Plan Review Details - Permit 17030213
Plan Review Stops For Permit 17030213
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-06-07 Cont ID  
Sent By shill Date 2017-06-07 Time 10:10 Rev Time 0.00
Received By shill Date 2017-06-07 Time 06:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-05-30 Cont ID  
Sent By shill Date 2017-05-30 Time 18:28 Rev Time 0.00
Received By shill Date 2017-05-30 Time 18:28 Sent To  
Notes
2017-06-07 06:47:37IMAGE OF SIGNATURE NOT AN ISSUE PER FBPE
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-04 Cont ID  
Sent By shill Date 2017-04-04 Time 12:54 Rev Time 0.00
Received By shill Date 2017-04-04 Time 10:00 Sent To  
Notes
2017-04-04 12:54:334/4/17 ****PENDING RESPONSE FROM FBPE**** AN EMAIL WAS
 SENT TO FBPE REGARDING THE IMAGE OF THE ENGINEER'S
 SIGNATURE ON THE DIGITAL PLAN PAGES. PER FBPE IN
 PREVIOUS CONVERSATIONS, THIS IS NOT PERMITTED PER
 FAC61G15-23. THEREFORE I SENT AN INQUIRY FOR
 CLARIFICATION.
  
 5/30/17: THE RESPONSE FROM FBPE VIA TELEPHONE: NO, AN
 IMAGE OF A SIGNATURE IS NOT CURRENTLY PERMITTED PER
 FAC61G15-23. HOWEVER, FBPE IS IN THE PROCESS OF
 AMENDING THIS SECTION SO THAT THE IMAGE IS ALLOWED.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-04-17 Cont ID  
Sent By vperez Date 2017-04-17 Time 08:11 Rev Time 0.00
Received By vperez Date 2017-04-17 Time 08:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-08 Cont ID  
Sent By wjolin Date 2017-06-08 Time 09:27 Rev Time 0.00
Received By wjolin Date 2017-06-08 Time 09:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-04-05 Cont ID  
Sent By wjolin Date 2017-04-05 Time 14:00 Rev Time 0.00
Received By wjolin Date 2017-04-05 Time 13:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-27 Cont ID  
Sent By hmoser Date 2017-06-27 Time 10:16 Rev Time 0.00
Received By hmoser Date 2017-06-06 Time 16:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-16 Cont ID  
Sent By lmarchan Date 2017-05-16 Time 15:54 Rev Time 0.00
Received By lmarchan Date 2017-03-31 Time 16:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-06-27 Cont ID  
Sent By hmoser Date 2017-06-27 Time 10:16 Rev Time 0.00
Received By hmoser Date 2017-06-27 Time 10:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-05-16 Cont ID  
Sent By hmoser Date 2017-05-16 Time 10:26 Rev Time 0.00
Received By hmoser Date 2017-05-16 Time 09:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-06-20 Cont ID  
Sent By tklarge Date 2017-06-20 Time 09:07 Rev Time 0.00
Received By tklarge Date 2017-06-20 Time 09:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-06-13 Cont ID  
Sent By tklarge Date 2017-06-13 Time 04:43 Rev Time 0.00
Received By tklarge Date 2017-06-13 Time 03:57 Sent To  
Notes
2017-06-13 04:41:021) SUBMIT A COMPLETE WATER AND SANITARY RISER DIAGRAM
 FOR THE COMBINED UNIT "F".WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 2) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF "UNIT
 F". I LOOKED AT ALL THE FLOOR PLANS SUBMITTED ON THE
 ARCHITECTURAL SHEETS FOR THIS REVISION AND COULD NOT
 FIND ONE THAT SHOWED THE LOCATION OF THIS UNIT.IT IS
 VERY CONFUSING. WPB AMEND. TO FBC SEC. 107.2.1.WHAT
 UNITS/AREAS WERE COMBINED TO FORM UNIT F? INDICATE ON
 THE ENLARGED PLANS FOR UNIT F. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-05-04 Cont ID  
Sent By tklarge Date 2017-05-04 Time 05:44 Rev Time 0.00
Received By tklarge Date 2017-04-28 Time 11:07 Sent To  
Notes
2017-04-28 11:08:201) SUBMIT AN EXPLANATION AS TO THE EXACT CHANGES THAT
 WERE DONE TO THE PLUMBING SHEETS ON THE SUMMARY OF
 ITEMS DOCUMENT THAT WAS SUBMITTED.WPB AMEND. TO FBC
 SEC. 107.2.1
 2) .SUBMIT REVISED SANITARY AND WATER RISER DIAGRAMS
 FOR ALL CHANGES MADE TO THE PLUMBING SYSTEMS UNDER THIS
 REVISION. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 3) SUBMIT AN EXPLANATION AS TO THE EXACT CHANGES THAT
 WERE DONE TO THE DRAINAGE SYSTEM ON SHT.# C103.
 4) THE SUBMITTED NARRRATIVE FOR THIS REVISION PROVIDES
 NO CLEAR EXPLANATION AS TO THE CHANGES THAT HAVE BEEN
 DONE TO EACH SHEET. PROVIDE A NARRATIVE THAT CLEALY
 DESCRIBES THE CHANGES THAT HAVE BEEN MADE TO EACH PLAN
 AND THOSE CHANGES SHALL BE CLEARLY IDENTIFIED ON THE
 PLANS.WPB AMEND. TO FBC SEC. 107.2.1.
 5) PLACE INFORMATION ON THE ARCHITECTURAL PLANS THAT
 THIS IS PHASE ONE OF THE PROJECT. WPB AMEND. TO FBC
 SEC. 107.2.1.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE SOLIDS
 INTERCEPTOR. WPB AMEND. TO FBC SEC. 107.2.1.
 7) SHT. P413 - THE SINK AT THE OUTDOOR KITCHEN SHALL
 DISCHARGE INDIRECTLY TO THE GI-2 INTERCEPTOR PER 2010
 FBC SEC.802.1.8.
 8) SHT. P413 - KITCHEN EQUIPMENT (ICE, COFFEE, STEAMER,
 BEVERAGE DISPENSER) SHALL BE EQUIPPED WITH BACKFLOW
 PREVENTERS PER 2010 FBC-PLUMBING SECS.608.16.1,
 608.16.10.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2017-06-27 Cont ID  
Sent By shill Date 2017-06-07 Time 08:57 Rev Time 0.00
Received By shill Date 2017-06-07 Time 08:57 Sent To  
Notes
2017-06-07 08:59:20SAMANTHA HILL
 561-805-6724
 [email protected]
  
