Plan Review Details - Permit 17030300
Plan Review Stops For Permit 17030300
Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-03-31 Cont ID  
Sent By ccole Date 2017-03-31 Time 07:58 Rev Time 0.00
Received By ccole Date 2017-03-29 Time 13:25 Sent To  
Notes
2017-03-30 13:25:44RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-03-27 Cont ID  
Sent By ccole Date 2017-03-27 Time 07:35 Rev Time 0.00
Received By ccole Date 2017-03-23 Time 11:42 Sent To  
Notes
2017-03-24 11:42:40RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-03-23 Cont ID  
Sent By ccole Date 2017-03-23 Time 07:59 Rev Time 0.00
Received By ccole Date 2017-03-21 Time 10:49 Sent To  
Notes
2017-03-22 10:51:19RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-16 Cont ID  
Sent By ccole Date 2017-03-16 Time 16:44 Rev Time 0.00
Received By ccole Date 2017-03-15 Time 10:27 Sent To  
Notes
2017-03-16 10:27:19RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-14 Cont ID  
Sent By ccole Date 2017-03-14 Time 08:46 Rev Time 0.00
Received By ccole Date 2017-03-08 Time 13:51 Sent To  
Notes
2017-03-09 13:51:42ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2017-03-31 Cont ID  
Sent By ccole Date 2017-03-31 Time 07:58 Rev Time 0.00
Received By ccole Date 2017-03-31 Time 07:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2017-03-27 Cont ID  
Sent By ccole Date 2017-03-27 Time 07:22 Rev Time 0.00
Received By ccole Date 2017-03-27 Time 07:07 Sent To  
Notes
2017-03-27 07:35:334TH REVIEW FBC-2014 MECHANICAL
 PERMIT #17030300
 3/27/17
  
 1) PLEASE REVIEW COMMENT #1 FROM THE 3RD REVIEW WHICH
 CLEARLY STATES THAT ALL PLANS SHALL BEAR THE SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. THE SUBMITTED
 PLAN FROM JOHN A. PETREIKIS MUST ALSO BEAR A VALID FL.
 ENGINEER'S SEAL- SEE SECTION 61G15 23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-03-22 Cont ID  
Sent By ccole Date 2017-03-22 Time 17:10 Rev Time 0.00
Received By ccole Date 2017-03-22 Time 17:03 Sent To  
Notes
2017-03-22 17:19:043RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17030300
 3/22/17
  
 1) THE COOLING TOWER REPLACEMENT IS NOT PART OF THE
 SCOPE OF WORK FOR THIS PROJECT. PLEASE PROVIDE A PLAN
 THAT SPECIFICALLY ADDRSSES THE ROOF FANS ONLY. PLEASE
 NOTE THAT ALL PLANS MUST BEAR THE SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1 WPB
 AMENDMENTS TO THE FBC.
  
 2) IN LIEU OF SITE SPECIFIC ENGINEERING, THE NOA FOR
 THE ROOF FANS HAS BEEN SUBMITTED, HOWEVER THE DOCUMENT
 HAS NOT BEEN MARKED UP OR HIGHLIGHTED TO SHOW THE
 APPLICABLE INSTALLATION DETAILS FOR THE PROPOSED FAN
 AND CURB INSTALLATIONS- PLEASE COMPLY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-03-16 Cont ID  
Sent By ccole Date 2017-03-16 Time 16:17 Rev Time 0.00
Received By ccole Date 2017-03-16 Time 16:17 Sent To  
Notes
2017-03-16 16:39:242ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17030300
 3/16/17
  
 1) PROVIDE LEGIBLE COPIES OF THE NOA #16-0209.05 THAT
 HAVE BEEN MARKED UP TO SHOW WHICH OF G SERIES FANS AND
 CURBS ARE TO BE INSTALLED, AND WHICH FASTENERS AND THE
 NUMBER OF EACH WILL BE USED TO ATTACH THE FANS TO THE
 CURBS, AND THE CURBS TO THE ROOF STRUCTURE. IF UNABLE
 TO PROVIDE THE ACCURATE INSTALLATION INFORMATION PER
 THE NOA, THEN PROVIDE WIND LOAD ENGINEERING BY A FL.
 LICENSE DESIGN PROFESSIONAL- SEE SECTION 301.15 FBC-14
 MECHANICAL, AND SECTION 1609 FBC-14 BUILDING.
  
 2) AS PREVIOUSLY REQUESTED PROVIDE A ROOF PLAN SHOWING
 THE LOCATIONS OF THE FANS. THE COPIED FOUR JAYS
 CONSULTING PLAN FOR INSTALLATION OF THE COOLING TOWER
 IS NOT LEGIBLE AND NOT TO MINIMUM 1/8" SCALE AS
 REQUIRED BY SECTION 107.2.1 WPB AMENDMENTS TO THE FBC.
  
 3) PLEASE NOTE PER SECTION 107.1 THAT ALL PLANS, SPECS,
 NOA'S ETC. SHALL BE SUBMITTED IN DUPLICATE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-14 Cont ID  
Sent By ccole Date 2017-03-14 Time 08:46 Rev Time 0.00
Received By ccole Date 2017-03-14 Time 08:46 Sent To  
Notes
2017-03-14 08:55:111ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030300
 3/14/17
  
 1) SUBMIT THE NOA'S FOR THE FANS AND PROVIDE WIND LOAD
 ENGINEERING FOR ATTACHMENT OF THE CURBS AND FANS TO THE
 ROOF STRUCTURE- SECTION 301.15.
  
 2) PROVIDE A ROOF PLAN SHOWING THE LOCATIONS OF ALL
 FANS AND IDENTIFY THEIR USES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  