 Sent To  
Notes
2017-03-16 13:40:06B10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-03-23 Cont ID  
Sent By shill Date 2017-03-23 Time 16:39 Rev Time 0.00
Received By shill Date 2017-03-23 Time 16:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-04-11 Cont ID  
Sent By ccole Date 2017-04-11 Time 16:29 Rev Time 0.00
Received By ccole Date 2017-04-11 Time 16:29 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-21 Cont ID  
Sent By ccole Date 2017-03-21 Time 16:27 Rev Time 0.00
Received By ccole Date 2017-03-21 Time 16:27 Sent To  
Notes
2017-03-21 16:37:051ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030643
 3/21/17
  
 1) M-1: THE PLAN IS INDICATING AN ALTERATION TO AN
 EXISTING SMOKE CONTROL SYSTEM HOWEVER IT DOES NOT
 APPEAR THAT THE CORRIDORS ARE ENCLOSED WITH PROPERLY
 CONSTRUCTED SMOKE BARRIERS IN ACCORDANCE WITH SECTIONS
 709 AND 909.5 FBC-14 BUILDING. PLEASE INDICATE THE
 MINIMUM PRESSURE DIFFERENCE REQUIRED ACROSS THE SMOKE
 BARRIER AND CLARIFY IF A RATIONAL ANALYSIS WAS USED TO
 ESTABLISH THE REQUIRED PRESSURES, AND TO ALSO SIZE THE
 DUCTS AND DIFFUSERS PROVIDING THE AIR- SEE SECTIONS
 909.4 AND 909.6.
  
 2) M-1: THE PLAN SHOWS SOME INCONSISTENCIES IN FLEX
 DUCT SIZING FOR THE DIFFUSERS SUPPLYING 250 AND 225
 CFMS. IN SOME ROOMS AND SPACES AN 8" DUCT IS USED, AND
 IN OTHERS A 10" DUCT.
  
 3) THE ENERGY FORM C402 MUST BE SIGNED AND DATED BY THE
 OWNER/AGENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-03-17 Cont ID  
Sent By gjohnson Date 2017-03-17 Time 10:55 Rev Time 0.00
Received By gjohnson Date 2017-03-17 Time 10:05 Sent To  
Notes
***NONE***