 ALL SHEETS, ALL TRADES HAVE BEEN VERIFIED AND COMPLY
 WITH FS471 / FS481.
  
 AFTER ALL PLAN REVIEWS ARE COMPLETE:
  
 IF ALL REVIEWS PASS, CONTACT ME TO CHANGE "FAIL" STATUS
 TO "PASS".
  
 IF ANY REVIEWS FAIL PLAN REVIEW, A NEW SIGNATURE REVIEW
 IS REQUIRED IN THE NEXT REVIEW CYCLE FOR NEW SHEETS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2017-05-25 Cont ID  
Sent By shill Date 2017-05-25 Time 14:36 Rev Time 0.00
Received By shill Date 2017-04-17 Time 08:14 Sent To  
Notes
2017-05-25 14:44:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 A SHEETS OK
 E SHEETS OK PER V.PEREZ
 FP201A, FP201B, POSSIBLY OTHER SHEETS - SHEETS HAVE AN
 ERROR; THE SIGNATURE IS CORRUPTED (AARON LEE JOHNSON,
 PE), CHECK ALL
 P101B, P102A, POSSIBLY OTHER SHEETS - SHEETS HAVE AN
 ERROR; SIGNATURE IS CORRUPTED (AARON LEE JOHNSON, PE),
 CHECK ALL
 M203A, POSSIBLY OTHER SHEETS - SHEETS HAVE AN ERROR;
 SIGNATURE CORRUPTED
 T SHEETS (DENNIS O DAVIS, PE) OK
  
  
  
  
2017-04-17 08:15:14ELEC SHEETS OK

Review Stop Z ZONING
Rev No 2 Status P Date 2017-06-15 Cont ID  
Sent By eschneid Date 2017-06-15 Time 12:05 Rev Time 1.00
Received By eschneid Date 2017-06-15 Time 11:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-05-16 Cont ID  
Sent By eschneid Date 2017-05-16 Time 14:05 Rev Time 2.00
Received By eschneid Date 2017-05-16 Time 14:05 Sent To  
Notes
***NONE***